VTS VENTUS PRO PVS 37x37 [14/25] 10 6 8

VTS VENTUS PRO PVS 34x34 [14/25] 10 6 8
1. Direct Expansion
2. Condanser
3. Heat Pipe
4. Hot Water
5. Supply Fan
6. Exhaust Fan
7. Compressor
8. Filter
9. Damper
10. Control Panel
PVS PO AC
PVS PO
25
PVS PO
30
PVS PO
36
PVS PO
50
PVS PO
60
PVS PO
70
PVS PO
80
PVS PO
100
PVS PO
120
PVS PO
150
PVS PO
180
PVS PO
200
PVS PO
230
PVS PO
250
PVS PO
300
Pool
Surface Area
61 73 88 122 146 171 195 244 293 366 439 488 562 610 732
Dehumidication
Capacity
kg/h 18 21 25 35 42 50 57 71 85 106 127 142 163 177 212
Air Flow m³/h 2500 3000 3600 5000 6000 7000 8000 10000 12000 15000 18000 20000 23000 25000 30000
Cooling Capacity kW 13,5 14,5 18,2 24 29 35 39 47 58 70 80 90 110 124 154
Hot Water Capacity
(90-70 °C)
kW 26 30 36 48 57 63 78 96 113 147 162 185 222 233 279
Compressor Type
(R407C)
Scroll
Compressor
Quantity
adet 1 1 1 2 2 1 2 2 2 2 3 3 3 2 2
Compressor Power kW 4,5 4,1 5,7 6,4 8,3 10,3 10,4 13,4 17 20,4 22,7 25 30 33,4 41,8
Supply Fan
External Pressure
Pa 300
Exhaust Fan
External Pressure
Pa 300
Supply Fan
Motor Power
kW 1,1 1,1 1,1 1,5 2,2 2,2 3 3 3 4 7,5 7,5 7,5 7,5 11
Exhaust Fan
Motor Power
kW 0,75 0,75 0,75 1,1 1,5 2,2 2,2 4 4 4 5,5 7,5 7,5 7,5 7,5
PVS PO EC
PVS PO
25
PVS PO
30
PVS PO
36
PVS PO
50
PVS PO
60
PVS PO
70
PVS PO
80
PVS PO
100
PVS PO
120
PVS PO
150
PVS PO
180
PVS PO
200
PVS PO
230
PVS PO
250
PVS PO
300
Pool
Surface Area
61 73 88 122 146 171 195 244 293 366 439 488 562 610 732
Dehumidification
Capacity
kg/h 18 21 25 35 42 50 57 71 85 106 127 142 163 177 212
Air Flow m³/h 2500 3000 3600 5000 6000 7000 8000 10000 12000 15000 18000 20000 23000 25000 30000
Cooling Capacity kW 13,5 14,5 18,2 24 29 35 39 47 58 70 80 90 110 124 154
Hot Water
Capacity
(90-70 °C)
kW 26 30 36 48 57 63 78 96 113 147 162 185 222 233 279
Compressor Type
(R407C)
Scroll
Compressor
Quantity
adet 1 1 1 2 2 1 2 2 2 2 3 3 3 2 2
Compressor
Power
kW 4,5 4,1 5,7 6,4 8,3 10,3 10,4 13,4 17,0 20,4 22,7 25,0 30,0 33,4 41,8
Supply Fan
External Pressure
Pa 300
Exhaust Fan
External Pressure
Pa 300
Supply Fan
Motor Power
kW 1,05 1,20 1,20 2,95 2,50 2,50 2,90 3,40 3,30 5,00 6,90 6,90 6,60 11,40 10,00
Exhaust Fan
Motor Power
kW 0,75 1,20 1,20 1,80 2,95 2,50 2,50 2,90 3,45 5,00 5,80 5,80 6,90 6,60 10,00
VENTUS PRO - PVS PO – POOL DEHUMIDIFICATION UNIT VENTUS PRO - PVS PO – POOL DEHUMIDIFICATION UNIT
2928
1
2
3
PVS PO pool dehumidiaction units are designed for indoor swimming pools and places where
dehumidication is necessary. According to VDI 2089 standards the relative humidity inside the indoor
pool spaces should be between 40% and 64%. If relative humidity is out of this range the formation
and proliferation of microorganisms such as bacteria, virus and fungi in the environment is increased.
In additon to this, the condensated chlorinated water leads to corrosion on metal and wood surfaces.
This unfavourable conditions are only overcomed by dehumidication and keeping relative humidity
between healthy climate conditions.
COMPRESSOR WORKİNG AREA
» High efciency with external air absolute humidity and air ow control
» Minimum energy consumption and operating cost with mechanical cooling
» Plate heat recovery options
» Automatic adjustment of fresh air rate according to need
Pool Dehumidication Units;
- Designed for 30°C DB and 54% RH comfort, -3°C and 90% outdoor weather conditions.
- Dehumidication capacity is calculated according to the 8,5g / kg (dry air) value of the blowing air.
Pool Dehumidication Units;
- Designed for 30°C DB and 54% RH comfort, -3°C and 90% outdoor weather conditions.
- Dehumidication capacity is calculated according to the 8,5g / kg (dry air) value of the blowing air.
89
9
9
7
10
6 8
5
1
2 4
3
9
A version with a pre-heater