ioPAC RTU Software RTU Communications
4-19
Port Trunking
To enable the port trunking function, use the debug port as described in the following steps.
1. Enable the port trunking function (IP_Bonding mode 1)
/etc/init.d/networking stop
ipset bond0 -aup -i192.168.19.151 -n255.255.255.0 -g192.168.19.254
modprobe bonding mode=1 miimon=100 use_carrier=0
/etc/init.d/networking start
2. After configuration, the virtual IP address will be set to 192.168.19.151
3. Disable the port trunking function
/etc/init.d/networking stop
ipset bond0 -adown
/etc/init.d/networking start
4. Use the ifconfig command to check the Ethernet configuration.
Serial Configuration
Modbus RTU Master
Modbus RTU is a very common communication protocol in industrial applications and the ioPAC RTU controller
has a built-in Modbus RTU master function. For more detailed information, see the C/C++ Sample Code
Programming Guide for ioPAC RTU Controllers.