6.2. Function settings
6.2.1. Function setting on the unit (Fig. 6-2)
Changing the power voltage setting
Be sure to change the power voltage setting depending on the voltage used.
1 Go to the function setting mode.
Switch OFF the remote controller.
Press the
A and B buttons simultaneously and hold them for at least 2
seconds. FUNCTION will start to flash.
2 Use the C button to set the refrigerant address (
) to 00.
3 Press D and [--] will start to flash in the unit number (
) display.
4 Use the C button to set the unit number (
) to 00.
5 Press the E MODE button to designate the refrigerant address/unit number. [--]
will flash in the mode number (
) display momentarily.
6 Press the F buttons to set the mode number (
) to 04.
7 Press the G button and the current set setting number (
) will flash.
Use the F button to switch the setting number in response to the power supply
voltage to be used.
Power supply voltage
240 V : setting number = 1
220 V, 230 V : setting number = 2
8 Press the MODE button E and mode and the setting number (
) and ( ) will change
to being on constantly and the contents of the setting can be confirmed.
9 Press the FILTER A and TEST RUN B buttons simultaneously for at least two
seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.
6.2.2. Function setting on the remote controller
Refer to the indoor unit operation manual.
Fig. 6-2
6. Electrical work
Function table
Select unit number 00
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode number
Setting number
Refrigerant address
Unit number
Mode Settings Mode no. Setting no. Initial setting Setting
Power failure automatic recovery
Not available
01
1
*2
Available *1
2
*2
Indoor temperature detecting
Indoor unit operating average
02
1
Set by indoor unit’s remote controller 2
Remote controller’s internal sensor
3–
LOSSNAY connectivity
Not Supported
03
1
Supported (indoor unit is not equipped with outdoor-air intake)
2
Supported (indoor unit is equipped with outdoor-air intake)
3
Power voltage
240 V
04
1
220 V, 230 V
2
Mode Settings Mode no. Setting no. Initial setting Setting
Filter sign
100 H
07
1
2500 Hr
2
No filter sign indicator
3
Fan speed Silent
08
1
Standard 2
3
*1 When the power supply returns, the air conditioner will start 4 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.