Mitsubishi Electric PKA-RP100KAL / PUHZ-SHW112YHA [2/34] Safetyprecautions
![Mitsubishi Electric PKA-RP71KAL / PUHZ-ZRP71VHA [2/34] Safetyprecautions](/views2/1330965/page2/bg2.png)
2
► Before installing the unit, make sure you read all the “Safety
precautions”.
► Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
Contents
Warning:
• Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and
use tools and pipe components specifically made for use with refrigerant
specified in the outdoor unit installation manual.
• The unit must be installed according to the instructions in order to
minimize the risk of damage from earthquakes, typhoons, or strong winds.
An incorrectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its
weight.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration in the room from exceeding the
safety limit in the event of refrigerant leakage. Should the refrigerant leak
and cause the concentration limit to be exceeded, hazards due to lack of
oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant
comes into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual.
• Use only specified cables for wiring.
• The terminal block cover panel of the unit must be firmly attached.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or
an authorized technician to install them.
• The user should never attempt to repair the unit or transfer it to another
location.
• After installation has been completed, check for refrigerant leaks. If
refrigerant leaks into the room and comes into contact with the flame of a
heater or portable cooking range, poisonous gases will be released.
• When installing or relocating, or servicing the air conditioner, use only the
specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it
with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal
high pressure in the refrigerant line, and may result in an explosion and
other hazards.
The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
1.1. Before installation (Environment)
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is
installed in areas exposed to steam, volatile oil (including machine oil), or
sulfuric gas, areas exposed to high salt content such as the seaside, the
performance can be significantly reduced and the internal parts can be
damaged.
• Do not install the unit where combustible gases may leak, be produced,
flow, or accumulate. If combustible gas accumulates around the unit, fire
or explosion may result.
• Do not keep food, plants, caged pets, artwork, or precision instruments in
the direct airflow of the indoor unit or too close to the unit as these items
can be damaged by temperature changes or dripping water.
• When the room humidity exceeds 80% or when the drainpipe is clogged,
water may drip from the indoor unit. Do not install the indoor unit where
such dripping can cause damage.
• When installing the unit in a hospital or communications office, be
prepared for noise and electronic interference. Inverters, home appliances,
high-frequency medical equipment, and radio communications equipment
can cause the air conditioner to malfunction or breakdown. The air
conditioner may also affect medical equipment, disturbing medical care,
and communications equipment, harming the screen display quality.
1. Safety precautions
After installation work has been completed, explain the “Safety precautions,” use,
and maintenance of the unit to the customer according to the information in the
Operation Manual and perform the test run to ensure normal operation. Both the
Installation Manual and Operation Manual must be given to the user for keeping.
These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
1.4. Before starting the test run
Caution:
• Turn on the main power switch more than 12 hours before starting
operation. Starting operation just after turning on the power switch can
severely damage the internal parts.
• Before starting operation, check that all panels, guards and other
protective parts are correctly installed. Rotating, hot, or high voltage parts
can cause injuries.
• Do not operate the air conditioner without the air filter set in place. If the
air filter is not installed, dust may accumulate and breakdown may result.
• Do not touch any switch with wet hands. Electric shock may result.
• Do not touch the refrigerant pipes with bare hands during operation.
•
After stopping operation, be sure to wait at least five minutes before turning
off the main power switch. Otherwise, water leakage or breakdown may result.
1.3. Before electric work
Caution:
• Be sure to install molded case circuit brakers. If not installed, electric
shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise,
a short circuit, overheating, or fire may result.
• When installing the power lines, do not apply tension to the cables.
• Be sure to ground the unit. If the unit is not properly grounded, electric
shock may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse),
and molded case circuit breaker) with the specified capacity. If the circuit
breaker capacity is larger than the specified capacity, breakdown or fire
may result.
1.2. Before installation or relocation
Caution:
• Be extremely careful when transporting the units. Two or more persons
are needed to handle the unit as it weighs 20 kg or more. Do not grasp the
packaging bands. Wear protective gloves as you can injure your hands on
the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials,
such as nails and other metal or wooden parts may cause stabs or other
injuries.
• Thermal insulation of the refrigerant pipe is necessary to prevent
condensation. If the refrigerant pipe is not properly insulated, condensation
will be formed.
• Place thermal insulation on the pipes to prevent condensation. If the
drainpipe is installed incorrectly, water leakage and damage to the ceiling,
floor, furniture, or other possessions may result.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened
too much, the flare nut can break after an extended period.
