OIMM – VENTUS PRO
INTERMEDIATE FAN DRIVE – 2-SPEED AC MOTOR
Dahlander pole changing motor – switch
(2-speed)
Pole chnager with two separate windings
(2-speed)
! Complete automatic control which should be an integral part of each air-conditioning system,
enables continuous operation of a device, in many cases it is an indispensable element and
lack of it may lead to serious operational problems or failures.
!
! In the case of AHUs equipped with water heat exchangers (heaters, coolers, glycol recovery)
air damper’s actuators of supply units should be equipped with a return spring ensuring its
spontaneous closure in case of power cut.
!
SETTING UP OF COMPONENTS
CONTROL SYSTEM
AIR DAMPERS
3.7
3.7.1
3.7.2
Dampers shall be equipped with the motor. Check that the blades turn back in closed position in case of power
supply failure during operation. Care must be taken to ensure that the actuator does not attempt to push the
damper blades beyond fully open or fully closed positions. All damper blades must be checked for free movement
and for fully open and fully closed positions.