The Legrand ARCHIMOD HE, model 60, is an UPS on line double
conversion with PWM Hi-Frequency technology. It has passing trough
neutral and Modular Architecture with the possibility to have N+X
redundancy. The nominal power is 60 kVA – 60 kW. Batteries are lead
acid, sealed, free maintenance, valve regulated, and arranged, inside
the UPS or external battery cabinet, in dedicated Drawers, in order
to guarantee compact dimensions reducing weights and DC voltage
level.
1.1 Modularity
The UPS ARCHIMOD HE 60 has modular architecture, it is
composed by identical modules which work in parallel. Modules are:
• PowerModules6,7kVA;
• BatteryDrawersofsevenbatteries(9Ah).
These modules are installed inside the UPS and have identical functions.
Power Modules are composed by the following circuits:
• Rectifier/PFC
• Inverter
• BatteryCharger
• CommandLogiccircuit
• AutomaticBy-pass
Battery drawers contain 7 batteries, and are easy to be move and
replace.
1.2 Scalability
ThemodularityofARCHIMODUPSallowstoexecutePowerand
Autonomy upgrade. Thanks to the intelligent Plug N’ Play connection,
no HW and SW settings are needed to increase or decrease the
power or the autonomy.
1.3 Redundancy
The modularity of the UPS allows the N+X redundant configurations.
TheRedundancyisachievedusingmoremodulesthanneeded,
modules will run in “load sharing”.
1.4 Architecture
The UPS ARCHIMOD HE 60 is three–phase input and output, the
architecture is distributed parallel architecture in each phase (there
are more modules in the same phase).
In case of redundant configuration, whenever one module fails, the
other modules in the same phase will guarantee the energy supply
and protection to the load. The available power in each phase will be
always the sum of the power of the modules installed in that phase.
1.5 Hot-plug
The UPS ARCHIMOD HE 60 The power modules are independently
controlled by 3 Command Tunnel. Each Command Tunnel controls, three
power modules. It is possible to turn off only one command tunnel and
install or replace modules inside of it, when the other tunnel is still running.
This allows the service on a part of the UPS without turn off the
1. GENERAL SPECIFICATIONS
complete system, losing only the power of the tunnel in maintenance.
In case of redundancy or scalability, the load is protected by the UPS
also during the replace or upgrade of power modules.
1.6 By-pass
In each Power Module there is a static By-pass system which, in case
of overload or other anomaly, automatically transfer the load to the
mains.
The UPS has embedded the manual bypass for service and
maintenance and it is possible to connect a dedicated bypass input line.
A dedicated software of remote monitoring and management,
installed on a PC connected to the UPS, allows to check and set all
working parameters of ARCHIMOD HE (the same functions available
on the UPS control panel) and, furthermore, to schedule and program
computer remote shutdown.
Optional software (UPS SuperviSor) or Net Interface card (CS121 SK)
allow the multi server shutdown and UPS remote control on the LAN.
ARCHIMOD HE is controlled by a main microprocessor which works
togetherwithmicroprocessorsineachpowermodules;Bydisplay
is possible to check all measurements, working parameters and
status of the system. Here follow the measurements and working
parameters available on the display:
Technicalsheet:UPS-LGR-0072/GB 01/02/2014Lastupdate:01/02/2014
1/2
Input
Current:
• RMSvalue
• Peakvalue
• CrestFactor
Voltage:
• Ph-NRMSvalue
• Ph-PhRMSvalue
• BypassLineVoltage
Power:
• Nominal(VA)
• Active(W)
Power Factor
Frequency
Output
Current:
• RMSvalue
• Peakvalue
• CrestFactor
Voltage:
• Ph-NRMSvalue
• Ph-PhRMSvalue
Power:
• Nominal(VA)
• Active(W)
Power Factor
Frequency
Batteries
• Voltage
• Capacity
• Current
• Historydata
• ResidualCapacity
• Chargingstatus
Misc.
• InternalTemperature
• FanSpeed
• HVDCBUSVoltage
DATA LOG.
• By-passintervention
• Overheats
• Overloads
• Batteryinterventions
• Totaldischarge
• Events(info,warning,critical)
• Alarms