1. Safety precautions .............................................................................................
2
2. Installation location ............................................................................................
3
3. Installing the indoor unit ....................................................................................
3
4. Installing the refrigerant piping ..........................................................................
7
5. Drainage piping work .........................................................................................
8
6. Electrical work ...................................................................................................
9
7. Test run ............................................................................................................
14
8. Easy maintenance function (Option) ...............................................................
16
Содержание
- Air conditioners 1
- Deutsch 1
- English 1
- Español 1
- Eγxeipiδio oδhγiωn eγkataσtaσhσ 1
- Français 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands 1
- Pka rp kal 1
- Português 1
- Svenska 1
- Türkçe 1
- Ελληνικά 1
- Руководство по установке 1
- Русский 1
- 中文 1
- 安装说明书 1
- Beforeelectricwork 2
- Beforeinstallation environment 2
- Beforeinstallationorrelocation 2
- Beforestartingthetestrun 2
- Contents 2
- Safetyprecautions 2
- Checktheindoorunitaccessories fig 1 3
- Drillingthepipinghole fig 3 3
- Installationlocation 3
- Installingtheindoorunit 3
- Installingthewallmountingfixture fig 3
- Outlinedimensions indoorunit fig 1 3
- Pka rp60 71 100kal 3
- Settingthewallmountingfixtureandpipingpositions 3
- Fig 10 fig 9 4
- Fig 7 fig 6 4
- Installingtheindoorunit 4
- Installingthewallmountingfixture 4
- Lowerpiping fig 7 4
- Pka rp60 71 100kal 4
- Pka rp60 71 100kal attachmentofl shapedconnectionpipe 4 right leftandrearpiping fig 6 4
- Pka rp60 71 100kal fig 4 4
- Preparingtheindoorunit 4
- Whenembeddingpipesintothewall fig 5 4
- Extractionandprocessingofthepipingandwiring fig 11 5
- Fig 11 5
- Fig 13 5
- Installingtheindoorunit 5
- Leakagecheckofthel shapedconnectionpipeconnectionportion 5
- Leftandleftrearpiping fig 13 5
- Rear rightandlowerpiping fig 1 5
- Fig 14 6
- Fig 15 6
- Fig 16 6
- Installingtheindoorunit 6
- Leftandleftrearpiping fig 16 6
- Mountingtheindoorunit 6
- Pka rp60 71 100kal 6
- Rear rightandlowerpiping fig 14 6
- Connectingpipes fig 1 7
- Indoorunit 7
- Installingtherefrigerantpiping 7
- Positioningrefrigerantanddrainpiping fig 7
- Refrigerantpiping fig 3 7
- Checkofdrainage fig 4 8
- Drainagepipingwork 8
- Drainagepipingwork fig 1 8
- Preparingleftandleftrearpiping fig 8
- Storinginthepipingspaceoftheindoorunit fig 3 8
- 1 system 9
- Electricalwork 9
- Indoorunit 9
- Indoorunitpowersuppliedfromoutdoorunit 9
- Pka rp60 71 100kal 9
- Pka rp60 71 100kal fig 1 9
- Simultaneous twin triple four system 9
- 1 system 10
- 3 installanearthlongerthanothercords 10
- Affix a label b that is included with the manuals near each wiring diagram for the indoor and outdoor units 10
- Electricalwork 10
- Notes 1 wiringsizemustcomplywiththeapplicablelocalandnationalcode powersupplycordsandindoorunit outdoorunitconnectingcordsshallnotbelighterthanpolychloroprenesheathedflexiblecord design 45iec 10
- Separateindoorunit outdoorunitpowersupplies forpuhzapplicationonly 10
- Simultaneous twin triple four system 10
- The following connection patterns are available the outdoor unit power supply patterns vary on models 10
- The optional wiring replacement kit is required 10
- The optional wiring replacement kits are required 10
- Electricalwork 11
- Forwiredremotecontroller optionalparts 1 installingprocedures 11
- On off 1 2 sw8 11
- Remotecontroller 11
- Assigningaremotecontrollertoeachunit fig 7 12
- Connectingprocedures fig 4 12
- Electricalwork 12
- Forwirelessremotecontroller 1 installationarea 12
