Aquaviva PH-RX-Free CL-температура [56/56] Вер 1 56

Превью страниц Страница 56 / 56
Aquaviva PH-RX-Free CL-температура [56/56] Вер 1 56
0000138157 Вер. 1.1
56
Note 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Note 2
Value Range ppm
Measure
Value on
Modbus
Means [ppm]
0 0-0,5 50 0,50
1 0-1 100 1,00
2 0-2 200 2,00
3 0-5 500 5,00
4 0-10 1000 10,00
5 0-20 2000 20,00
6 0-200 2000 200,0
7 0-500 5000 500,0
8 0-1000 10000 1000,0
9 0-2000 20000 2000,0
10 0-10000 10000 10000
11 0-20000 20000 20000
12 0-100000 10000 100000
Note 3
Value Mode
0 ON/OFF
1 TIMED
2 PWM
Note 4
Cd Cell Probe C Factor
Value Reference
0 Custom (Use Cd Custom C Factor Value)
1 C 001
2 C 01
3 C 02
4 C 03
5 C 1
Note 6
Cd Programming Measure
Value Reference
0 Ohm Available
1 KOhm Available
2 MOhm Available
3 uS Available
4 mS Available
5 ppm Available
6 mgl Available
7 gl Available
Is the unit measure set in program, that the system use in programming mode to realize any
program setting(If is a submultiple of S (siemens), the measure is displayed in submultiple of S).
(If is Ohm or Multiple of Ohm, the measure in visual is displayed in Ohm or Multiple).
Note 7
Available Only On Cooling Tower Version
Cd Type Of Visual
Value Example
xx 00 2000,0 uS,ppm,mgl
xx 01 19500 uS,ppm,mgl
xx 02 100,00 mS,gl
xx 03 15000 Ohm
xx 04 15000 KOhm
xx 05 1500,0 KOhm
xx 06 150,00 KOhm
It's a integer number, but the highest part is a don't care part.
Note 8
Flow Unit
Value Reference
0 L/sec
1 L/min
2 L/h
3 m3/h
4 Gpm
Note 9
Water Meter Unit
Value Reference
0 L
1 m3
2 GAL
Note 10
For Totalizer(HIGH and LOW) if the unit is CUBE METER on registers decimal part are not indicated
For Totalizer(HIGH and LOW) if the unit is GAL the number is with 1 decimal
For Totalizer(HIGH and LOW) if the unit is Liters the number is with 0 decimal
MODBUS FUNCTION
READ HOLDING REGISTERS code: 0x03
WRITE MULTIPLE REGISTERS code: 0x10
STATUS (bit field 16 bit register)
LEVEL_0_ALARM
LEVEL_1_ALARM
HOLD_ALARM
Cl Pot 1 Over Current
Cl Pot 2 Under Current
Cl Pot 2 Over Current
Cl Pot 1 Under Current
REED_ALARM
Kilo with 2 decimal values
micro,ppm,mlg with 1 decimal value
micro,ppm,mgl with no decimal value
milli,gl with 2 decimal values
unit with no decimal value
Kilo with no decimal value
Kilo with 1 decimal value
Reference
Reserverd
Reserverd
Reserverd
PERMANECY (Permanency Allarm)
Range ClPot
Relè Mode
Reserverd
Reserverd
OFA2 (Over Feed Alarm) 100% OFA Time
OFA1 (Over Feed Alarm) 70% OFA Time

Содержание