14 Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual
Configuration
3. Press 1 and ENTER to select Device Manager.
Select the model by entering the corresponding number, then press ENTER.
4. Press 3 and ENTER to select Configuration.
5. Press 1 and ENTER to select Battery.
6. Press 2 and ENTER to change Battery Settings.
7. Type in the number of external battery packs then press ENTER.
Number of external battery packs:
1=1 external battery pack; 2=2 external battery packs; 3=3 external battery packs etc.
8. Press 3 and ENTER to accept the changes.
9. Press ESC multiple times (5) to return to the main menu.
10.Press 4 and ENTER to log out.
Configure UPS connection settings using UPS terminal mode
Connect the serial cable to the serial port on the back of the UPS. If using USB communication to the UPS,
disconnect the USB cable prior to connecting the serial cable.
1. Open a terminal program, such as HyperTerminal
From the Desktop, go to: Start, Programs, Accessories, Communication, HyperTerminal
2. Follow the prompts to choose a name and select an icon. Disregard the message, "...must install a
modem," if it is displayed. Click Cancel
3. Go to File, Properties. Select the COM port that is connected to your UPS. The port settings are:
– bits per second - 2400
– data - bits 8
– parity - none
– stop bit - 1
– flow control - none
4. Click OK in each of two windows
5. Press ENTER
Configure the number of external battery packs using UPS terminal mode
1. Once the blank terminal window is open, follow these steps to enter the number of external battery packs:
NOTE: Letter key commands are case sensitive. Use capital letters when using letter key commands.
2. Press Y. The UPS will respond with SM in the command box. If the UPS does not respond to the Y
command, ensure the serial cable is securely connected to the serial port on the UPS. Use only an APC
supplied serial cable.
3. When SM appears in the command box press the > key. The UPS will respond with the number of
external battery packs connected to the UPS. If the UPS has not been previously programmed to
recognize the number of external battery packs this number will be zero.
4. Use the + or - keys to change the number of external battery packs. OK will appear in the command box.
5. Press > key. The number of external battery packs will appear in the command box.
NOTE: The + or - keys and the > key must be used again to change the number of external battery packs
from this point in the programming.
6. Press R. The UPS will respond with BYE in the command box.
Содержание
- Rack mount 3u 1
- Smart up 1
- Uninterruptible power supply 1
- About this ups 3
- Accessories 3
- Check the package contents 3
- If a standard accessory such as a network management card is installed on this ups refer to the accessory user manual or cd for installation and operation instructions 3
- Inspect the ups upon receipt notify the carrier and dealer if there is damage 3
- Install accessories prior to connecting power to the ups 3
- Introduction 3
- Note the model and serial numbers are located on a small rear panel label for some models an additional label is located on the chassis under the front bezel 3
- Read the safety guide before installing the ups 3
- The apc uninterruptible power supply ups provides protection for electronic equipment from utility power blackouts brownouts sags and surges the ups filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power the ups provides continuous power from the batteries until utility power returns to safe levels or the batteries are fully discharged 3
- The packaging is recyclable save it for reuse or dispose of it properly 3
- This ups is equipped with an accessory smartslot refer to the apc web site www apc com for available accessories 3
- Unpack 3
- Be sure the air vents on the ups are not blocked 4
- Dimensions h w d 4
- Electrical 4
- Environmental 4
- Humidity 4
- Kg 139 lbs 4
- Maximum elevation operating storage 4
- Maximum number of external battery packs supported by the smart ups xl 4
- Output 4
- Physical 4
- Specifications 4
- Temperature operating storage 4
- V models 120 v models 200 v models 230 v models 4
- Weight 4
- Install the rails in the rack 5
