Mitsubishi Electric PSA-RP140KA / PUHZ-P140VHA [10/24] Test run
![Mitsubishi Electric PSA-RP125KA / PUHZ-P125VHA [10/24] Test run](/views2/1331322/page10/bga.png)
10
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
Fig. 7-2
7.2. Test run
The following 2 methods are available.
7.2.1. Using wired remote controller (Fig. 7-1)
1 Turn on the power at least 12 hours before the test run.
2 Press the [TEST] button twice. “TEST RUN” liquid crystal display
3 Press the [Mode selection] button. Make sure that wind is blown out.
4 Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
5 Press the [Fan speed] button. Make sure that the wind speed is switched.
6 Check operation of the outdoor unit fan.
7 Release test run by pressing the [ON/OFF] button. Stop
8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the operation
manual for the indoor unit.
7.2.2. Using SW4 in outdoor unit
Refer to the outdoor unit installation manual.
7.3. Self-check (Fig. 7-2)
1 Turn on the power.
2 Press the [CHECK] button twice.
3 Set refrigerant address with [TEMP] button if system control is used.
4 Press the [ON/OFF] button to stop the self-check.
A CHECK button
B Refrigerant address
C TEMP. button
D IC: Indoor unit
OC: Outdoor unit
E Check code
F Unit address
°C
°C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN
COOL, HEAT
A ON/OFF button
B Test run display
C Indoor temperature liquid line
temperature display
D ON/OFF lamp
E Power display
F Error code display
Test run remaining time
display
G Set temperature button
H Mode selection button
I Fan speed button
M TEST button
Fig. 7-1
7. Test run
7.1. Before test run
► After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong polarity, and no disconnection of one phase in the
supply.
► Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M
Ω.
► Do not carry out this test on the control wiring (low voltage circuit) termi
-
nals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0 MΩ.
Insulation resistance
Check code Symptom Remark
P1 Intake sensor error
P2 Pipe (TH2) sensor error
P9 Pipe (TH5) sensor error
E6, E7 Indoor/outdoor unit communication error
P4 Drain sensor error
P5 Drain pump error
P6 Freezing/Overheating safeguard operation
EE Communication error between indoor and outdoor units
P8 Pipe temperature error
E4 Remote controller signal receiving error
––
––
PL Refrigerant circuit abnormal
Fb Indoor unit control system error (memory error, etc.)
– –
No corresponding
[Output pattern A] Errors detected by indoor unit
Содержание
- Air conditioners 1
- Deutsch 1
- English 1
- Español 1
- Eγxeipiδio oδhγiωn eγkataσtaσhσ 1
- Eλληνικά 1
- Français 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands 1
- Português 1
- Psa rp ka 1
- Svenska 1
- Türkçe 1
- Before electric work 2
- Before installation euvironment 2
- Before installation or relocation 2
- Before starting the test run 2
- Contents 2
- Safety precautions 2
- Check the indoor unit accessories 3
- Fig 2 1 3
- Fig 3 1 3
- Fig 3 2 3
- Installation location 3
- Installing the indoor unit 3
- Outline dimensions indoor unit fig 2 1 3
- Tip over prevention bracket fig 3 2 3
- Fig 3 3 4
- Fig 3 4 4
- Floor mounting 4
- For devices that use r410a refrigerant 4
- Installing the indoor unit 4
- Installing the refrigerant piping 4
- Mounting the tip over prevention bracket fig 3 3 4
- Precautions 4
- Fig 4 1 5
- Fig 4 2 5
- Fig 4 3 5
- Indoor unit fig 4 1 5
- Installing the refrigerant piping 5
- Refrigerant and drainage pipe locations fig 4 3 5
- Drainage check fig 5 2 6
- Drainage piping work 6
- Drainage piping work fig 5 1 6
- Fig 4 4 6
- Fig 4 5 6
- Fig 5 1 6
- Fig 5 2 6
- Installing the refrigerant piping 6
- 1 system 7
- Electric wiring fig 6 1 7
- Electrical work 7
- Fig 6 1 7
- Indoor unit power supplied from outdoor unit 7
- Simultaneous twin triple four system 7
- 1 system 8
- Affix a label b that is included with the manuals near each wiring diagram for the indoor and outdoor units 8
- Electrical work 8
- If the indoor and outdoor units have separate power supplies refer to the table at the below if the optional wiring replacement kit is used change the indoor unit electrical box wiring refering to the figure in the right and the dip switch settings of the outdoor unit control board 8
- Indoor unit specifications indoor power supply terminal kit option required indoor unit electrical box connector con nection change required 8
- Label affixed near each wiring diagram for the indoor and outdoor units required 8
- Notes 1 wiring size must comply with the applicable local and national code 2 power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord design 60245 iec 57 3 install an earth longer than other cables 8
- On off 1 2 sw8 3 8
- Outdoor unit dip switch settings when using separate indoor unit outdoor unit power supplies only 8
- Separate indoor unit outdoor unit power supplies for puhz application only 8
- Simultaneous twin triple four system 8
- The following connection patterns are available the outdoor unit power supply patterns vary on models 8
- The optional wiring replacement kit is required 8
- The optional wiring replacement kits are required 8
- There are three types of labels labels a b and c affix the appropriate labels to the units according to the wiring method 8
