DIP Switch Settings
There are 8 DIP switches on the top panel of the ICF-1280I series
converter. All DIP switches except SW5 are set to the factory default OFF
position.
Transmission Speed (kbps)
SW1
SW2
SW3
SW4
Auto (default)
OFF
OFF
OFF
OFF
12000
OFF
OFF
OFF
ON
6000
OFF
OFF
ON
OFF
3000
OFF
OFF
ON
ON
1500
OFF
ON
OFF
OFF
500
OFF
ON
OFF
ON
187.5
OFF
ON
ON
OFF
93.75
OFF
ON
ON
ON
45.45
ON
OFF
OFF
OFF
19.2
ON
OFF
OFF
ON
9.6
ON
OFF
ON
OFF
Setting
ON
OFF
SW5
Fiber Link Monitor
Disable
SW8
Remote Fiber Diagnosis*
Disable
Topology
SW6
SW7
Linear, Star (P1/P2 enable)
OFF
OFF
Linear, Star (P1 disable)
OFF
ON
Linear, Star (P2 disable)
ON
OFF
Redundant Ring
ON
ON
In Redundant Ring mode, the Fiber Link Monitor function should also be
enabled. Set SW5 to the ON position. For point-to-point topology with
redundant fiber cables, set both converters to Redundant Ring mode
with the correct slot time setting.
Note: Refer to the Remote Fiber Diagnosis section for instructions.
If an ICF-1280I converter is deployed at the beginning
or at the end of the
topology in Linear mode or Star mode, the unused port should be
disabled. In such cases, we recommend using an ICF-1180I series
converter. Please use the ICF-1180I series with Rev. 1.3, or higher
versions to connect with the ICF-1280I series.