Installation space (Unit: mm)
Reserve sufficient space required for installation or service work.
Filter cleaning sign term setting
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed
according to the condition of installation.
For setup method, refer to “Filter sign setting” in the Applicable controls of this Manual.
100 or
more
Air discharge
Ceiling
25
A
25
2500 or
more
B
or more
70 or
more
5 or
more
275
Inspection opening (Ceiling opening)
Floor surface
Air discharge
100 or more
450
Check port
120
Service space
(B for maintenance of air filter)
B
Ceiling
25
50 or more
Inspection opening (Ceiling opening)
570
Air intake
Air intake
570
25
Ceiling
Inspection opening (Ceiling opening)
Air intake
570
25
Ceiling
Inspection opening (Ceiling opening)
300 or more
AB
AP0076~AP0186 750 700
AP0246~AP0306 1050 500
AP0366~AP0566 1450 700
4 Installation
CAUTION
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
• To move the indoor unit, hold the hooking brackets (4 positions) only.
Do not apply force to the other parts (such as refrigerant pipe, drain pan, foamed parts, or resin parts).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
External dimensions (Unit: mm)
▼ Dimension
ABCD
AP0076~AP0186 700 765 640 750
AP0246~AP0306 1000 1065 940 1050
AP0366~AP0566 1400 1465 1340 1450
1
180
275
C
L
750
50 50
355
345
236
22
25
570
43
187.5
131
415
13.5
Main unit dimension A
Hanging bolt pitch B
External dimensions of flange C
Access panel
Electrical
control box
D
345 or more
70 or more
Drain pan / Drain
pump check cover
Hanging bolt pitch 650
11-EN 12-EN
Содержание
- Accessory parts p.2
- Drain piping p.2
- Definition of qualified installer or qualified service person the air conditioner must be installed maintained repaired and removed by a qualified installer or qualified service person when any of these jobs is to be done ask a qualified installer or qualified service person to do them for you a qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the following table p.2
- Maintenance 8 p.2
- Generic denomination air conditioner p.2
- Electrical connection 3 p.2
- Duct design 1 p.2
- Troubleshooting 9 p.2
- Contents p.2
- This air conditioner uses r410a an environmentally friendly refrigerant p.2
- Applicable controls 5 p.2
- Thank you for purchasing this toshiba air conditioner please read carefully through these instructions that contain important information which complies with the machinery directive directive 2006 42 ec and ensure that you understand them after completing the installation work hand over this installation manual as well as the owner s manual provided to the user and ask the user to keep them in a safe place for future reference p.2
- Adoption of new refrigerant p.2
- Test run 7 p.2
- Specifications 4 p.2
- Selection of installation place p.2
- Refrigerant piping 2 p.2
- Precautions for safety p.2
- Please read this installation manual carefully before installing the air conditioner p.2
- Original instruction p.2
- Installation p.2
- Stop the unit before the servicing p.3
- Open the service valves before the operation otherwise there might be the burst p.3
- Caution p.3
- Burst hazard p.3
- Warning indications on the air conditioner unit p.3
- Warning p.3
- Warning p.4
- The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual p.4
- Selection of installation location p.4
- Refrigerant piping p.4
- Precautions for safety p.4
- Installation p.4
- General p.4
- Electrical wiring p.4
- Caution p.5
- Accessory parts p.5
- Selection of installation place p.6
- Installation under high humidity atmosphere p.6
- Avoid installing in the following places p.6
- Caution p.7
- Installation space p.7
- Installation p.7
- Filter cleaning sign term setting p.7
- External dimensions p.7
- Treatment of ceiling p.8
- Slide and push the filters until it stop p.8
- Remove the suction board cover attached to the bottom and screw it to the back of unit p.8
- Remove the filters on back of unit p.8
- Mounting filter rails and filters p.8
- Mount the supplied rail to the bottom then set the filter p.8
- Mount the filter stopper p.8
