Aquaviva SMV SmartPlus Rx 1.6 л/ч [20/21] Smart plus ph orp

Превью страниц Страница 20 / 21
Aquaviva SPH SmartPlus pH 1.6 л/ч [20/21] Smart plus ph orp
Smart Plus | pH · ORP
0000138883
9
9. ALARMS
Alarm Display Smart Plus pH Display Smart Plus ORP Actions to do
Level - Restore Product tank
Measure out of
range
(<5 pH)
(>9pH)
(<100 mV)
- Replace or check the
measure probe
- Restore pH / ORP
measure
OFA Alarm
(time >OFA time)
- Push to reset
Flow Rate - Restore Flow Rate
Calibration
Function
- Restore Probe or Buffer
solution and repeat
calibration procedure
System Error
- Press
to restore Default
parameter
- Broken Unit
Modbus Error
- Press to reset
- Restore communication
Default Parameters Smart Plus pH Smart Plus ORP
Language
EN
Time OFA
OFF
Flow Input
OFF
Set Point value
7.4 pH
700 mV
Calibration
7 pH / 4 pH (2-point)
475 mV
Dosing Method
Acid
Low
To restore the default parameters, follow the steps below:
x Power off the Smart Plus unit
x Keep and pressed and power on the unit
x The unit will flash
x Press
x Press to restore the default parameters.

8