Wiring the Relay Contact
The PT-508 has one set of relay outputrelay 1. The relay contact
consists of two contacts of the terminal block on the PT-508’s bottom
panel. Refer to the next section for detailed instructions on how to
connect the wires to the terminal block connector, and how to attach the
terminal block connector to the terminal block receptor.
The fault circuit will open if:
1. A relay warning event is triggered, OR
2. The PT-508 is the Master of this Turbo Ring, and the Turbo Ring is
broken, OR
3. Start-up failure.
If none of these three conditions is met, the fault circuit will remain
closed.
Wiring the Redundant Power Inputs (24/48 VDC models)
The PT-508 (24/48 VDC models) unit has two sets of power inputs –
power input 1 and power input 2. Top and front views of one of the
terminal block connectors are shown below.
Take the following steps to wire the redundant power inputs:
STEP 1: Insert the negative/positive DC wires into the V-/V+ terminals.
STEP 2: To keep the DC wires from pulling loose, use a small flat-blade
screwdriver to tighten the wire-clamp screws on the front of the terminal
block connector.
STEP 3: Insert the plastic terminal block connector prongs into the
terminal block receptor, which is located on the PT’s bottom panel.
ATTENTION
Before connecting
the PT
to the DC power inputs, make sure the
DC power source voltage is stable.