- Electrical work 9
- Fig 6 2 9
- Function setting on the remote controller 9
- Function setting on the unit fig 6 2 9
- Function settings 9
- Before test run 10
- Fig 7 1 10
- Fig 7 2 10
- Self check fig 7 2 10
- Test run 10
- Test run 11
- 1 press the button for three seconds to activate the maintenance mode 12
- 2 press the temp buttons to set the refrigerant address 12
- 3 select the data you want to display 12
- 4 press the button 12
- 5 the data is displayed in 12
- 6 press the button for three seconds or press the button to deactivate the maintenance mode 12
- By using the maintenance mode you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units this function can be used whether the air conditioner is operating or not during air conditioner operation data can be checked during either normal operation or maintenance mode stable operation this function cannot be used during the test run the availability of this function depends on the connecting outdoor unit refer to the brochures 12
- Display example comp discharge temperature 64 c 12
- Easy maintenance function 12
- Maintenance mode operation procedures 12
- Press the button 12
- Press the button to select the operation mode 12
- Repeat steps 2 to 5 to check another date 12
- Stable operation using the maintenance mode the operation frequency can be fixed and the operation can be stabilized if the air conditioner is stopped use the following procedure to start this operation 12
- The filter operation time displayed is the number of hours the filter has been used since the filter reset was performed 12
- You can check the data using steps 3 to 5 of the maintenance mode operation procedures while waiting for the stable operation 12
- Дренажные трубы 27 6 электрические работы 28 7 выполнение испытания 31 8 функция простого техобслуживания 33 13
- Меры предосторожности 13
- Меры предосторожности 23 2 место установки 24 3 установка внутреннего прибора 24 4 прокладка труб хладагента 25 13
- Перед тестовым прогоном 13
- Перед установкой или перемещением 13
- Перед установкой окружающая среда 13
- Перед электрическими работами 13
- Содержание 13
- Fig 2 1 14
- Fig 3 1 3 крепежный кронштейн для предотвращения опрокидывания прибора fig 3 2 14
- Fig 3 2 14
- Контурные габариты внутренний прибор fig 2 1 14
- Место установки 14
- Проверьте наличие дополнительных принадлежностей к внутреннему прибору 14
- Установка внутреннего прибора 14
- Fig 3 3 15
- Fig 3 4 15
- Для устройств в которых используется хладагент r410a 15
- Меры предосторожности 15
- Монтаж крепежного кронштейна для предотвращения опрокидывания прибора fig 3 3 15
- Монтаж на полу 15
- Прокладка труб хладагента 15
- Установка внутреннего прибора 15
- Fig 4 1 16
- Fig 4 2 16
- Fig 4 3 16
- Внутренний прибор fig 4 1 16
- Прокладка труб хладагента 16
- Расположение труб хладагента и дренажных труб fig 4 3 16
- Fig 4 4 17
- Fig 4 5 17
- Fig 5 1 17
- Fig 5 2 17
- Дренажные трубы 17
- Проверка дренажа fig 5 2 17
- Прокладка дренажных труб fig 5 1 17
- Прокладка труб хладагента 17
- Fig 6 1 18
- Одновременная двойная тройная четверная система 18
- Питание на внутренний прибор подается от наружного прибора 18
- Система 1 1 18
- Электрические работы 18
- Электрические работы fig 6 1 18
- On off 1 2 sw8 3 19
- Одновременная двойная тройная четверная система 19
- Отдельные источники электропитания для внутреннего прибора наружного прибора только для применения puhz 19
- Система 1 1 19
- Электрические работы 19
- Fig 6 2 20
- Установки функций 20
- Функциональная настройка на пульте дистанционного управления 20
- Функциональная настройка прибора fig 6 2 20
- Электрические работы 20
- Fig 7 1 21
- Fig 7 2 21
- Выполнение испытания 21
- Перед пробным прогоном 21
- Самодиагностика fig 7 2 21
- Выполнение испытания 22
- Процедуры работы в режиме техобслуживания 23
- Функция простого техобслуживания 23
Похожие устройства
- Mitsubishi Electric PSA-RP125KA / PUHZ-P125VHA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP125KA / PUHZ-P125VHA Инструкция по установке
- Mitsubishi Electric PSA-RP100KA / PUHZ-P100VHA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP100KA / PUHZ-P100VHA Инструкция по установке
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125VKA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125VKA Инструкция по установке
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140VKA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140VKA Руководство по установке
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140VKA Сертификат
- Mitsubishi Electric PSA-RP71KA / PUHZ-ZRP71VHA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP71KA / PUHZ-ZRP71VHA Инструкция по установке
- EQTA BC03 Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP140KA / PUHZ-P140YHA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP140KA / PUHZ-P140YHA Инструкция по установке
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Руководство по установке
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Сертификат
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125YKA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125YKA Инструкция по установке
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140YKA Инструкция по эксплуатации