Daikin FHQ100CB_RZQSG100L9V [11/52] Installation
![Daikin FAQ100C9_RZQG100L9V [11/52] Installation](/views2/1251643/page11/bgb.png)
6Installation
Installerreferenceguide
11
RZQG71~140L_V1+Y1+RZQSG100~140L_V1+Y1
Splitsystemairconditioners
4P3855221–2014.08
5.3.3 Refrigerantpipinginsulation
▪ Usepolyethylenefoamasinsulationmaterial:
▪ withaheattransferratebetween0.041and0.052W/mK(0.035
and0.045kcal/mh°C)
▪ withaheatresistanceofatleast120°C
▪ Insulationthickness
Ambient
temperature
Humidity Minimumthickness
≤30°C 75%to80%RH 15mm
>30°C ≥80%RH 20mm
5.4 Preparingelectricalwiring
5.4.1 Aboutpreparingelectricalwiring
INFORMATION
Also read the precautions and requirements in the
"Generalsafetyprecautions"chapter.
INFORMATION
Also read "6.7.5 Specifications of standard wiring
components"onpage22.
WARNING
▪ If the power supply has a missing or wrong Nphase,
equipmentmightbreakdown.
▪ Establish proper earthing.Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incompleteearthingmaycauseelectricalshock.
▪ Installtherequiredfusesorcircuitbreakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping,particularlyonthehighpressureside.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
Theycancauseoverheating,electricalshockorfire.
▪ DoNOTinstallaphaseadvancingcapacitor,because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performanceand may
causeaccidents.
WARNING
▪ All wiring must be performed by an authorized
electrician and must comply with the applicable
legislation.
▪ Makeelectricalconnectionstothefixedwiring.
▪ All components procured on the site and all electrical
construction must comply with the applicable
legislation.
WARNING
ALWAYSusemulticorecableforpowersupplycables.
6 Installation
6.1 Overview:Installation
This chapter describes what you have to do and know onsite to
installthesystem.
Typicalworkflow
Installationtypicallyconsistsofthefollowingstages:
▪ Mountingtheoutdoorunit.
▪ Mountingtheindoorunits.
▪ Connectingtherefrigerantpiping.
▪ Checkingtherefrigerantpiping.
▪ Chargingrefrigerant.
▪ Connectingtheelectricalwiring.
▪ Finishingtheoutdoorinstallation.
▪ Finishingtheindoorinstallation.
INFORMATION
Forinstallationoftheindoorunit(mountingtheindoorunit,
connecting the refrigerant piping to the indoor unit,
connecting the electrical wiring to the indoor unit …), see
theinstallationmanualoftheindoorunit.
6.2 Openingtheunits
6.2.1 Aboutopeningtheunits
Atcertaintimes,youhavetoopentheunit.Example:
▪ Whenconnectingtherefrigerantpiping
▪ Whenconnectingtheelectricalwiring
▪ Whenmaintainingorservicingtheunit
DANGER:RISKOFELECTROCUTION
DoNOTleavetheunitunattendedwhentheservicecover
isremoved.
6.2.2 Toopentheoutdoorunit
1×
1
2
Содержание
- Installer reference guide 1
- Split system air conditioners 1
- About the box 6 2
- About the documentation 5 2
- About the units and options 6 2
- Commissioning 24 2
- Disposal 27 2
- General safety precautions 3 2
- Glossary 50 2
- Hand over to the user 26 2
- Installation 11 2
- Installer reference guide 2
- Maintenance and service 26 2
- Preparation 7 2
- Table of contents 2
- Technical data 28 2
- Troubleshooting 26 2
- About the documentation 3
- For the installer 3
- General 3
- General safety precautions 3
- Installation site 3
- Meaning of warnings and symbols 3
- General safety precautions 4
- Refrigerant 4
- About the documentation 5
- About this document 5
- Electrical 5
- Installer reference guide at a glance 5
- About the box 6
- About the units and options 6
- Identification 6
- Identification label outdoor unit 6
- Outdoor unit 6
- Overview about the box 6
- Overview about the units and options 6
- To handle the outdoor unit 6
- To remove the accessories from the outdoor unit 6
- To unpack the outdoor unit 6
- Combining units and options 7
- Installation site requirements of the outdoor unit 7
- Overview preparation 7
- Possible options for the outdoor unit 7
- Preparation 7
- Preparing installation site 7
- About reusing existing piping 8
- Additional installation site requirements of the outdoor unit in cold climates 8
- Preparation 8
- Preparing refrigerant piping 8
- To check if piping is contaminated 8
- Definitions l1 l7 h1 h2 9
- Preparation 9
- Refrigerant piping diameter 9
- Refrigerant piping material 9
- Refrigerant piping requirements 9
- Preparation 10
- Refrigerant piping length and height difference 10
- About opening the units 11
- About preparing electrical wiring 11
- Installation 11
- Opening the units 11
- Overview installation 11
- Preparing electrical wiring 11
- Refrigerant piping insulation 11
