Mitsubishi Electric PSA-RP140KA / PUHZ-P140VHA [2/24] Safety precautions
![Mitsubishi Electric PSA-RP100KA / PUHZ-ZRP100VKA [2/24] Safety precautions](/views2/1331322/page2/bg2.png)
2
Contents
1. Safety precautions .....................................................................................2
2. Installation location ....................................................................................3
3. Installing the indoor unit ............................................................................3
4. Installing the refrigerant piping ..................................................................4
5. Drainage piping work .................................................................................6
6. Electrical work ...........................................................................................7
7. Test run ....................................................................................................10
8. Easy maintenance function .....................................................................12
1.2. Before installation or relocation
Caution:
• Be extremely careful when transporting the units. Two or more persons
are needed to handle the unit, as it weighs 20 kg or more. Do not grasp the
packaging bands. Wear protective gloves as you can injure your hands on
the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials,
such as nails and other metal or wooden parts may cause stabs or other
injuries.
Warning:
• Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and use
tools and pipe components specifically made for use with refrigerant specified
in the outdoor unit installation manual.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor
-
rectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its
weight.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Should the refrigerant leak and cause
the concentration limit to be exceeded, hazards due to lack of oxygen in the
room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual.
• Use only specified cables for wiring. The wiring connections must be made
securely with no tension applied on the terminal connections. Also, never
splice the cables for wiring (unless otherwise indicated in this document).
Failure to observe these instructions may result in overheating or a fire.
• The terminal block cover panel of the unit must be firmly attached.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or
an authorized technician to install them.
• The user should never attempt to repair the unit or transfer it to another loca
-
tion.
• After installation has been completed, check for refrigerant leaks. If refriger-
ant leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.
• When installing or relocating, or servicing the air conditioner, use only the
specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with
any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other
hazards.
The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
1.1. Before installation (Euvironment)
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is installed
in areas exposed to steam, volatile oil (including machine oil), or sulfuric gas,
areas exposed to high salt content such as the seaside, the performance can
be significantly reduced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, flow,
or accumulate. If combustible gas accumulates around the unit, fire or explo-
sion may result.
• Do not keep food, plants, caged pets, artwork, or precision instruments in the
direct airflow of the indoor unit or too close to the unit, as these items can be
damaged by temperature changes or dripping water.
• When the room humidity exceeds 80% or when the drainpipe is clogged,
water may drip from the indoor unit. Do not install the indoor unit where such
dripping can cause damage.
• When installing the unit in a hospital or communications office, be prepared for
noise and electronic interference. Inverters, home appliances, high-frequency
medical equipment, and radio communications equipment can cause the air
conditioner to malfunction or breakdown. The air conditioner may also affect
medical equipment, disturbing medical care, and communications equipment,
harming the screen display quality.
• Thermal insulation of the refrigerant pipe is necessary to prevent condensation.
If the refrigerant pipe is not properly insulated, condensation will be formed.
• Place thermal insulation on the pipes to prevent condensation. If the drain
-
pipe is installed incorrectly, water leakage and damage to the ceiling, floor,
furniture, or other possessions may result.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened too
much, the flare nut can break after an extended period.
1.3. Before electric work
Caution:
• Be sure to install circuit breakers. If not installed, electric shock may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a
short circuit, overheating, or fire may result.
• When installing the power lines, do not apply tension to the cables.
• Be sure to ground the unit. If the unit is not properly grounded, electric shock
may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and
molded case circuit breaker) with the specified capacity. If the circuit breaker
capacity is larger than the specified capacity, breakdown or fire may result.
1. Safety precautions
1.4. Before starting the test run
Caution:
• Turn on the main power switch more than 12 hours before starting operation.
Starting operation just after turning on the power switch can severely damage
the internal parts.
• Before starting operation, check that all panels, guards and other protective
parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.
• Do not operate the air conditioner without the air filter set in place. If the air
filter is not installed, dust may accumulate and breakdown may result.
• Do not touch any switch with wet hands. Electric shock may result.
• Do not touch the refrigerant pipes with bare hands during operation.
• After stopping operation, be sure to wait at least five minutes before turning off
the main power switch. Otherwise, water leakage or breakdown may result.