- Functionsettingontheunit selectingtheunitfunctions 1 forwiredremotecontroller fig 8 12
- Functionsettings 12
- Installationmethod fig 5 12
- Setting fig 6 12
- Tworemotecontrollerssetting 12
- Wirelessremotecontrollerpairnumbersettingoperation 12
- Electricalwork 13
- Forwirelessremotecontroller fig 9 13
- Functionsettingontheremotecontroller 13
- Functiontable 13
- Beforetestrun 14
- M i hg 14
- Self check 14
- Testrun 14
- Testrun 15
- Displayexample compdischargetemperature64 c 16
- Easymaintenancefunction option 16
- Testrun 16
- 1 press the 17
- 2 press the temp buttons to set the refrigerant address 17
- 3 select the data you want to display 17
- 4 press the 17
- 5 the data is displayed in c 17
- 6 press the 17
- Activate the maintenance mode 17
- Button 17
- Button for three seconds or press the 17
- Button for three seconds to 17
- Button to select the operation mode 17
- Easymaintenancefunction option 17
- Maintenance mode operation procedures 17
- Operation can be stabilized if the air conditioner is stopped use the following procedure to start this operation 17
- Operation procedures while waiting for the stable operation 17
- Press the 17
- Repeat steps 2 to 5 to check another date 17
- Stableoperation using the maintenance mode the operation frequency can be fixed and the 17
- The filter operation time displayed is the number of hours the filter has been 17
- To deactivate the maintenance mode 17
- Used since the filter reset was performed 17
- You can check the data using steps 3 to 5 of the maintenance mode 17
- Мерыпредосторожности 18
- Передтестовымпрогоном 18
- Передустановкой окружающаясреда 18
- Передустановкойилиперемещением 18
- Передэлектрическимиработами 18
- Содержание 18
- Контурныегабариты внутреннийприбор рис 1 19
- Местоустановки 19
- Проверьтеналичиедополнительных принадлежностейквнутреннемуприбору рис 1 19
- Рис 1 19
- Рис 2 19
- Рис 3 19
- Установкавнутреннегоприбора 19
- Установканастенногокрепления рис 2 19
- Pka rp60 71 100kal 20
- Pka rp60 71 100kal подсоединениеl образнойсоединительнойтрубки 4 правые левыеинижниетрубопроводы рис 6 20
- Pka rp60 71 100kal рис 4 20
- Встраиваниетрубвстены рис 5 20
- Нижняятрубка рис 7 20
- Подготовкавнутреннегоблока 20
- Рис 10 рис 9 20
- Рис 4 20
- Рис 5 20
- Рис 7 рис 6 20
- Рис 8 20
- Установкавнутреннегоприбора 20
- Установканастенногокронштейна 20
- Извлечениеиобработкатрубопроводовиэлектропроводки рис 11 21
- Леваяилеваянижняятрубки рис 13 21
- Правые левыеинижниетрубопроводы рис 12 21
- Рис 11 21
- Рис 12 21
- Рис 13 21
- Тестнапротечкусоединительнойчастиl образной соединительнойтрубки 21
- Установкавнутреннегоприбора 21
- Pka rp60 71 100kal 22
- Леваяилеваянижняятрубки рис 16 22
- Правые левыеинижниетрубопроводы рис 14 22
- Рис 14 22
- Рис 15 22
- Рис 16 22
- Установкавнутреннегоблока 22
- Установкавнутреннегоприбора 22
- Внутреннийблок 23
- Выборрасположениятрубхладагентаи дренажныхтруб рис 2 23
- Прокладкатрубхладагента 23
- Рис 1 23
- Рис 2 23
- Рис 3 23
- Рис 4 23
- Соединениетруб рис 1 23
- Трубыхладагента рис 3 23
- Дренажныетрубы 24
- Дренажныетрубы рис 1 24
- Подготовкатрубслеваислевасзади рис 2 24
- Проверкадренажа рис 4 24
- Рис 1 24
- Рис 2 24
- Рис 3 24
- Рис 4 24
- Укладкавместодлятрубоквнутреннегоблока рис 3 24
- Pka rp60 71 100kal 25
- Pka rp60 71 100kal рис 1 25
- Внутреннийблок 25
- Одновременная двойная тройная четверная система 25
- Питаниенавнутреннийприборподаетсяотнаружногоприбора 25
- Рис 1 25
- Система 1 1 25
- Электрическиеработы 25
- Имеются следующие шаблоны подключения конструкция блока питания внешнего прибора зависит от модели 26
- Одновременная двойная тройная четверная система 26
- Отдельныеисточникиэлектропитаниядлявнутреннегоприбора наружногоприбора толькодляпримененияpuhz 26
- Прикрепите бирку b прилагаемую к руководствам около каждой схемы подключения для внутреннего и наружного приборов 26