- To open the outdoor unit 11
- About mounting the outdoor unit 12
- Installation 12
- Mounting the outdoor unit 12
- Precautions when mounting the outdoor unit 12
- To install the outdoor unit 12
- To provide drainage 12
- To provide the installation structure 12
- About connecting the refrigerant piping 13
- Connecting the refrigerant piping 13
- Installation 13
- Precautions when connecting the refrigerant piping 13
- To prevent the outdoor unit from falling over 13
- Guidelines when connecting the refrigerant piping 14
- Installation 14
- Pipe bending guidelines 14
- To braze the pipe end 14
- To flare the pipe end 14
- To handle the stop valve 14
- Using the stop valve and service port 14
- Installation 15
- To connect the refrigerant piping to the outdoor unit 15
- To handle the service cap 15
- To handle the stem cap 15
- To open close the stop valve 15
- About checking the refrigerant piping 16
- Checking the refrigerant piping 16
- Installation 16
- Precautions when checking the refrigerant piping 16
- To determine if oil traps are required 16
- About charging refrigerant 17
- Charging refrigerant 17
- Checking refrigerant piping setup 17
- Installation 17
- To check for leaks 17
- To perform vacuum drying 17
- Installation 18
- Definitions l1 l7 h1 h2 19
- Installation 19
- Precautions when charging refrigerant 19
- To determine the additional refrigerant amount 19
- About connecting the electrical wiring 20
- Charging refrigerant setup 20
- Connecting the electrical wiring 20
- Installation 20
- To charge refrigerant 20
- To determine the complete recharge amount 20
- To fix the fluorinated greenhouse gases label 20
- About electrical compliance 21
- Guidelines when connecting the electrical wiring 21
- Installation 21
- Precautions when connecting the electrical wiring 21
- Installation 22
- Specifications of standard wiring components 22
- To connect the electrical wiring on the outdoor unit 22
- Finishing the outdoor unit installation 23
- Installation 23
- To check the insulation resistance of the compressor 23
- To close the outdoor unit 23
- To finish the outdoor unit installation 23
- Checklist before test run 24
- Commissioning 24
- Overview commissioning 24
- Precautions when commissioning 24
- To perform a test run 24
- Commissioning 25
- Error codes when performing a test run 25
- Checklist for yearly maintenance of the outdoor unit 26
- Hand over to the user 26
- Maintenance and service 26
- Maintenance safety precautions 26
- Overview maintenance and service 26
- Overview troubleshooting 26
- Precautions when troubleshooting 26
- Troubleshooting 26
- About pump down 27
- Disposal 27
- Overview disposal 27
- To pump down 27
- Components 28
- Dimensions and service space 28
- Dimensions outdoor unit 28
- Overview technical data 28
- Piping diagram 28
- Rzqg71 rzqsg100 125 dimensions in mm 28
- Technical data 28
- Technical specifications 28
- This chapter contains information about 28
- Wiring diagram 28
- A gas pipe connection ø15 flare connection 29
- B liquid pipe connection ø9 flare connection 29
- C internal service port in the unit 29
- D earthing terminal m5 in the switch box 29
- D076346 29
- E refrigerant piping intake 29
- F power supply wiring intake knockout hole ø34 29
- G control wiring intake knockout hole ø27 29
- H drain hole 29
- I anchor point bolt 4 m12 29
- Installer reference guide 29
- Rzqg100 140 rzqsg140 dimensions in mm 29
- Rzqg71 140l_v1 y1 rzqsg100 140l_v1 y1 split system air conditioners 4p385522 1 2014 8 29
- Technical data 29
- Service space outdoor unit 30
- Technical data 30
- Technical data 31
- Components 32
- Components outdoor unit 32
- Rzqg100 140_v1 rzqsg140_v1 32
- Rzqg71_v1 rzqsg100 125_v1 32
- Technical data 32
- M2f m1f 33
- Rzqg100 140_y1 rzqsg140_y1 33
- Rzqg71_y1 rzqsg100 125_y1 33
- S1ph x1m 33
- Technical data 33
- Piping diagram 34
- Piping diagram outdoor unit 34
- Technical data 34
- Colours see legend 35
- D089497b 35
- For a legend explaining the figures below refer to the end of this topic 35
- Information 35
- Refer to the combination table and the option manual for how to connect the wiring to x6a x28a and x77a 35
- Refer to the service manual for instructions on how to set the selector switches ds1 the factory setting of all switches is off 35
- Refer to the wiring diagram sticker on the back of the service cover for how to use the bs1 bs4 and ds1 switches 35
- Rzqg71_v1 rzqsg100_v1 35
- Symbols see legend 35
- Technical data 35
- The wiring diagram is delivered with the unit located at the inside of the service cover 35