- Install the ups in the rack and connect the battery module 5
- Installation 5
- 3000 va 120 vac 3000 va 100 vac 6
- 3000 va 230 vac 6
- Installation 6
- Rear panel features 6
- Rear panels 6
- Va 200 vac 6
- Connect equipment external battery pack s and power to the ups 7
- Start the ups 7
- Start up and operation 7
- Display panel indicators and function buttons 8
- Display panels 8
- Indicator led indicator title description 8
- Feature button feature title function 9
- Configuration 10
- Function factory default user selectable choices description 10
- Settings are adjusted through powerchute software or optional smartslot accessory cards 10
- Ups settings 10
- Function factory default user selectable choices description 11
- Adhere to all national and local electrical codes when wiring the epo 1 use the epo terminal block supplied with the ups 2 insert one wire from the epo cable into the 24 terminal and one wire into the in terminal of the epo terminal block 3 secure the connection by tightening the screws on the epo terminal block 4 plug the terminal block into the ups 12
- Cl2 class 2 cable for general use cl2p plenum cable for use in ducts plenums and other spaces used for environmental air cl2r riser cable for use in a vertical run in a floor to floor shaft clex limited use cable for use in dwellings and for use in raceways for installation in canada use only csa certified type elc extra low voltage control cable for installation in other countries use standard low voltage cable in accordance with national and local regulations 12
- Connect the emergency power off option 12
- Function factory default user selectable choices description 12
- The emergency power off epo option is a safety feature that will immediately remove power to all connected equipment when the epo button is pushed all connected equipment will immediately turn off and will not switch to battery power 12
- The epo interface is a safety extra low voltage selv circuit connect it only to other selv circuits the epo interface monitors circuits that have no determined voltage potential such closure circuits may be provided by a switch or relay properly isolated from the utility to avoid damage to the ups do not connect the epo interface to any circuit other than a closure type circuit 12
- Use one of the following cable types to connect the ups to the epo switch 12
- Configure ups parameters 13
- Maintenance transport and service 15
- Replacing the battery module 15
- Problem and or possible cause solution 16
- Troubleshooting 16
- Use this table to solve minor ups installation and operation problems refer to www apc com for assistance with complex ups problems 16
- Problem and or possible cause solution 17
- Problem and or possible cause solution 18
- 200 v models 19
- Fcc compliance notice 19
- Regulatory agency approvals and radio frequency warnings 19
- Regulatory and warranty information 19
- V models 19
- Exclusions 20
- Limited warranty 20
- Non transferable warranty 20
- Terms of warranty 20
- Two year 20
- Two year limited warranty 20
- Warranty claims 20
- Two year limited warranty 21
- Apc worldwide customer support 22
Похожие устройства
- APC smart-ups smt750rmi2u Инструкция по эксплуатации
- APC smart-ups smt3000i Инструкция по эксплуатации
- APC smart-ups smt2200i Инструкция по эксплуатации
- APC smart-ups smt750i Инструкция по эксплуатации
- APC smart-ups smt1000i Инструкция по эксплуатации
- APC smart-ups smt1500rmi2u Инструкция по эксплуатации
- APC back-ups bx800ci-rs Инструкция по эксплуатации
- APC smart-ups smt3000rmi2u Инструкция по эксплуатации
- APC smart surt10000rmxli 6u Инструкция по эксплуатации
- APC bc500-rs Инструкция по эксплуатации
- APC bc650-rs Инструкция по эксплуатации
- APC smart-ups smx2200rmhv2u Инструкция по эксплуатации
- APC smart-ups smx3000rmhv2u Инструкция по эксплуатации
- APC smart-ups smx3000rmhv2unc Инструкция по эксплуатации
- APC smart-ups smt1000rmi2u Инструкция по эксплуатации
- APC smart-ups smt1500rmi1u Инструкция по эксплуатации
- APC smart-ups smx750i Инструкция по эксплуатации
- APC smart-ups smx1000i Инструкция по эксплуатации
- APC smart-ups smx1500rmi2u Инструкция по эксплуатации
- APC smart-ups sum1500rmxli2u Инструкция по эксплуатации
Скачать
Случайные обсуждения