ioLogik R1200 Series Modbus Mapping
A-15
Reference Address Data Type Description
40038 0x0025 1 Word CH5 DI filter value
40065 0x0040 1 Word CH0 DI counter trigger type, 0:L2H, 1:H2L, 2: Both
40066 0x0041 1 Word CH1 DI counter trigger type, 0:L2H, 1:H2L, 2: Both
40067 0x0042 1 Word CH2 DI counter trigger type, 0:L2H, 1:H2L, 2: Both
40068 0x0043 1 Word CH3 DI counter trigger type, 0:L2H, 1:H2L, 2: Both
40069 0x0044 1 Word CH4 DI counter trigger type, 0:L2H, 1:H2L, 2: Both
40070 0x0045 1 Word CH5 DI counter trigger type, 0:L2H, 1:H2L, 2: Both
40321 0x0140 1 Word CH0 Relay value, 0=OFF, 1=ON
40322 0x0141 1 Word CH1 Relay value, 0=OFF, 1=ON
40323 0x0142 1 Word CH2 Relay value, 0=OFF, 1=ON
40324 0x0143 1 Word CH3 Relay value, 0=OFF, 1=ON
40325 0x0144 1 Word CH4 Relay value, 0=OFF, 1=ON
40326 0x0145 1 Word CH5 Relay value, 0=OFF, 1=ON
40353 0x0160 2 Word CH0 Relay pulse out count
40355 0x0162 2 Word CH1 Relay pulse out count
40357 0x0164 2 Word CH2 Relay pulse out count
40359 0x0166 2 Word CH3 Relay pulse out count
40361 0x0168 2 Word CH4 Relay pulse out count
40363 0x016A 2 Word CH5 Relay pulse out count
40545 0x0220 1 Word CH0 Relay power on delay
40546 0x0221 1 Word CH1 Relay power on delay
40547 0x0222 1 Word CH2 Relay power on delay
40548 0x0223 1 Word CH3 Relay power on delay
40549 0x0224 1 Word CH4 Relay power on delay
40550 0x0225 1 Word CH5 Relay power on delay
R1240 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
00705 0x02C0 1Bit CH0 AI reset min value counter, 1= reset
00706 0x02C1 1Bit CH1 AI reset min value counter, 1= reset
00707 0x02C2 1Bit CH2 AI reset min value counter, 1= reset
00708 0x02C3 1Bit CH3 AI reset min value counter, 1= reset
00709 0x02C4 1Bit CH4 AI reset min value counter, 1= reset
00710 0x02C5 1Bit CH5 AI reset min value counter, 1= reset
00711 0x02C6 1Bit CH6 AI reset min value counter, 1= reset
00712 0x02C7 1Bit CH7 AI reset min value counter, 1= reset
00737 0x02E0 1Bit CH0 AI reset max value counter, 1= reset
00738 0x02E1 1Bit CH1 AI reset max value counter, 1= reset
00739 0x02E2 1Bit CH2 AI reset max value counter, 1= reset
00740 0x02E3 1Bit CH3 AI reset max value counter, 1= reset
00741 0x02E4 1Bit CH4 AI reset max value counter, 1= reset
00742 0x02E5 1Bit CH5 AI reset max value counter, 1= reset
00743 0x02E6 1Bit CH6 AI reset max value counter, 1= reset
00744 0x02E7 1Bit CH7 AI reset max value counter, 1= reset
Содержание
- Edition 2 september 2016 1
- Iologik r1200 series user s manual 1
- Www moxa com product 1
- Copyright notice 2
- Disclaimer 2
- Iologik r1200 series user s manual 2
- Technical support contact information 2
- Trademarks 2
- Www moxa com support 2
- Table of contents 3
- Overview 5
- Introduction 6
- Iologik r1200 series overview 6
- Ordering information 6
- Package checklist 6
- Product features 6
- Product model information 6
- Common specifications 7
- Environmental limits 7
- Iologik r1200 series overview 7
- Physical characteristics 7
- Serial communication 7
- Serial communication parameters 7
- Specifications 7
- Standards and certifications 7
- Warranty 7
- Digital input 8
- Digital output 8
- Inputs and outputs 8
- Iologik r1200 series overview 8
- Iologik r1210 8
- Iologik r1212 8
- Power requirements 8
- Digital input 9
- Inputs and outputs 9
- Iologik r1200 series overview 9
- Iologik r1214 9
- Power requirements 9
- Relay output 9
- Analog input 10
- Analog output 10
- Inputs and outputs 10
- Iologik r1200 series overview 10
- Iologik r1240 10
- Iologik r1241 10
- Power requirements 10
- Hardware reference 11
- Iologik r1200 series overview 11
- Panel guide 11
- Physical dimensions 11
- Di circuit diagram 12
- Iologik r1200 series overview 12
- Led indicators 12
- Switch settings 12
- Dio circuit diagram 13
- Iologik r1200 series overview 13
- Ai circuit diagram 14
- Iologik r1200 series overview 14
- Relay circuit diagram 14
- Initial setup 15
- Attention 16
- Connecting the power 16
- Connecting to serial interface 16
- Grounding the iologik r1200 16
- Hardware installation 16
- Iologik r1200 series initial setup 16
- Mounting the iologik r1200 16
- Tb1 and tb2 two rs 485 2 wire connectors 16
- Analog input output 17
- Connecting to digital sensors and devices 17
- Digital input output sink type 17
- Iologik r1200 series initial setup 17
- Relay output form a 17
- Iologik r1200 series initial setup 18
- Rs 485 networks 18
- Serial communication initial setup 18
- Serial communication parameters initial state 18
- Setting the device id for rs 485 serial communication 18
- Connecting multiple modbus rtu devices 19
- Connecting one modbus rtu device 19
- Dual rs 485 or repeater settings 19
- Iologik r1200 series initial setup 19
- Modbus rtu devices 19
