12Technicaldata
Installerreferenceguide
42
RZQG71~140L_V1+Y1+RZQSG100~140L_V1+Y1
Splitsystemairconditioners
4P3855221–2014.08
RZQG71_V1 RZQG100_V1 RZQG125_V1 RZQG140_V1
NightquietCooling Soundpressure 43dBA 45dBA
NightquietHeating Soundpressure
Refrigerant
Type R410A
Charge 2.9kg 4.0kg
Control Expansionvalve(electronictype)
Nr.ofcircuits 1
Refrigerantoil
Type FVC50K
Chargedvolume 0.9l 1.35l
PED
Categoryofunit 1
ExcludedfromPEDduetoarticle1,item3.6of97/23/EC
Pipingconnections
Liquid Quantity 1
Type Flareconnection
Diameter(OD) Ø9.52mm
Gas Quantity 1
Type Flareconnection
Diameter(OD) Ø15.9mm
Drain Quantity 5
Type Hole
Diameter(OD) Ø26mm
Pipinglength Minimum 3m
Whenpipinglengthis<5m,acompleterechargeoftheunitisrequired.
Maximum 50m 75m
Equivalent 70m 90m
Chargeless 30m
Additionalrefrigerantcharge See"Todeterminetheadditionalrefrigerantamount"
Maximumheightdifferencebetweenoutdoor
unitandindoorunit
30m
Maximuminterunitleveldifference 0.5m
Heatinsulation Bothliquidandgaspipes
Defrostmethod Reversecycle
Defrostcontrol Sensorforoutdoorheatexchangertemperature
Capacitycontrolmethod Invertercontrolled
Capacitycontrol
Cooling Minimum
Maximum
Heating Minimum
Maximum
Safetydevices Highpressureswitch/lowpressureswitch/fandriveroverloadprotector/fuse
Standardaccessories 1installationmanual/2tiewraps
Electricalspecifications:RZQG_V1
RZQG71_V1 RZQG100_V1 RZQG125_V1 RZQG140_V1
Powersupply
Name V1
Phase 1~
Frequency 50Hz
Voltage 220240V
Voltagerange Minimum 198V
Maximum 264V
Current