4. Installing the refrigerant piping
B
A
45 2
4.3. Indoor unit (Fig. 4-3)
Installing procedures
1. Slide the supplied pipe cover
2
over the gas tubing until it is pressed against the
sheet metal inside the unit.
2. Slide the provided pipe cover
3
over the liquid tubing until it is pressed against
the sheet metal inside the unit.
3. Tighten the pipe covers
2
and
3
at the both ends (20 mm) with the supplied
bands
4
.
A
Gas tubing
E
Pipe cover
3
B
Liquid tubing
F
Press the pipe cover against the sheet metal.
C
Band
4
G
Refrigerant tubing heat insulating material
D
Pipe cover
2
4.4. For twin/triple combination
Refer to the outdoor unit installation manual.
4.1. Precautions
For devices that use R410A refrigerant
• Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigera-
tion oil applied to the fl ared sections.
• Use C1220 copper phosphorus for copper and copper alloy seamless
pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thick-
nesses specifi ed in the table below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.
Warning:
When installing or relocating, or servicing the air conditioner, use only the
specifi ed refrigerant (R410A) to charge the refrigerant lines. Do not mix it
with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other haz-
ards.
The use of any refrigerant other than that specifi ed for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
RP35, 50 RP60-140
Liquid pipe
[
6.35 thickness 0.8 mm
[
9.52 thickness 0.8 mm
Gas pipe
[
12.7 thickness 0.8 mm
[
15.88 thickness 1.0 mm
• Do not use pipes thinner than those specifi ed above.
4.2. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C or
more, thickness of 12 mm or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam in-
sulation materials (specifi c gravity of 0.03, thickness of 9 mm or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten-
ing fl are nut.
• Use 2 wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections. In-
sulate carefully.
B
Flare nut tightening torque
Copper pipe O.D.
(mm)
Flare nut O.D.
(mm)
Tightening torque
(N·m)
[
6.35 17 14-18
[
6.35 22 34-42
[
9.52 22 34-42
[
12.7 26 49-61
[
12.7 29 68-82
[
15.88 29 68-82
[
15.88 36 100-120
[
19.05 36 100-120
C
Apply refrigerating machine oil over the entire fl are seat surface.
D
Use correct fl are nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP35, 50 RP60 RP71-140
Liquid side
[
6.35 Ο
[
6.35 —
—
[
9.52 Ο
[
9.52 Ο
Gas side
[
12.7 Ο
[
15.88 Ο
[
15.88 Ο
Ο : Factory fl are nut attachment to the heat exchanger.
A
Flare cutting dimensions
Copper pipe O.D.
(mm)
Flare dimensions
[
A dimensions (mm)
[
6.35 8.7 - 9.1
[
9.52 12.8 - 13.2
[
12.7 16.2 - 16.6
[
15.88 19.3 - 19.7
[
19.05 23.6 - 24.0
Copper pipe O.D.
(mm)
B (mm)
Flare tool for R410A
Clutch type
[
6.35 (1/4″) 0 - 0.5
[
9.52 (3/8″) 0 - 0.5
[
12.7 (1/2″) 0 - 0.5
[
15.88 (5/8″) 0 - 0.5
[
19.05 (3/4″) 0 - 0.5
Fig. 4-3
Fig. 4-1
Fig. 4-2
90° ± 0.5°
R0.4 - R0.8
E
Die
F
Copper pipe
Содержание
- Air conditioners кондиционеры 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Εγχειριδιο οδηγιων εγκαταστασησ 1
- Руководство по установке 1
- Before electric work 2
- Before installation environment 2
- Before installation or relocation 2
- Before starting the test run 2
- Contents 2
- Safety precautions 2
- Check the indoor unit accessories fig 3 1 3
- Fig 2 1 3
- Fig 3 1 3
- Fig 3 2 3
- Installation location 3
- Installing the indoor unit 3
- Outline dimensions indoor unit fig 2 1 3
- Outline dimensions outdoor unit 3
- Preparation for installation fig 3 2 3
- Fig 3 3 4
- Fig 3 4 4
- Fig 3 5 4
- Fig 3 6 4
- Installing the indoor unit 4
- Installing the indoor unit fig 3 5 4
- Connecting pipes fig 4 1 5
- Fig 4 1 5
- Fig 4 2 5
- Fig 4 3 5
- For twin triple combination 5
- Indoor unit fig 4 3 5
- Installing the refrigerant piping 5
- Precautions 5
- Drainage piping work 6
- Electric wiring fig 6 1 6
- Electrical work 6
- Fig 5 1 6
- Fig 5 2 6
- Fig 5 3 6
- Fig 6 1 6
- 1 system 7
- Electrical work 7
- Indoor unit power supplied from outdoor unit 7
- Separate indoor unit outdoor unit power supplies for puhz application only 7
- Simultaneous twin triple quadruple system 7
- System 7
- Electrical work 8
- On off 1 2 sw8 3 8
- Simultaneous twin triple quadruple system 8
- Electrical work 9
- Fig 6 2 fig 6 3 9
- Fig 6 4 9
- Remote controller 9
- Electrical work 10
- Fig 6 5 fig 6 6 10
- Fig 6 7 fig 6 8 10
- Fig 6 9 10
- Function setting on the unit selecting the unit functions 10
- Function settings 10
- Electrical work 11
- Fig 6 10 11
- Function setting on the remote controller 11
- Before test run 12
- Fig 7 1 12
- Fig 7 2 12
- Fig 7 3 12
- Fig 7 4 12
- Test run 12
- Using wired remote controller 12
- Fig 7 5 13
- Fig 7 6 13
- Self check 13
- Test run 13
- Test run 14
- Test run 15
- Easy maintenance function 16
- F1 f2 f3 f4 16
- Дренажные трубы 71 6 электрические работы 71 7 выполнение испытания 77 8 функция простого техобслуживания 81 17
- Меры предосторожности 17
- Меры предосторожности 67 2 место установки 68 3 установка внутреннего прибора 68 4 прокладка труб хладагента 70 17
- Перед тестовым прогоном 17
- Перед установкой или перемещением 17
- Перед установкой окружающая среда 17
- Перед электрическими работами 17
- Содержание 17
- Fig 2 1 18
- Fig 3 1 18
- Fig 3 2 18
- Контурные габариты наружный прибор 18
- Место установки 18
- Подготовка к установке fig 3 2 18
- Проверьте наличие дополнительных принадлежностей к внутреннему прибору fig 3 1 18
- Установка внутреннего прибора 18
- Fig 3 3 19
- Fig 3 4 19
- Fig 3 5 19
- Fig 3 6 19
- Установка внутреннего прибора 19
- Установка внутреннего прибора fig 3 5 19
- Fig 4 1 20
- Fig 4 2 20
- Fig 4 3 20
- Внутренний прибор fig 4 3 20
- Для комбинации из двух трех элементов 20
- Меры предосторожности 20
- Прокладка труб хладагента 20
- Соединение труб fig 4 1 20
- Fig 5 1 21
- Fig 5 2 21
- Fig 5 3 21
- Fig 6 1 21
- Дренажные трубы 21
- Электрические работы 21
- Электропроводка fig 6 1 21
- 1 system 22
- System 22
- Одновременная двойная тройная четверная система 22
- Отдельные источники электропитания для внутреннего прибора наружного прибора только для применения puhz 22
- Питание на внутренний прибор подается от наружного прибора 22
- Система 1 1 22
- Электрические работы 22
- G g g g 23
- On off 1 2 sw8 3 23
- Если у внутреннего и наружного приборов различные источники электропитания см таблицу ниже при использовании комплекта клемм источника электропитания внутреннего прибора замените проводку распределительной коробки внутреннего прибора в соответствии с рисунком справа и измените настройки микропереключателя панели управления наружного прибора 23
- Изменение соединения разъема распределительной коробки внутреннего прибора 23
- Одновременная двойная тройная четверная система 23
- Электрические работы 23
- Fig 6 2 fig 6 3 24
- Fig 6 4 24
- Пульт дистанционного управления 24
- Электрические работы 24
- Fig 6 5 fig 6 6 25
- Fig 6 7 fig 6 8 25
- Fig 6 9 25
- Установки функций 25
- Функциональная настройка прибора выбор функций прибора 25
- Электрические работы 25
- Fig 6 10 26
- Функциональная настройка на пульте дистанционного управления 26
- Электрические работы 26
- Fig 7 1 27
- Fig 7 2 27
- Fig 7 3 27
- Fig 7 4 27
- Выполнение испытания 27
- Перед пробным прогоном 27
- Fig 7 5 28
- Fig 7 6 28
- Выполнение испытания 28
- Самодиагностика 28
- Выполнение испытания 29
- Выполнение испытания 30
- F1 f2 f3 f4 31
- Функция простого техобслуживания 31
Похожие устройства
- Mitsubishi Electric PCA-RP71KAQ / PUHZ-ZRP71VHA Руководство по установке
- Mitsubishi Electric PCA-RP71KAQ / PUHZ-ZRP71VHA Инструкция по установке
- Mitsubishi Electric PCA-RP71KAQ / SUZ-KA71VA Руководство по установке
- Mitsubishi Electric PCA-RP71KAQ / SUZ-KA71VA Инструкция по установке
- Mitsubishi Electric PCA-RP140KAQ / PUHZ-P140YHA Руководство по установке
- Mitsubishi Electric PCA-RP140KAQ / PUHZ-P140YHA Инструкция по установке
- Mitsubishi Electric PCA-RP100KAQ / PUHZ-P100YHA Руководство по установке
- Mitsubishi Electric PCA-RP100KAQ / PUHZ-P100YHA Инструкция по установке
- Mitsubishi Electric PCA-RP140KAQ / PUHZ-P140VHA Руководство по установке
- Mitsubishi Electric PCA-RP140KAQ / PUHZ-P140VHA Инструкция по установке
- Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125YHA Руководство по установке
- Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125YHA Инструкция по установке
- Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125VHA Руководство по установке
- Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125VHA Инструкция по установке
- Mitsubishi Electric PCA-RP60KAQ / SUZ-KA60VA Руководство по установке
- Mitsubishi Electric PCA-RP60KAQ / SUZ-KA60VA Инструкция по установке
- Liebherr GNP 3056 Инструкция по эксплуатации
- Fagor CO-110 DD Инструкция по эксплуатации
- Mitsubishi Electric PCA-RP71HAQ / PUHZ-ZRP71VHA Руководство по установке
- Mitsubishi Electric PCA-RP71HAQ / PUHZ-ZRP71VHA Инструкция по установке