Aten PE5208 [8/16] Default snmp agent settings
![Aten PE5208 [8/16] Default snmp agent settings](/views2/1977968/page8/bg8.png)
. eco Sensors
5
Default SNMP Agent Settings
This section allows you to set up your default SNMP and system parameters so
that eco Sensors can connect to the NRGence devices in your installation:
1. Enter a Username/Community, Port ID and Trap Port for the events.
2. Set the timeout and retry values.
3. Select the SNMP version, Privacy, and Authentication protocols from the
drop-down menus.
4. Key in the Privacy and Authentication passwords.
Note: Certain parameters in this section must match those of all the
NRGence devices in the installation. See Synchronizing SNMP
Parameters, page 6.
5. Click Search. The devices will then be displayed in a list.
SNMP Trap Receiver
To be notified of SNMP trap events, do the following:
1. Enter a Username, Port ID and Trap Port for the events.
2. Set the timeout and retry values.
3. Select the SNMP version, Privacy, and Authentication type from the drop-
down menus.
4. Key in the Privacy and Authentication passwords.
Note: Certain parameters in this section must match those of all the eco
PDU devices in the installation. See Synchronizing SNMP
Parameters, page 6.
System Parameters
Enter the service delay time in seconds.
Enter the Energy Box voltage in V.
Note: The EC1000 measures current only. Enter a reference voltage value
here to calculate power and power dissipation in EC installations.
Содержание
- Eco pdu pe series snmp settings user instructions 1
- Be sure to register your product at our online support center 2
- For telephone support call this number 2
- Online registration 2
- Pe device safety notice 2
- Telephone support 2
- User information 2
- User notice 2
- Contents 3
- Configuring snmp 4
- Introduction 4
- Eco pdu 5
- Graphical user interface gui 5
- Snmp trap receivers 6
- Eco sensors 7
- Power management software 7
- Default snmp agent settings 8
- Snmp trap receiver 8
- System parameters 8
- Management information base 10
- Mib browser 10
- Set snmp parameters 12
- Setting up thresholds 14
- Setting device outlet status 15
- Reading device outlet status 16
Похожие устройства
- Aten PE5208 Краткое руководство по установке
- Aten PE5208 Руководство пользователя
- Aten PE1216 Руководство пользователя
- Aten PE1216 Краткое руководство по установке
- Aten PE1324 Руководство пользователя
- Aten PE1324 Краткое руководство по установке
- Aten PE0118S Краткое руководство по установке
- Aten PE0218S Краткое руководство по установке
- Aten PE0116S Краткое руководство по установке
- Aten PE0216S Краткое руководство по установке
- Nissan Murano z50 Руководство пользователя ч2
- Nissan Murano z50 Руководство пользователя
- Aten PE0224S Краткое руководство по установке
- Aten PE0316S Краткое руководство по установке
- Aten PE0324S Краткое руководство по установке
- Aten PE0316B Краткое руководство по установке
- Aten PE0324B Краткое руководство по установке
- Aten PE0210S Краткое руководство по установке
- Aten PE0209S Краткое руководство по установке
- Aten PE0110S Краткое руководство по установке