7 Configuration
Installer and user reference guide
31
RXYSQ8~12TMY1B
VRV IV-S system air conditioner
4P404225-1A – 2015.11
# Action Button/display
2 Check the status of LED
H6P.
H6P OFF: Unit is currently
not operating under low noise
restrictions.
H6P ON: Unit is currently
operating under low noise
restrictions.
Example: 7‑LEDs display – Mode1
(in case of RXYSQ8)
You can read out setting [1‑5] (= the total number of connected
indoor units) as follows:
# Action Button/display
1 Start from the default
situation.
2 Select mode 1.
BS1 [1×]
3 Select setting 5.
("X×" depends on the setting
that you want to select.)
BS2 [X×]
(= binary 5)
4 Display the value of setting 5.
(there are 8 indoor units
connected)
BS3 [1×]
(= binary 8)
5 Quit mode 1.
BS1 [1×]
Example: 7‑segments display – Mode1
(in case of RXYSQ10+12)
You can read out setting [1‑10] (= the total number of connected
indoor units) as follows:
# Action Button/display
1 Start from the default
situation.
2 Select mode 1.
BS1 [1×]
3 Select setting 10.
("X×" depends on the setting
that you want to select.)
BS2 [X×]
4 Display the value of setting
10.
(there are 8 indoor units
connected)
BS3 [1×]
5 Quit mode 1.
BS1 [1×]
7.2.6 To use mode 2
In mode 2 you can make field settings to configure the system. How
to do this differs slightly depending on the model.
Example: 7‑LEDs display – Mode 2
(in case of RXYSQ8)
You can change the value of setting [2‑8] (= T
e
target temperature
during cooling operation) to 4 (=8°C) as follows:
# Action Button/display
1 Start from the default
situation.
2 Select mode 2.
BS1 [5 s]
3 Select setting 8.
("X×" depends on the setting
that you want to select.)
BS2 [X×]
(= binary 8)
4 Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×"
depends on the current
value, and the value that you
want to select.)
c: Enter the value in the
system.
d: Confirm. The system starts
operating according to the
setting.
BS2 [X×]b
a
BS3 [1×]c
BS3 [1×]d
BS3 [1×]
5 Quit mode 2.
BS1 [1×]
Example: 7‑segments display – Mode 2
(in case of RXYSQ10+12)
You can change the value of setting [2‑8] (= T
e
target temperature
during cooling operation) to 4 (=8°C) as follows:
# Action Button/display
1 Start from the default
situation.
2 Select mode 2.
BS1 [5 s]
3 Select setting 8.
("X×" depends on the setting
that you want to select.)
BS2 [X×]
4 Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×"
depends on the current
value, and the value that you
want to select.)
c: Enter the value in the
system.
d: Confirm. The system starts
operating according to the
setting.
BS3 [1×]
BS2 [X×]b
a
BS3 [1×]c
BS3 [1×]d
5 Quit mode 2.
BS1 [1×]
7.2.7 Mode 1 (and default situation): Monitoring
settings
In mode 1 (and in default situation) you can read out some
information. What you can read out differs depending on the model.
7‑LEDs display – Default situation (H1P OFF)
(in case of RXYSQ8)
You can read out the following information: