3. Installing the indoor unit
Fig. 3-4
A
B
C
D
I
G
F
H
E
PKA-RP60, 71, 100KAL
Fig. 3-5
Fig. 3-7Fig. 3-6
A A
Fig. 3-8
A
B
D
C
E
Fig. 3-10Fig. 3-9
B
A
C
D
3.2.3. Installing the wall mounting fixture
► Since the indoor unit weighs near 21 kg, selection of the mounting
location requires thorough consideration. If the wall does not seem to be
strong enough, reinforce it with boards or beams before installation.
► The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(If possible, secure the fixture at all the positions marked with a bold arrow.)
Warning:
If possible, secure the fixture at all positions indicated with a bold arrow.
Caution:
• The unit body must be mounted horizontally.
• Fastenattheholesmarkedwith▲asshownbythearrows.
PKA-RP60, 71, 100KAL (Fig. 3-4)
AMin. 120 mm (617.6 mm or greater with optional drain pump installation)
BMin. 220 mm
CMin. 70 mm (130 mm or greater with left, rear left, or lower left piping, and optional drain
pump installation)
DFixing screws (4 × 25) 2
ELevel
FFasten a thread to the hole.
G
Place the level against the horizontal reference line of the mount board and mount so that it is
level. Hang a weight from the thread and align with EPK of the mount board to permit leveling.
HWeight
IMount board 1
3.3. When embedding pipes into the wall (Fig. 3-5)
• The pipes are on the bottom left.
• When the cooling pipe, drain pipes internal/external connection lines etc are to
be embedded into the wall in advance, the extruding pipes etc, may have to be
bent and have their length modified to suit the unit.
• Use marking on the mount board as a reference when adjusting the length of the
embedded cooling pipe.
• During construction, give the length of the extruding pipes etc some leeway.
AMount board 1
BReference marking for flare connection
CThrough hole
DOn-site piping
3.4. Preparing the indoor unit
* Check beforehand because the preparatory work will differ depending on the
exiting direction of the piping.
* When bending the piping, bend gradually while maintaining the base of the
piping exiting portion. (Abrupt bending will cause misshaping of the piping.)
PKA-RP60, 71, 100KAL
Attachment of L-shaped connection pipe 4
Right, left and rear piping (Fig. 3-6)
1. Remove the flare nut and cap of the indoor unit. (Gas pipe only)
2. Apply refrigerating machine oil to the flare sheet surface. (Preparation on
location)
3. Facing the direction in which the L-shaped connection pipe
4 will be removed,
make a quick connection to the indoor unit flare connection opening.
4. Tighten the flare nut using a double open-end wrench. (Fig. 3-9)
Tightening force: 68 to 82 N•m
5. Attach the charge nut
5 to the liquid pipe side joint portion, and check for
leakage of the L-shaped connection pipe 4 connection portion.
Remove the charge nut
5 after completion of the work.
Tightening force: 34 to 42 N•m
6. Cover the flare connection portion with the pipe cover of the L-shaped
connection pipe 4 so that it is not exposed. (Fig. 3-10)
AL-shaped connection pipe 4
BCut-off position (Straight pipe portion)
CTightening direction
DCover with pipe cover
E Cover the flare nut connection portion with the pipe cover.
Lower piping (Fig. 3-7)
1. Cut L-shaped connection pipe 4 at the position indicated in (Fig. 3-8).
2. Insert the flare nut that was removed earlier onto the straight pipe side of the cut
L-shaped connection pipe 4 and then flare the end of the pipe.
3. Remove the flare nut and cap of the indoor unit. (Gas pipe only)
4. Apply refrigerating machine oil to the flare sheet surface. (Preparation on
location)
5. Quickly connect the L-shaped connection pipe
4 that has been processed as
described in part 2) to the indoor unit flare connection opening.
6. Tighten the flare nut using a double open-end wrench. (Fig. 3-9)
Tightening force: 68 to 82 N•m
7. Attach the charge nut
5 to the liquid pipe side joint portion, and check for
leakage of the L-shaped connection pipe 4 connection portion.
Remove the charge nut
5 after completion of the work.
Tightening force: 34 to 42 N•m
8. Cover the flare connection portion with the pipe cover of the L-shaped
connection pipe 4 so that it is not exposed. (Fig. 3-10)
Содержание
- Air conditioners 1
- Deutsch 1
- English 1
- Español 1
- Eγxeipiδio oδhγiωn eγkataσtaσhσ 1
- Français 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands 1
- Pka rp kal 1
- Português 1
- Svenska 1
- Türkçe 1
- Ελληνικά 1
- Руководство по установке 1
- Русский 1
- 中文 1
- 安装说明书 1
- Beforeelectricwork 2
- Beforeinstallation environment 2
- Beforeinstallationorrelocation 2
- Beforestartingthetestrun 2
- Contents 2
- Safetyprecautions 2
- Checktheindoorunitaccessories fig 1 3
- Drillingthepipinghole fig 3 3
- Installationlocation 3
- Installingtheindoorunit 3
- Installingthewallmountingfixture fig 3
- Outlinedimensions indoorunit fig 1 3
- Pka rp60 71 100kal 3
- Settingthewallmountingfixtureandpipingpositions 3
- Fig 10 fig 9 4
- Fig 7 fig 6 4
- Installingtheindoorunit 4
- Installingthewallmountingfixture 4
- Lowerpiping fig 7 4
- Pka rp60 71 100kal 4
- Pka rp60 71 100kal attachmentofl shapedconnectionpipe 4 right leftandrearpiping fig 6 4
- Pka rp60 71 100kal fig 4 4
- Preparingtheindoorunit 4
- Whenembeddingpipesintothewall fig 5 4
- Extractionandprocessingofthepipingandwiring fig 11 5
- Fig 11 5
- Fig 13 5
- Installingtheindoorunit 5
- Leakagecheckofthel shapedconnectionpipeconnectionportion 5
- Leftandleftrearpiping fig 13 5
- Rear rightandlowerpiping fig 1 5
- Fig 14 6
- Fig 15 6
- Fig 16 6
- Installingtheindoorunit 6
- Leftandleftrearpiping fig 16 6
- Mountingtheindoorunit 6
- Pka rp60 71 100kal 6
- Rear rightandlowerpiping fig 14 6
- Connectingpipes fig 1 7
- Indoorunit 7
- Installingtherefrigerantpiping 7
- Positioningrefrigerantanddrainpiping fig 7
- Refrigerantpiping fig 3 7
- Checkofdrainage fig 4 8
- Drainagepipingwork 8
- Drainagepipingwork fig 1 8
- Preparingleftandleftrearpiping fig 8
- Storinginthepipingspaceoftheindoorunit fig 3 8
- 1 system 9
- Electricalwork 9
- Indoorunit 9
- Indoorunitpowersuppliedfromoutdoorunit 9
- Pka rp60 71 100kal 9
- Pka rp60 71 100kal fig 1 9
- Simultaneous twin triple four system 9
- 1 system 10
- 3 installanearthlongerthanothercords 10
- Affix a label b that is included with the manuals near each wiring diagram for the indoor and outdoor units 10
- Electricalwork 10
- Notes 1 wiringsizemustcomplywiththeapplicablelocalandnationalcode powersupplycordsandindoorunit outdoorunitconnectingcordsshallnotbelighterthanpolychloroprenesheathedflexiblecord design 45iec 10
- Separateindoorunit outdoorunitpowersupplies forpuhzapplicationonly 10
- Simultaneous twin triple four system 10
- The following connection patterns are available the outdoor unit power supply patterns vary on models 10
- The optional wiring replacement kit is required 10
- The optional wiring replacement kits are required 10
- Electricalwork 11
- Forwiredremotecontroller optionalparts 1 installingprocedures 11
- On off 1 2 sw8 11
- Remotecontroller 11
- Assigningaremotecontrollertoeachunit fig 7 12
- Connectingprocedures fig 4 12
- Electricalwork 12
- Forwirelessremotecontroller 1 installationarea 12
- Functionsettingontheunit selectingtheunitfunctions 1 forwiredremotecontroller fig 8 12
- Functionsettings 12
- Installationmethod fig 5 12
- Setting fig 6 12
- Tworemotecontrollerssetting 12
- Wirelessremotecontrollerpairnumbersettingoperation 12
- Electricalwork 13
- Forwirelessremotecontroller fig 9 13
- Functionsettingontheremotecontroller 13
- Functiontable 13
- Beforetestrun 14
- M i hg 14
- Self check 14
- Testrun 14
- Testrun 15
- Displayexample compdischargetemperature64 c 16
- Easymaintenancefunction option 16
- Testrun 16
