The 420 mA burnout mode values are defined in the following diagram:
Users can define burnout values for selected ranges. When input values are in the burnout range, raw data will
register as 0000h to indicate analog input burnout. The definition of raw data is as follows:
Burnout Value (BO) 0.0 < BO < 4.0 User-defined (default: 2 mA)
Burnout State 0 ≤ AI < BO mA S/W output 0000h
Under Range BO ≤ AI < 4 mA S/W output raw data
Normal Range 4 ≤AI ≤ 20.00 mA S/W output raw data until FFFEh
Over Range XX > 20.00 mA S/W output FFFFh
Current
Data Current
0 0 mA
1 0.3125 µA
13107 4 mA
49152 15 mA
65534 20 mA
65535 > 20 mA
Voltage
Data Voltage
0 0 V
1 0.16 mV
16384 2.5 V
32768 5 V
65535 10 V