Moxa MxNVR-IA8 [20/61] Attention

Moxa MxNVR-IA8 [20/61] Attention
Moxa MxNVR-IA8 Getting Started
2-9
Four rackmount screws are required to attach the MxNVR-IA8 to a standard rack.
Follow these steps to install the MxNVR-IA8 on a rack.
STEP 1: Install the rackmount kit.
Take the rackmount kit out of the package. There are two rackmount ears and 12 screws. Each ear requires six
screws to attach to the rack.
STEP 2: Install the rackmount ears on the MxNVR-IA8.
Use 6 screws to attach one rackmount ear to one side of the MxNVR-IA8. Repeat this step to attach the ear on
the other side of the MxNVR-IA8.
STEP 3: Install the MxNVR-IA8 to a rack.
Gently slide the MxNVR-IA8 onto the rack, and then use the screws provided by the rack supplier to fix the
rackmount support to the rail.
ATTENTION
Safety First!
The following or similar rackmount instructions are included in the installation instructions:
1. Elevated Operating Ambient - If installed in a closed or multi-unit rack assembly,
the operating ambient
temperature of the rack environment may be greater than the room ambient. Therefore, consideration
should be given to installing the equipment in an environment compatible with the maximum ambient
temperature (Tma) specified by the manufacturer.
2. Reduced Air Flow - Installation of the equipment in a rack should be such that the amount of air flow
required for safe operation of the equipment is not compromised.
3. Mechanical Loading - Mounting of the equipment in the rack should be such that
a hazardous condition is
not achieved due to uneven mechanical loading.
4. Circuit Overloading - Consideration should be given to the connection of the equipment to the supply
circuit and the effect that overloading of the circuits might have on overcurrent protection and supply
wiring. Appropriate consideration of
equipment nameplate ratings should be used when addressing this
concern.
5. Reliable Earthing - Reliable earthing of rackmounted equipment should be maintained. Particular
attention should be given to supply connections other than
direct connections to the branch circuit (e.g.
use of power strips).