Mitsubishi Electric PCA-RP71KAQ / PUHZ-ZRP71VHA [15/32] Test run
![Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125YHA [15/32] Test run](/views2/1331075/page15/bgf.png)
15
7. Test run
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wireless remote controller
Wired remote
controller
Symptom Remark
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
Check code
1 E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
For details, check the LED
display of the outdoor controller
board.
2 UP Compressor overcurrent interruption
3 U3, U4 Open/short of outdoor unit thermistors
4 UF Compressor overcurrent interruption (When compressor locked)
5 U2 Abnormal high discharging temperature/49C worked/insuffi cient refrigerant
6 U1, Ud Abnormal high pressure (63H worked)/Overheating protection operation
7 U5 Abnormal temperature of heat sink
8 U8 Outdoor unit fan protection stop
9 U6 Compressor overcurrent interruption/Abnormal of power module
10 U7 Abnormality of super heat due to low discharge temperature
11 U9, UH
Abnormality such as overvoltage or voltage shortage and abnormal
synchronous signal to main circuit/Current sensor error
12 — —
13 — —
14 Others Other errors (Refer to the technical manual for the outdoor unit.)
*1. If the beeper does not sound again after the initial 2 beeps to confi rm the self-check start signal was received and the OPERATION INDICATOR lamp does
not come on, there are no error records.
*2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confi rm the self-check start signal was re-
ceived, the specifi ed refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.
• If the unit cannot be operated properly after test run, refer to the following table to fi nd the cause.
Symptom
Cause
Wired remote controller LED 1, 2 (PCB in outdoor unit
PLEASE WAIT
For about 2 minutes
after power-on
After LED 1, 2 are lighted, LED 2 is turned
off, then only LED 1 is lighted. (Correct
operation)
•For about 2 minutes after power-on, operation of the remote
controller is not possible due to system start-up. (Correct
operation)
PLEASE WAIT →Error code
Subsequent to about
2 minutes after
power-on
Only LED 1 is lighted.
→
LED 1, 2 blink.
•Connector for the outdoor unit’s protection device is not con-
nected.
Reverse or open phase wiring for the outdoor unit’s power
terminal block (L1, L2, L3)
Display messages do not appear
even when operation switch is
turned ON
(operation lamp does not light up).
Only LED 1 is lighted.
→
LED 1 blinks
twice, LED 2 blinks once.
•Incorrect wiring between indoor and outdoor units (incorrect
polarity of S1, S2, S3)
•Remote controller wire short
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller are accepted.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED 1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED is always lit.
LED 2 (power for remote controller) Indicates whether power is supplied to the remote controller. This LED lights only in the case of
the indoor unit which is connected to the outdoor unit refrigerant address “0”.
LED 3 (communication between indoor and outdoor units) Indicates state of communication between the indoor and outdoor units. Make sure that this LED
is always blinking.
Содержание
- Air conditioners кондиционеры 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Εγχειριδιο οδηγιων εγκαταστασησ 1
- Руководство по установке 1
- Before electric work 2
- Before installation environment 2
- Before installation or relocation 2
- Before starting the test run 2
- Contents 2
- Safety precautions 2
- Check the indoor unit accessories fig 3 1 3
- Fig 2 1 3
- Fig 3 1 3
- Fig 3 2 3
- Installation location 3
- Installing the indoor unit 3
- Outline dimensions indoor unit fig 2 1 3
- Outline dimensions outdoor unit 3
- Preparation for installation fig 3 2 3
- Fig 3 3 4
- Fig 3 4 4
- Fig 3 5 4
- Fig 3 6 4
- Installing the indoor unit 4
- Installing the indoor unit fig 3 5 4
- Connecting pipes fig 4 1 5
- Fig 4 1 5
- Fig 4 2 5
- Fig 4 3 5
- For twin triple combination 5
- Indoor unit fig 4 3 5
- Installing the refrigerant piping 5
- Precautions 5
- Drainage piping work 6
- Electric wiring fig 6 1 6
- Electrical work 6
- Fig 5 1 6
- Fig 5 2 6
- Fig 5 3 6
- Fig 6 1 6
- 1 system 7
- Electrical work 7
- Indoor unit power supplied from outdoor unit 7
- Separate indoor unit outdoor unit power supplies for puhz application only 7
- Simultaneous twin triple quadruple system 7
- System 7
- Electrical work 8
- On off 1 2 sw8 3 8
- Simultaneous twin triple quadruple system 8
- Electrical work 9
- Fig 6 2 fig 6 3 9
- Fig 6 4 9
- Remote controller 9
