13.8 Capacity table: Indoor unit
Total capacity of indoor units needs to be within the specified range.
The connection ratio (CR): 50%≤CR≤130%.
HP class of
outdoor
unit
50%
minimum
CR
(VRVDX)
80%
minimum
CR (RADX)
100%
nominal CR
130%
maximum
CR
8 100 160 200 260
10 125 200 250 325
12 150 240 300 390
NOTICE
When selecting the total capacity higher than mentioned in
above table, cooling and heating capacity will drop. For
additional information see technical engineering data.