- Attention 20
- Iologik r1200 series initial setup 20
- Jumper settings dio and ai 20
- Pull high low dip switch settings for the rs 485 port 20
- Iologik r1200 series initial setup 21
- Iosearch installation 21
- Software installation 21
- Iologik r1200 series initial setup 22
- Configure the device 23
- Import configuration file 23
- Initial setup by usb 23
- Iologik r1200 series initial setup 23
- Upgrade firmware 23
- Iologik r1200 series initial setup 24
- Restore factory default settings 24
- Using iosearch 25
- Introduction to iosearch 26
- Iologik r1200 series using iosearch 26
- Iosearch main screen 26
- Main screen overview 26
- Iologik r1200 series using iosearch 27
- Iosearch setup 27
- System 27
- Iologik r1200 series using iosearch 28
- Attention 29
- Iologik r1200 series using iosearch 29
- Connect disconnect 30
- Iologik r1200 series using iosearch 30
- Locate 30
- Main functions 30
- Quick links 30
- Change server name 31
- Export 31
- Firmware upgrade 31
- Import 31
- Iologik r1200 series using iosearch 31
- Delete iologik device 32
- Iologik r1200 series using iosearch 32
- Reset to default 32
- Restart system 32
- Configuring digital input channels 33
- I o configuration tab general 33
- Iologik r1200 series using iosearch 33
- Main screen 33
- Iologik r1200 series using iosearch 34
- Configuring digital output channels 35
- Iologik r1200 series using iosearch 35
- Iologik r1200 series using iosearch 36
- Ai input range 37
- Configuring analog input channels 37
- Iologik r1200 series using iosearch 37
- Attention 38
- Configuring analog output channels 38
- Iologik r1200 series using iosearch 38
- Iologik r1200 series using iosearch 39
- Iologik r1200 series using iosearch 40
- Server info tab 40
- Iologik r1200 series using iosearch 41
- Server settings tab general 41
- Iologik r1200 series using iosearch 42
- Watchdog 42
- A modbus mapping 43
- Modbus mapping 43
- Iologik r1200 series modbus mapping 44
- R1210 modbus mapping 44
- Xxxx read write coils functions 1 5 15 44
- Iologik r1200 series modbus mapping 45
- Iologik r1200 series modbus mapping 46
- Xxxx read only coils function 2 46
- Xxxx read only registers function 4 46
- Iologik r1200 series modbus mapping 47
- Xxxx read write registers functions 3 6 16 47
- Iologik r1200 series modbus mapping 48
- R1212 modbus mapping 48
- Xxxx read write coils functions 1 5 15 48
- Iologik r1200 series modbus mapping 49
- Iologik r1200 series modbus mapping 50
- Iologik r1200 series modbus mapping 51
- Xxxx read only coils function 2 51
- Xxxx read only registers function 4 51
- Iologik r1200 series modbus mapping 52
- Xxxx read write registers functions 3 6 16 52
- Iologik r1200 series modbus mapping 53
- Iologik r1200 series modbus mapping 54
- R1214 modbus mapping 54
- Xxxx read write coils functions 1 5 15 54
- Iologik r1200 series modbus mapping 55
- Iologik r1200 series modbus mapping 56
- Xxxx read only coils function 2 56
- Xxxx read only registers function 4 56
- Xxxx read write registers functions 3 6 16 56
- Iologik r1200 series modbus mapping 57
- R1240 modbus mapping 57
- Xxxx read write coils functions 1 5 15 57
- Iologik r1200 series modbus mapping 58
- Xxxx read only registers function 4 58
- Iologik r1200 series modbus mapping 59
- Xxxx read write registers functions 3 6 16 59
- Iologik r1200 series modbus mapping 60
- R1241 modbus mapping 60
- Xxxx read write registers functions 3 6 16 60
- B factory defaults 61
- Factory defaults 61
- C pinouts 62
- Pinouts 62
- D fcc interference statement 63
- Fcc interference statement 63
- Federal communication commission warning 63
- E european community ce 64
Похожие устройства
- Moxa ioLogik R1240-T Технические характеристики
- Moxa ioLogik R1240-T Руководство по аппаратной части
- Moxa ioLogik R1241 Инструкция по эксплуатации
- Moxa ioLogik R1241 Технические характеристики
- Moxa ioLogik R1241 Руководство по аппаратной части
- Moxa ioLogik R1241-T Инструкция по эксплуатации
- Moxa ioLogik R1241-T Технические характеристики
- Moxa ioLogik R1241-T Руководство по аппаратной части
- Moxa ioLogik R2140 Инструкция по эксплуатации
- Moxa ioLogik R2140 Руководство по аппаратной части
- Moxa ioLogik R2140 Технические характеристики
- Moxa ioMirror E3210 Инструкция по эксплуатации
- Moxa ioMirror E3210 Руководство по аппаратной части
- Moxa ioMirror E3210 Технические характеристики
- Moxa ioLogik 2512 Инструкция по эксплуатации
- Moxa ioLogik 2512 Руководство по аппаратной части
- Moxa ioLogik 2512 Технические характеристики
- Moxa ioLogik 2512 Руководство пользователя Click-n-Go_Plus
- Moxa ioLogik 2512-T Инструкция по эксплуатации
- Moxa ioLogik 2512-T Руководство по аппаратной части