- Electrical work 10
- Fig 6 5 fig 6 6 10
- Fig 6 7 fig 6 8 10
- Fig 6 9 10
- Function setting on the unit selecting the unit functions 10
- Function settings 10
- Electrical work 11
- Fig 6 10 11
- Function setting on the remote controller 11
- Before test run 12
- Fig 7 1 12
- Fig 7 2 12
- Fig 7 3 12
- Fig 7 4 12
- Test run 12
- Using wired remote controller 12
- Fig 7 5 13
- Fig 7 6 13
- Self check 13
- Test run 13
- Test run 14
- Test run 15
- Easy maintenance function 16
- F1 f2 f3 f4 16
- Дренажные трубы 71 6 электрические работы 71 7 выполнение испытания 77 8 функция простого техобслуживания 81 17
- Меры предосторожности 17
- Меры предосторожности 67 2 место установки 68 3 установка внутреннего прибора 68 4 прокладка труб хладагента 70 17
- Перед тестовым прогоном 17
- Перед установкой или перемещением 17
- Перед установкой окружающая среда 17
- Перед электрическими работами 17
- Содержание 17
- Fig 2 1 18
- Fig 3 1 18
- Fig 3 2 18
- Контурные габариты наружный прибор 18
- Место установки 18
- Подготовка к установке fig 3 2 18
- Проверьте наличие дополнительных принадлежностей к внутреннему прибору fig 3 1 18
- Установка внутреннего прибора 18
- Fig 3 3 19
- Fig 3 4 19
- Fig 3 5 19
- Fig 3 6 19
- Установка внутреннего прибора 19
- Установка внутреннего прибора fig 3 5 19
- Fig 4 1 20
- Fig 4 2 20
- Fig 4 3 20
- Внутренний прибор fig 4 3 20
- Для комбинации из двух трех элементов 20
- Меры предосторожности 20
- Прокладка труб хладагента 20
- Соединение труб fig 4 1 20
- Fig 5 1 21
- Fig 5 2 21
- Fig 5 3 21
- Fig 6 1 21
- Дренажные трубы 21
- Электрические работы 21
- Электропроводка fig 6 1 21
- 1 system 22
- System 22
- Одновременная двойная тройная четверная система 22
- Отдельные источники электропитания для внутреннего прибора наружного прибора только для применения puhz 22
- Питание на внутренний прибор подается от наружного прибора 22
- Система 1 1 22
- Электрические работы 22
- G g g g 23
- On off 1 2 sw8 3 23
- Если у внутреннего и наружного приборов различные источники электропитания см таблицу ниже при использовании комплекта клемм источника электропитания внутреннего прибора замените проводку распределительной коробки внутреннего прибора в соответствии с рисунком справа и измените настройки микропереключателя панели управления наружного прибора 23
- Изменение соединения разъема распределительной коробки внутреннего прибора 23
- Одновременная двойная тройная четверная система 23
- Электрические работы 23
- Fig 6 2 fig 6 3 24
- Fig 6 4 24
- Пульт дистанционного управления 24
- Электрические работы 24
- Fig 6 5 fig 6 6 25
- Fig 6 7 fig 6 8 25
- Fig 6 9 25
- Установки функций 25
- Функциональная настройка прибора выбор функций прибора 25
- Электрические работы 25
- Fig 6 10 26
- Функциональная настройка на пульте дистанционного управления 26
- Электрические работы 26
- Fig 7 1 27
- Fig 7 2 27
- Fig 7 3 27
- Fig 7 4 27
- Выполнение испытания 27
- Перед пробным прогоном 27
- Fig 7 5 28
- Fig 7 6 28
- Выполнение испытания 28
- Самодиагностика 28
- Выполнение испытания 29
- Выполнение испытания 30
- F1 f2 f3 f4 31
- Функция простого техобслуживания 31
Похожие устройства
- Mitsubishi Electric PCA-RP71KAQ / SUZ-KA71VA Руководство по установке
- Mitsubishi Electric PCA-RP71KAQ / SUZ-KA71VA Инструкция по установке
- Mitsubishi Electric PCA-RP140KAQ / PUHZ-P140YHA Руководство по установке
- Mitsubishi Electric PCA-RP140KAQ / PUHZ-P140YHA Инструкция по установке
- Mitsubishi Electric PCA-RP100KAQ / PUHZ-P100YHA Руководство по установке
- Mitsubishi Electric PCA-RP100KAQ / PUHZ-P100YHA Инструкция по установке
- Mitsubishi Electric PCA-RP140KAQ / PUHZ-P140VHA Руководство по установке
- Mitsubishi Electric PCA-RP140KAQ / PUHZ-P140VHA Инструкция по установке
- Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125YHA Руководство по установке
- Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125YHA Инструкция по установке
- Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125VHA Руководство по установке
- Mitsubishi Electric PCA-RP125KAQ / PUHZ-P125VHA Инструкция по установке
- Mitsubishi Electric PCA-RP60KAQ / SUZ-KA60VA Руководство по установке
- Mitsubishi Electric PCA-RP60KAQ / SUZ-KA60VA Инструкция по установке
- Liebherr GNP 3056 Инструкция по эксплуатации
- Fagor CO-110 DD Инструкция по эксплуатации
- Mitsubishi Electric PCA-RP71HAQ / PUHZ-ZRP71VHA Руководство по установке
- Mitsubishi Electric PCA-RP71HAQ / PUHZ-ZRP71VHA Инструкция по установке
- Mitsubishi Electric PCA-RP140KAQ / PU-P140YHAR Руководство по установке
- Mitsubishi Electric PCA-RP140KAQ / PU-P140YHAR Инструкция по установке