- Примечания 1 диаметрпроводовдолженсоответствоватьприменимымместныминациональнымнормам 2 силовыекабелиикабелисоединениявнутреннего наружногоприборанедолжныбытьлегчеэкранированногогибкогопроводаиз полихлоропрена модель245iec57 3 длинаустанавливаемогокабелязаземлениядолжнапревышатьдлинудругихкабелей 26
- Система 1 1 26
- Требуется дополнительный сменный комплект проводки 26
- Требуются дополнительные комплекты для замены проводов 26
- Электрическиеработы 26
- On off 1 2 sw8 27
- Дляпроводногопультадистанционногоуправления дополнительныедетали 1 процедураустановки 27
- Пультдистанционногоуправления 27
- Рис 2 27
- Рис 3 27
- Электрическиеработы 27
- Длябеспроводногопультадистанционногоуправления 1 местаустановки 28
- Дляпроводногопультадистанционногоуправления рис 8 28
- Методустановки рис 5 28
- Настройка рис 6 28
- Настройкадвухпультовдистанционногоуправления 28
- Операциисоединения рис 4 28
- Приписаниепультадистанционногоуправленияотдельным приборам рис 7 28
- Процедуранастройкиномерапарыпультадистанционного 28
- Рис 4 28
- Рис 5 28
- Рис 6 28
- Рис 7 28
- Рис 8 28
- Управления 28
- Установкифункций 28
- Электрическиеработы 28
- Длябеспроводногопультадистанционногоуправления рис 9 29
- Рис 9 29
- Таблицафункций 29
- Функциональнаянастройканапультедистанционногоуправления 29
- Электрическиеработы 29
- M i hg 30
- Выполнениеиспытания 30
- Передпробнымпрогоном 30
- Рис 1 30
- Рис 2 30
- Рис 3 30
- Рис 4 30
- Самодиагностика 30
- Выполнениеиспытания 31
- Выполнениеиспытания 32
- Примердисплея температуранагнетаниякомпрессора64 c 32
- Функцияпростоготехобслуживания опция 32
- 1 нажмите и удерживайте в течение трех 33
- 2 нажмите temp темп нажмите temp темп 33
- 3 выберите данные которые необходимо отобразить 33
- 4 нажмите кнопку 33
- 5 данные отображаются в c 33
- 6 нажмите и удерживайте в течение трех секунд кнопку 33
- Время работы фильтра отображается в виде количества часов 33
- Данные можно проверить выполнив шаги с 3 по 5 процедур по 33
- Для включения режима 33
- Для выбора режима работы 33
- Или 33
- Использования фильтра с момента выполнения сброса фильтра 33
- Нажмите кнопку 33
- Повторите шаги со 2 по 5 для проверки другой даты 33
- Процедуры работы в режиме техобслуживания 33
- Работе в режиме техобслуживания ожидая стабильной работы 33
- Секунд кнопку 33
- Стабильнаяработа используя режим техобслуживания можно зафиксировать рабочую частоту 33
- Техобслуживания 33
- Функцияпростоготехобслуживания опция 33
- Что приведет к стабилизации работы если кондиционер остановлен используйте следующую процедуру чтобы начать данную операцию 33
- Чтобы отключить режим техобслуживания 33
Похожие устройства
- Mitsubishi Electric PKA-RP100KAL / PUHZ-SHW112YHA Сертификат
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100YHA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100YHA Руководство по установке
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100YHA Сертификат
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100VKA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100VKA Руководство по установке
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100VKA Сертификат
- Mitsubishi Electric PLA-RP50BA / PUHZ-ZRP50VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP50BA / PUHZ-ZRP50VHA Руководство по установке
- Mitsubishi Electric PLA-RP50BA / PUHZ-ZRP50VHA Сертификат
- Mitsubishi Electric PLA-RP35BA / PUHZ-ZRP35VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP35BA / PUHZ-ZRP35VHA Руководство по установке
- Mitsubishi Electric PLA-RP35BA / PUHZ-ZRP35VHA Сертификат
- Mitsubishi Electric PLA-RP71BA / PUHZ-ZRP71VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP71BA / PUHZ-ZRP71VHA Руководство по установке
- Mitsubishi Electric PLA-RP71BA / PUHZ-ZRP71VHA Сертификат
- Mitsubishi Electric PLA-RP60BA / PUHZ-ZRP60VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP60BA / PUHZ-ZRP60VHA Руководство по установке
- Mitsubishi Electric PLA-RP60BA / PUHZ-ZRP60VHA Сертификат
- Graude IKG 180.0 Инструкция по эксплуатации