u Communication line
Remote controller wiring
2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
CAUTION
The remote controller wire (Communication line) and AC220240V wires cannot be parallel to contact each
other and cannot be stored in the same conduits.
If doing so, a trouble may be caused on the control system due to noise, etc.
Control wiring between indoor units, and outdoor unit
(2-core shield wire)
Central control line wiring (2-core shield wire)
Wire size
Wire size
(Up to 1000m) 1.25 mm²
(Up to 2000m) 2.0 mm²
(Up to 1000m) 1.25 mm²
(Up to 2000m) 2.0 mm²
Remote controller wiring, remote controller inter-unit wiring Wire size: 0.5mm² to 2.0mm²
Total wire length of remote controller wiring and
In case of wired type only Up to 500m
remote controller inter-unit wiring = L + L1 + L2 + Ln
In case of wireless type included Up to 400m
Total wire length of remote controller inter-unit wiring = L1 + L2 + Ln Up to 200m
n Wire connection
REQUIREMENT
Be sure to connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
Be sure to pass the wires through the bushing of wiring connection port of the indoor unit.
Keep a margin (Approx. 100mm) on a wire to hang down the electric parts box at servicing, etc.
The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
Make a loop on the wire for margin of the length so that the electric parts box can be taken out during servicing.
1. Remove the cover of the electric parts box by taking off the mounting screws (2 positions) and pushing the
hooking section. (The cover of the electric parts box remains hanged to the hinge.)
2. Connect the power supply wire and remote controller wire to the terminal block of the electric parts box.
3. Tighten the screws of the terminal block, and fix the wires with cord clamp attached to the electric parts box.
(Do not apply tension to the connecting section of the terminal block.)
4. Using the attached thermal insulation material, seal the pipe connecting port.
Otherwise, dewing may be caused.
5. Mount the cover of the electric parts box without pinching wires.
(Mount the cover after wiring on the ceiling panel.)
u Thermal insulation to wiring connecting port
7 ELECTRICAL WORK
Remote controller
wiring
Indoor unit
Remote
controller
Remote controller inter-unit wiring
Ln
(Max. 8 units)
L1 L2
Indoor unit Indoor unit Indoor unit
R
(L)
10
10
50
70
S
(N)
RS
U
1
U
2
A
B
Notched section
Adhered surface
Connecting cord
Earth line
Hinge
Screws in 2 positions
Louver connector
(CN510:White)
Side D (Space: 8.5mm) Side C (Space: 4mm)
* Cable clamp can be attached on left side.
Wire type
Cabtyre cable
Cabtyre cable
Specification
3-core
stranded wire 2.5mm²
4-core
stranded wire 1.5mm²
Cable clamping
position
Side D
Side C
Power supply terminal block
Cord clamp
Remote controller
terminal block