► Before installing the unit, make sure you read all the “Safety precau-
tions”.
► Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the “Safety Precautions,” use, and
maintenance of the unit to the customer according to the information in the Operation
Manual and perform the test run to ensure normal operation. Both the Installation
Manual and Operation Manual must be given to the user for keeping. These manuals
must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
Содержание
- Air conditioners 1
- Deutsch 1
- English 1
- Español 1
- Eγxeipiδio oδhγiωn eγkataσtaσhσ 1
- Eλληνικά 1
- Français 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands 1
- Português 1
- Psa rp ka 1
- Svenska 1
- Türkçe 1
- Before electric work 2
- Before installation euvironment 2
- Before installation or relocation 2
- Before starting the test run 2
- Contents 2
- Safety precautions 2
- Check the indoor unit accessories 3
- Fig 2 1 3
- Fig 3 1 3
- Fig 3 2 3
- Installation location 3
- Installing the indoor unit 3
- Outline dimensions indoor unit fig 2 1 3
- Tip over prevention bracket fig 3 2 3
- Fig 3 3 4
- Fig 3 4 4
- Floor mounting 4
- For devices that use r410a refrigerant 4
- Installing the indoor unit 4
- Installing the refrigerant piping 4
- Mounting the tip over prevention bracket fig 3 3 4
- Precautions 4
- Fig 4 1 5
- Fig 4 2 5
- Fig 4 3 5
- Indoor unit fig 4 1 5
- Installing the refrigerant piping 5
- Refrigerant and drainage pipe locations fig 4 3 5
- Drainage check fig 5 2 6
- Drainage piping work 6
- Drainage piping work fig 5 1 6
- Fig 4 4 6
- Fig 4 5 6
- Fig 5 1 6
- Fig 5 2 6
- Installing the refrigerant piping 6
- 1 system 7
- Electric wiring fig 6 1 7
- Electrical work 7
- Fig 6 1 7
- Indoor unit power supplied from outdoor unit 7
- Simultaneous twin triple four system 7
- 1 system 8
- Affix a label b that is included with the manuals near each wiring diagram for the indoor and outdoor units 8
- Electrical work 8
- If the indoor and outdoor units have separate power supplies refer to the table at the below if the optional wiring replacement kit is used change the indoor unit electrical box wiring refering to the figure in the right and the dip switch settings of the outdoor unit control board 8
- Indoor unit specifications indoor power supply terminal kit option required indoor unit electrical box connector con nection change required 8
- Label affixed near each wiring diagram for the indoor and outdoor units required 8
- Notes 1 wiring size must comply with the applicable local and national code 2 power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord design 60245 iec 57 3 install an earth longer than other cables 8
- On off 1 2 sw8 3 8
- Outdoor unit dip switch settings when using separate indoor unit outdoor unit power supplies only 8
- Separate indoor unit outdoor unit power supplies for puhz application only 8
- Simultaneous twin triple four system 8
- The following connection patterns are available the outdoor unit power supply patterns vary on models 8
- The optional wiring replacement kit is required 8
- The optional wiring replacement kits are required 8
- There are three types of labels labels a b and c affix the appropriate labels to the units according to the wiring method 8
- Electrical work 9
- Fig 6 2 9
- Function setting on the remote controller 9
- Function setting on the unit fig 6 2 9
- Function settings 9
- Before test run 10
- Fig 7 1 10
- Fig 7 2 10
- Self check fig 7 2 10
- Test run 10
- Test run 11
- 1 press the button for three seconds to activate the maintenance mode 12
- 2 press the temp buttons to set the refrigerant address 12
- 3 select the data you want to display 12
- 4 press the button 12
- 5 the data is displayed in 12
- 6 press the button for three seconds or press the button to deactivate the maintenance mode 12
- By using the maintenance mode you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units this function can be used whether the air conditioner is operating or not during air conditioner operation data can be checked during either normal operation or maintenance mode stable operation this function cannot be used during the test run the availability of this function depends on the connecting outdoor unit refer to the brochures 12
- Display example comp discharge temperature 64 c 12