- This wiring diagram applies only to the outdoor unit 35
- When operating do not short circuit protective devices s1ph and s1pl 35
- Wiring diagram 35
- Wiring diagram outdoor unit 35
- D080114b 36
- Installer reference guide 36
- Only for 71 class 36
- P385522 1 2014 8 36
- Refer to the combination table and the option manual for how to connect the wiring to x6a x28a and x77a 36
- Refer to the service manual for instructions on how to set the selector switches ds1 the factory setting of all switches is off 36
- Refer to the wiring diagram sticker on the back of the service cover for how to use the bs1 bs4 and ds1 switches 36
- Rzqg71 140l_v1 y1 rzqsg100 140l_v1 y1 36
- Rzqg71_y1 rzqsg100 125_y1 36
- Split system air conditioners 36
- Technical data 36
- This wiring diagram applies only to the outdoor unit 36
- When operating do not short circuit protective device s1ph 36
- Colours see legend 37
- D088865c 37
- Installer reference guide 37
- Refer to the combination table and the option manual for how to connect the wiring to x6a x28a and x77a 37
- Refer to the service manual for instructions on how to set the selector switches ds1 the factory setting of all switches is off 37
- Refer to the wiring diagram sticker on the back of the service cover for how to use the bs1 bs4 and ds1 switches 37
- Rzqg100 140_v1 rzqsg140_v1 37
- Rzqg71 140l_v1 y1 rzqsg100 140l_v1 y1 split system air conditioners 4p385522 1 2014 8 37
- Symbols see legend 37
- Technical data 37
- This wiring diagram applies only to the outdoor unit 37
- When operating do not short circuit protective devices s1ph and s1pl 37
- D077192 38
- Installer reference guide 38
- Only for 71 class 38
- P385522 1 2014 8 38
- Refer to the combination table and the option manual for how to connect the wiring to x6a x28a and x77a 38
- Refer to the service manual for instructions on how to set the selector switches ds1 the factory setting of all switches is off 38
- Refer to the wiring diagram sticker on the back of the service cover for how to use the bs1 bs4 and ds1 switches 38
- Rzqg100 140_y1 rzqsg140_y1 38
- Rzqg71 140l_v1 y1 rzqsg100 140l_v1 y1 38
- Split system air conditioners 38
- Technical data 38
- This wiring diagram applies only to the outdoor unit 38
- When operating do not short circuit protective device s1ph 38
- Colours see legend 39
- D089489b 39
- Installer reference guide 39
- Refer to the combination table and the option manual for how to connect the wiring to x6a x28a and x77a 39
- Refer to the service manual for instructions on how to set the selector switches ds1 the factory setting of all switches is off 39
- Refer to the wiring diagram sticker on the back of the service cover for how to use the bs1 bs4 and ds1 switches 39
- Rzqg71 140l_v1 y1 rzqsg100 140l_v1 y1 split system air conditioners 4p385522 1 2014 8 39
- Rzqsg125_v1 39
- Symbols see legend 39
- Technical data 39
- This wiring diagram applies only to the outdoor unit 39
- When operating do not short circuit protective devices s1ph and s1pl 39
- Technical data 40
- Technical data 41
- Technical specifications 41
- Technical specifications outdoor unit 41
- Technical data 42
- Technical data 43
- Technical data 44
- Technical data 45
- Technical data 46
- Technical data 47
- Technical data 48
- Technical data 49
- Glossary 50
Похожие устройства
- Daikin FHQ100CB_RZQSG100L9V Инструкция по монтажу (внутр. блок)
- Daikin FHQ125CB_RZQSG125L9V Инструкция по эксплуатации
- Daikin FHQ125CB_RZQSG125L9V Инструкция по монтажу (нар. блок)
- Daikin FHQ125CB_RZQSG125L9V Инструкция по монтажу (внутр. блок)
- Daikin FHQ140CB_RZQSG140L9V Инструкция по эксплуатации
- Daikin FHQ140CB_RZQSG140L9V Инструкция по монтажу (нар. блок)
- Daikin FHQ140CB_RZQSG140L9V Инструкция по монтажу (внутр. блок)
- Daikin FHQ71CB_RQ71BV Инструкция по эксплуатации
- Daikin FHQ71CB_RQ71BV Инструкция по монтажу (нар. блок)
- Daikin FHQ71CB_RQ71BV Инструкция по монтажу (внутр. блок)
- Daikin FHQ100CB_RQ100BV Инструкция по эксплуатации
- Daikin FHQ100CB_RQ100BV Инструкция по монтажу (нар. блок)
- Daikin FHQ100CB_RQ100BV Инструкция по монтажу (внутр. блок)
- Daikin FHQ125CB_RQ125B Инструкция по эксплуатации
- Daikin FHQ125CB_RQ125B Инструкция по монтажу (нар. блок)
- Daikin FHQ125CB_RQ125B Инструкция по монтажу (внутр. блок)
- Daikin FHQ71CB_RR71BV Инструкция по эксплуатации
- Daikin FHQ71CB_RR71BV Инструкция по монтажу (нар. блок)
- Daikin FHQ71CB_RR71BV Инструкция по монтажу (внутр. блок)
- Daikin FHQ100CB_RR100BV Инструкция по эксплуатации