- 1 press the 17
- 2 press the temp buttons to set the refrigerant address 17
- 3 select the data you want to display 17
- 4 press the 17
- 5 the data is displayed in c 17
- 6 press the 17
- Activate the maintenance mode 17
- Button 17
- Button for three seconds or press the 17
- Button for three seconds to 17
- Button to select the operation mode 17
- Easymaintenancefunction option 17
- Maintenance mode operation procedures 17
- Operation can be stabilized if the air conditioner is stopped use the following procedure to start this operation 17
- Operation procedures while waiting for the stable operation 17
- Press the 17
- Repeat steps 2 to 5 to check another date 17
- Stableoperation using the maintenance mode the operation frequency can be fixed and the 17
- The filter operation time displayed is the number of hours the filter has been 17
- To deactivate the maintenance mode 17
- Used since the filter reset was performed 17
- You can check the data using steps 3 to 5 of the maintenance mode 17
- Мерыпредосторожности 18
- Передтестовымпрогоном 18
- Передустановкой окружающаясреда 18
- Передустановкойилиперемещением 18
- Передэлектрическимиработами 18
- Содержание 18
- Контурныегабариты внутреннийприбор рис 1 19
- Местоустановки 19
- Проверьтеналичиедополнительных принадлежностейквнутреннемуприбору рис 1 19
- Рис 1 19
- Рис 2 19
- Рис 3 19
- Установкавнутреннегоприбора 19
- Установканастенногокрепления рис 2 19
- Pka rp60 71 100kal 20
- Pka rp60 71 100kal подсоединениеl образнойсоединительнойтрубки 4 правые левыеинижниетрубопроводы рис 6 20
- Pka rp60 71 100kal рис 4 20
- Встраиваниетрубвстены рис 5 20
- Нижняятрубка рис 7 20
- Подготовкавнутреннегоблока 20
- Рис 10 рис 9 20
- Рис 4 20
- Рис 5 20
- Рис 7 рис 6 20
- Рис 8 20
- Установкавнутреннегоприбора 20
- Установканастенногокронштейна 20
- Извлечениеиобработкатрубопроводовиэлектропроводки рис 11 21
- Леваяилеваянижняятрубки рис 13 21
- Правые левыеинижниетрубопроводы рис 12 21
- Рис 11 21
- Рис 12 21
- Рис 13 21
- Тестнапротечкусоединительнойчастиl образной соединительнойтрубки 21
- Установкавнутреннегоприбора 21
- Pka rp60 71 100kal 22
- Леваяилеваянижняятрубки рис 16 22
- Правые левыеинижниетрубопроводы рис 14 22
- Рис 14 22
- Рис 15 22
- Рис 16 22
- Установкавнутреннегоблока 22
- Установкавнутреннегоприбора 22
- Внутреннийблок 23
- Выборрасположениятрубхладагентаи дренажныхтруб рис 2 23
- Прокладкатрубхладагента 23
- Рис 1 23
- Рис 2 23
- Рис 3 23
- Рис 4 23
- Соединениетруб рис 1 23
- Трубыхладагента рис 3 23
- Дренажныетрубы 24
- Дренажныетрубы рис 1 24
- Подготовкатрубслеваислевасзади рис 2 24
- Проверкадренажа рис 4 24
- Рис 1 24
- Рис 2 24
- Рис 3 24
- Рис 4 24
- Укладкавместодлятрубоквнутреннегоблока рис 3 24
- Pka rp60 71 100kal 25
- Pka rp60 71 100kal рис 1 25
- Внутреннийблок 25
- Одновременная двойная тройная четверная система 25
- Питаниенавнутреннийприборподаетсяотнаружногоприбора 25
- Рис 1 25
- Система 1 1 25
- Электрическиеработы 25
- Имеются следующие шаблоны подключения конструкция блока питания внешнего прибора зависит от модели 26
- Одновременная двойная тройная четверная система 26
- Отдельныеисточникиэлектропитаниядлявнутреннегоприбора наружногоприбора толькодляпримененияpuhz 26
- Прикрепите бирку b прилагаемую к руководствам около каждой схемы подключения для внутреннего и наружного приборов 26
- Примечания 1 диаметрпроводовдолженсоответствоватьприменимымместныминациональнымнормам 2 силовыекабелиикабелисоединениявнутреннего наружногоприборанедолжныбытьлегчеэкранированногогибкогопроводаиз полихлоропрена модель245iec57 3 длинаустанавливаемогокабелязаземлениядолжнапревышатьдлинудругихкабелей 26
- Система 1 1 26