- Easy maintenance function 12
- Maintenance mode operation procedures 12
- Press the button 12
- Press the button to select the operation mode 12
- Repeat steps 2 to 5 to check another date 12
- Stable operation using the maintenance mode the operation frequency can be fixed and the operation can be stabilized if the air conditioner is stopped use the following procedure to start this operation 12
- The filter operation time displayed is the number of hours the filter has been used since the filter reset was performed 12
- You can check the data using steps 3 to 5 of the maintenance mode operation procedures while waiting for the stable operation 12
- Дренажные трубы 27 6 электрические работы 28 7 выполнение испытания 31 8 функция простого техобслуживания 33 13
- Меры предосторожности 13
- Меры предосторожности 23 2 место установки 24 3 установка внутреннего прибора 24 4 прокладка труб хладагента 25 13
- Перед тестовым прогоном 13
- Перед установкой или перемещением 13
- Перед установкой окружающая среда 13
- Перед электрическими работами 13
- Содержание 13
- Fig 2 1 14
- Fig 3 1 3 крепежный кронштейн для предотвращения опрокидывания прибора fig 3 2 14
- Fig 3 2 14
- Контурные габариты внутренний прибор fig 2 1 14
- Место установки 14
- Проверьте наличие дополнительных принадлежностей к внутреннему прибору 14
- Установка внутреннего прибора 14
- Fig 3 3 15
- Fig 3 4 15
- Для устройств в которых используется хладагент r410a 15
- Меры предосторожности 15
- Монтаж крепежного кронштейна для предотвращения опрокидывания прибора fig 3 3 15
- Монтаж на полу 15
- Прокладка труб хладагента 15
- Установка внутреннего прибора 15
- Fig 4 1 16
- Fig 4 2 16
- Fig 4 3 16
- Внутренний прибор fig 4 1 16
- Прокладка труб хладагента 16
- Расположение труб хладагента и дренажных труб fig 4 3 16
- Fig 4 4 17
- Fig 4 5 17
- Fig 5 1 17
- Fig 5 2 17
- Дренажные трубы 17
- Проверка дренажа fig 5 2 17
- Прокладка дренажных труб fig 5 1 17
- Прокладка труб хладагента 17
- Fig 6 1 18
- Одновременная двойная тройная четверная система 18
- Питание на внутренний прибор подается от наружного прибора 18
- Система 1 1 18
- Электрические работы 18
- Электрические работы fig 6 1 18
- On off 1 2 sw8 3 19
- Одновременная двойная тройная четверная система 19
- Отдельные источники электропитания для внутреннего прибора наружного прибора только для применения puhz 19
- Система 1 1 19
- Электрические работы 19
- Fig 6 2 20
- Установки функций 20
- Функциональная настройка на пульте дистанционного управления 20
- Функциональная настройка прибора fig 6 2 20
- Электрические работы 20
- Fig 7 1 21
- Fig 7 2 21
- Выполнение испытания 21
- Перед пробным прогоном 21
- Самодиагностика fig 7 2 21
- Выполнение испытания 22
- Процедуры работы в режиме техобслуживания 23
- Функция простого техобслуживания 23
Похожие устройства
- Mitsubishi Electric PSA-RP125KA / PUHZ-P125VHA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP125KA / PUHZ-P125VHA Инструкция по установке
- Mitsubishi Electric PSA-RP100KA / PUHZ-P100VHA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP100KA / PUHZ-P100VHA Инструкция по установке
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125VKA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125VKA Инструкция по установке
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140VKA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140VKA Руководство по установке
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140VKA Сертификат
- Mitsubishi Electric PSA-RP71KA / PUHZ-ZRP71VHA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP71KA / PUHZ-ZRP71VHA Инструкция по установке
- EQTA BC03 Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP140KA / PUHZ-P140YHA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP140KA / PUHZ-P140YHA Инструкция по установке
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Инструкция по эксплуатации
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Руководство по установке
- Mitsubishi Electric PLA-RP71BA / PUHZ-SHW80VHA Сертификат
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125YKA Инструкция по эксплуатации
- Mitsubishi Electric PSA-RP125KA / PUHZ-ZRP125YKA Инструкция по установке
- Mitsubishi Electric PLA-RP140BA / PUHZ-ZRP140YKA Инструкция по эксплуатации