Mitsubishi Electric MSZ-SF20VA [2/12] Beforeinstallation

Mitsubishi Electric MSZ-SF15VA [2/12] Beforeinstallation
En-1
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
• Besuretoobservethewarningsandcautionsspeciedhereastheyincludeimportantitemsrelatedtosafety.
• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.
1-2. SELECTING THE INSTALLATION LOCATION
CAUTION
(Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincorrectly.)
Required Tools for Installation
Phillipsscrewdriver
Level
Scale
Utility
knifeorscissors
65mmholesaw
Torque wrench
Wrench(orspanner)
4mmhexagonalwrench
Flare tool for R410A
GaugemanifoldforR410A
VacuumpumpforR410A
ChargehoseforR410A
Pipecutterwithreamer
n
Do not install the unit by yourself (user).
Incomplete installation could cause fire, electric
shock, injury due to the unitfalling, or leakage
ofwater.Consultthedealerfromwhomyoupur-
chased
theunitoraqualiedinstaller.
n
Perform the installation securely referring to
the installation manual.
Incomplete installation could cause fire, electric
shock,injuryduetotheunitfalling,orleakageof
water.
n
When installing the unit, use appropriate pro-
tective
equipment and tools for safety.
Failuretodosocouldcauseinjury.
n
Install the unit securely in a place which can
bear the weight of the unit.
If the installation location cannot bear the weight
oftheunit,theunitcouldfallcausinginjury.
n
E
lectrical work should be performed by a
qualied, experienced electrician, according
to the installation manual. Be sure to use an ex-
c
lusive circuit. Do not connect other electrical
appliances to the circuit.
Ifthecapacityofthepowercircuitisinsufcientor
thereisincompleteelectricalwork,itcouldresult
inareoranelectricshock.
n
Earth the unit correctly.
Donot connect the earth to a gas pipe, water
pipe, lightning rod ortelephone earth. Defective
earthingcouldcauseelectricshock.
n
Do not damage the wires by applying exces-
sive
pressure with parts or screws.
Damagedwirescouldcausereorelectricshock.
n
Be
sure to cut off the main power in case of
setting up the indoor P.C. board or wiring
works.
Failuretodosocouldcauseelectricshock.
n
U
se the specied wires to connect the indoor
and outdoor units securely and attach the
wires rmly to the terminal block connecting
s
ections so the stress of the wires is not ap-
plied to the sections. Do not extend the wires,
o
r use intermediate connection.
Incompleteconnectingandsecuringcouldcause
re.
n
Do not install the unit in a place where inam-
mable
gas may leak.
Ifgasleaksandaccumulatesintheareaaround
theunit,itcouldcauseanexplosion.
n
Do not use intermediate connection of the
power cord or the extension cord and do not
connect
many devices to one AC outlet.
It could cause a re or an electric shock dueto
defectivecontact,defectiveinsulation,exceeding
thepermissiblecurrent,etc.
n
Be sure to use the parts provided or specied
parts
for the installation work.
Theuseofdefectivepartscouldcauseaninjuryor
leakageofwaterduetoare,anelectricshock,the
unitfalling,etc.
n
W
hen plugging the power supply plug into the
outlet, make sure that there is no dust, clogging,
or loose parts in both the outlet and the plug.
Make sure that the power supply plug is pushed
completely into the outlet.
Ifthereisdust,clogging,orloosepartsonthepower
supplyplugortheoutlet,itcouldcauseelectric
shockorre.Ifloosepartsarefoundonthepower
supplyplug,replaceit.
n
Attach
the electrical cover to the indoor unit
and the service panel to the outdoor unit
securely.
If the electrical cover of the indoor unit and/or the
service panel of the outdoor unit are not attached
securely,itcouldresultinareoranelectricshock
duetodust,water,etc.
n
When
installing, relocating, or servicing the
unit, make sure that no substance other than
the specied refrigerant (R410A) enters the
refrigerant
circuit.
Any presence of foreign substance such as air
cancauseabnormalpressureriseandmayresult
inexplosion or injury. Theuse of anyrefrigerant
otherthanthatspeciedforthesystemwillcause
mechanical failure,systemmalfunction, or unit
breakdown.Intheworstcase,thiscouldleadtoa
seriousimpedimenttosecuringproductsafety.
n
D
o not discharge the refrigerant into the atmos-
p
here. If refrigerant leaks during installation,
ventilate the room.
Ifrefrigerantcomesincontactwithare,harmful
gascouldbegenerated.Refrigerantleakagemay
cause suffocation. Provide ventilation in accord
-
ance
with EN378-1.
n
Check
that the refrigerant gas does not leak
after installation has been completed.
