ANOMALY PRESENCE
Anomalies have 2 possible effects:
1 The sysem goes in non-volatile lockout;
2 The system become non-active, but restarts working properly if the anomaly disappears;
#
DESCIPTION EFFECT RED LED SIGNAL
1 Flow air sensor damaged Burner non active SLOW FLASHING
2 Flame lost Non-volatile lockout (manual request required) LED ON
3 Over-heat burner non active Burner (if the anomay disappears, the
burner restarts working). Post ventilation while
T>Tamb + 10°C
SLOW FLASHING
4 Fan damaged before start up cycle Non-volatile lockout after 30s or less LED ON
5 Fan damaged after fl ow sensor
control
Non-volatile lockout for safety thermostat
temperature
LED ON
6 Fan damaged before 1 min. 30 sec
from running position
Non-volatile lockout for safety thermostat
temperature
LED ON
7 Fan damaged after 1 min and 30 sec.
from running
Not working Burner ans start post ventilation LED ON