Adding refrigerant If the connecting pipe is longer than 7 metres add refrigerant as needed Cool only type added English amount A Lm 7m X 15g m Heat pump type added amount A Lm 7m X50g m A amount of added refrigerant L the length of connecting pipe The length of connecting pipe m 7 8 9 10 Cool only type added amount g 0 15 30 45 Heat pump type added amount g 0 50 100 150 Exhaust the air as the above mentioned method Screw the gas shut off valve to close connect charging hose low pressure to the service valve and then open gas shut off valve again Connect the refrigerant bottle to the charging hose and then convert it Fill in liquid refrigerant as the above table Disconnect the manifold gauge after turning off the shut off valve and then open gas shut off valve again Tighten nuts and caps of each valve 16