If refrigerantgas leaks indoors, and comes into
contactwith theflame of a fanheater,space
heater, stove, etc., harmful substances will be
generated.
n
Use
appropriate tools and piping materials for
installation.
The pressure of R410A is 1.6 times more than
R22.Notusingappropriatetoolsormaterialsand
incomplete installation could cause the pipes to
burstorinjury.
n
When
pumping down the refrigerant, stop the
compressor before disconnecting the refriger-
ant
pipes.
If the refrigerant pipes are disconnected while the
compressorisrunningandthestopvalveisopen,
air could be drawn in and the pressure in the re
-
f
rigerationcycle could become abnormally high.
Thiscouldcausethepipestoburstorinjury.
n
When
installing the unit, securely connect the
refrigerant pipes before starting the compres-
sor.
Ifthecompressorisstartedbeforetherefrigerant
pipes are connected and when the stop valve is
open, air could be drawn in and the pressurein
the refrigerationcycle could become abnormally
high.Thiscouldcausethepipestoburstorinjury.
n
Fasten a are nut with a torque wrench as
specied in this manual.
Iffastenedtootight,aarenutmaybreakaftera
longperiodandcauserefrigerantleakage.
n
The
unit shall be installed in accordance with
national wiring regulations.
n
Install
an earth leakage breaker depending on
the installation place.
If an earth leakagebreaker isnot installed,it
couldcauseelectricshock.
n
Perform the drainage/piping work securely ac-
cording
to the installation manual.
Ifthereisdefectinthedrainage/pipingwork,wa-
ter
coulddropfromtheunit,soakinganddamag-
ing
household goods.
n
Do not touch the air inlet or the aluminum ns
of
the outdoor unit.
Thiscouldcauseinjury.
n
Do not install the outdoor unit where small
animals may live.
Ifsmallanimalsenterandtouchtheelectricparts
inside the unit, it could cause a malfunction,
smokeemission,orre.Also,adviseusertokeep
the area around the unit clean.
INDOOR UNIT
• Whereairowisnotblocked.
•
Wherecoolairspreadsovertheentireroom.
Rigid wall without vibration.
• Whereitisnotexposedtodirectsunshine.Donot
expose to direct sunshine also during the period
followingunpackingtobeforeuse.
• Whereeasilydrained.
• Atadistance1mormoreawayfromyourTVand
radio.Operationoftheairconditionermayinterfere
with radio or TV reception. An amplifier may be
required for the affected device.
• Inaplaceasfarawayaspossiblefromuorescent
and incandescentlights(so the infrared remote
controlcanoperatetheairconditionernormally).
• Wheretheair ltercanbe removedandreplaced
easily.
REMOTE CONTROLLER
• Whereitiseasytooperateandeasilyvisible.
Where children cannot touch it.
• Selectapositionabout1.2mabovetheoorand
check that signals fromthe remote controller are
surely received by theindoor unit from thatposi
-
tion
(‘beep’or‘beepbeep’receivingtonesounds).
Afterthat,attachremotecontrollerholdertoapillar
orwallandinstallwirelessremotecontroller.
Note:
Inroomswhereinvertertypeuorescentlampsare
used,thesignalfromthewirelessremotecontroller
maynotbereceived.
Note:
Avoid the following places for installation where air
conditioner trouble is liable to occur.
• Whereammablegascouldleak.
• Wherethereismuchmachineoil.
• Whereoilissplashedorwheretheareaislled
withoilysmoke(suchascookingareasandfac
-
tories,
inwhichthepropertiesofplasticcouldbe
changedanddamaged).
• Saltyplacessuchastheseaside.
• Where sulde gas is generated such as a hot
spring.
•
Wherethereishigh-frequencyorwirelessequip-
ment.
•
WherethereisemissionofhighlevelsofVOCs,
including phthalate compounds, formaldehyde,
etc.,whichmaycausechemicalcracking.
WARNING
(Couldleadtodeath,seriousinjury,etc.)
ENGLISH
Thisinstallationmanualde-
scribesonlyfortheindoorunit.
RefertotheMXZtypemanualfor
outdoor unit set up.
CONTENTS
1. BEFORE INSTALLATION ..................................1
2. INDOOR UNIT INSTALLATION .........................3
3.
PURGINGPROCEDURES,LEAKTEST,AND
TEST RUN .........................................................5
4.
RELOCATIONANDMAINTENANCE ................5
English is
original.
JG79A682H01_en.indd 1 2013/01/28 (月) 午後 4:40:52