- Требуется дополнительный сменный комплект проводки 26
- Требуются дополнительные комплекты для замены проводов 26
- Электрическиеработы 26
- On off 1 2 sw8 27
- Дляпроводногопультадистанционногоуправления дополнительныедетали 1 процедураустановки 27
- Пультдистанционногоуправления 27
- Рис 2 27
- Рис 3 27
- Электрическиеработы 27
- Длябеспроводногопультадистанционногоуправления 1 местаустановки 28
- Дляпроводногопультадистанционногоуправления рис 8 28
- Методустановки рис 5 28
- Настройка рис 6 28
- Настройкадвухпультовдистанционногоуправления 28
- Операциисоединения рис 4 28
- Приписаниепультадистанционногоуправленияотдельным приборам рис 7 28
- Процедуранастройкиномерапарыпультадистанционного 28
- Рис 4 28
- Рис 5 28
- Рис 6 28
- Рис 7 28
- Рис 8 28
- Управления 28
- Установкифункций 28
- Электрическиеработы 28
- Длябеспроводногопультадистанционногоуправления рис 9 29
- Рис 9 29
- Таблицафункций 29
- Функциональнаянастройканапультедистанционногоуправления 29
- Электрическиеработы 29
- M i hg 30
- Выполнениеиспытания 30
- Передпробнымпрогоном 30
- Рис 1 30
- Рис 2 30
- Рис 3 30
- Рис 4 30
- Самодиагностика 30
- Выполнениеиспытания 31
- Выполнениеиспытания 32
- Примердисплея температуранагнетаниякомпрессора64 c 32
- Функцияпростоготехобслуживания опция 32
- 1 нажмите и удерживайте в течение трех 33
- 2 нажмите temp темп нажмите temp темп 33
- 3 выберите данные которые необходимо отобразить 33
- 4 нажмите кнопку 33
- 5 данные отображаются в c 33
- 6 нажмите и удерживайте в течение трех секунд кнопку 33
- Время работы фильтра отображается в виде количества часов 33
- Данные можно проверить выполнив шаги с 3 по 5 процедур по 33
- Для включения режима 33
- Для выбора режима работы 33
- Или 33
- Использования фильтра с момента выполнения сброса фильтра 33
- Нажмите кнопку 33
- Повторите шаги со 2 по 5 для проверки другой даты 33
- Процедуры работы в режиме техобслуживания 33
- Работе в режиме техобслуживания ожидая стабильной работы 33
- Секунд кнопку 33
- Стабильнаяработа используя режим техобслуживания можно зафиксировать рабочую частоту 33
- Техобслуживания 33
- Функцияпростоготехобслуживания опция 33
- Что приведет к стабилизации работы если кондиционер остановлен используйте следующую процедуру чтобы начать данную операцию 33
- Чтобы отключить режим техобслуживания 33
Похожие устройства
- Mitsubishi Electric PKA-RP100KAL / PUHZ-SHW112YHA Сертификат
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100YHA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100YHA Руководство по установке
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100YHA Сертификат
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100VKA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100VKA Руководство по установке
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100VKA Сертификат
- Mitsubishi Electric PLA-RP50BA / PUHZ-ZRP50VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP50BA / PUHZ-ZRP50VHA Руководство по установке
- Mitsubishi Electric PLA-RP50BA / PUHZ-ZRP50VHA Сертификат
- Mitsubishi Electric PLA-RP35BA / PUHZ-ZRP35VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP35BA / PUHZ-ZRP35VHA Руководство по установке
- Mitsubishi Electric PLA-RP35BA / PUHZ-ZRP35VHA Сертификат
- Mitsubishi Electric PLA-RP71BA / PUHZ-ZRP71VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP71BA / PUHZ-ZRP71VHA Руководство по установке
- Mitsubishi Electric PLA-RP71BA / PUHZ-ZRP71VHA Сертификат
- Mitsubishi Electric PLA-RP60BA / PUHZ-ZRP60VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP60BA / PUHZ-ZRP60VHA Руководство по установке
- Mitsubishi Electric PLA-RP60BA / PUHZ-ZRP60VHA Сертификат
- Graude IKG 180.0 Инструкция по эксплуатации