- Mount the filter rail so that the hooks fit into the corresponding holes note that the upper and lower filter rails are not identical p.8
- Installation of indoor unit p.8
- Installation of hanging bolt p.8
- Changing from back air intake to under air intake p.8
- Caution p.8
- Pipe material size and insulator p.9
- Gravitational drainage p.9
- Drain up p.9
- Drain piping p.9
- Connecting drain pipe p.9
- When the electrical and wiring work has not been completed p.10
- When the electrical and wiring work has been completed p.10
- Heat insulating process p.10
- Connecting method of the duct p.10
- Check the draining p.10
- Caution p.10
- Lower limit of p.11
- Air volume p.11
- Low tap 120pa p.11
- 480 580 680 780 880 980 p.11
- High tap 80pa p.11
- 300 400 500 600 700 800 p.11
- 1200 1400 1600 1800 2000 2200 2400 2600 p.11
- High tap 65pa p.11
- 1100 1300 1500 1700 1900 2100 2300 2500 p.11
- High tap 50pa p.11
- High tap 40pa p.11
- High tap 30pa p.11
- High tap 120pa p.11
- High tap 100pa p.11
- Upper limit of external static pessure 120pa p.11
- High tap p.11
- Upper limit of p.11
- Fan characteristics p.11
- Standard filter pressure p.11
- External static pressure pa p.11
- Standard filter p.11
- External static p.11
- Pressure loss p.11
- En 20 en p.11
- Pessure 120pa p.11
- Ap0306 type ap03 6 type ap0486 ap0566 type p.11
- Lower limit of external static pessure 120pa p.11
- Ap0076 type ap0096 ap0126 type ap0156 ap0186 type ap0246 ap0276 type p.11
- Duct design p.12
- Arrangement p.12
- Ap0246 ap0276 ap0306 ap0366 ap0486 ap0566 p.12
- Ap0156 ap0186 p.12
- Ap0076 ap0096 ap0126 p.12
- Flaring p.13
- Evacuation p.13
- Connecting refrigerant piping p.13
- Caution p.13
- Refrigerant piping p.13
- Refrigerant amount to be added p.13
- Projection margin in flaring b unit mm p.13
- Pipe size p.13
- Permissible piping length and p.13
- Open the valve fully p.13
- Height difference p.13
- Gas leak check p.13
- Flaring diameter size a unit mm p.13
- Warning p.14
- Specifications p.14
- Power supply wire and communication wires p.14
- Indoor unit power supply p.14
- Heat insulation process p.14
- Electrical connection p.14
- Caution p.14
- Wiring example p.15
- Wiring between indoor unit and outdoor unit p.15
- The remote controller wire communication line and ac 220 240 v wires cannot be parallel to contact each other and cannot be stored in the same conduits if doing so a trouble may be caused on the control system due to noise or other factor p.15
- Remote controller wiring p.15
- Power supply p.15
- Control wiring central controller wiring p.15
- Communication line p.15
- Caution p.15
- An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit p.15
- 2 core with polarity wires are used for the control wiring between indoor unit and outdoor unit and central controller wiring to prevent noise trouble use 2 core shield wire the length of the communication line means the total length of the inter unit wire length between indoor and outdoor units added with the central control system wire length p.15
- 2 core with non polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring p.15
- Settings p.16
- Remote controller wiring p.16
- Push and hold button and temp button simultaneously for 4 seconds or more after a while the display flashes as shown in the figure confirm that the code no is 01 p.16
- Basic procedure for changing p.16
- Applicable controls p.16
- Wire connection p.16
- Settings p.17
- External static pressure p.17
- Test run p.18
- Maintenance p.19
- Troubleshooting p.20
- Confirmation of error log p.20
- Confirmation and check p.20
- The following list shows each check code find the check contents from the list according to part to be checked in case of check from indoor remote controller see wired remote controller display in the list in case of check from outdoor unit see outdoor unit 7 segment display in the list in case of check from ai net central control remote controller see ai net central control display in the list in case of check from indoor unit with a wireless remote controller see sensor block display of receiving unit in the list lighting flashing goes off ai net artificial intelligence ipdu intelligent power drive unit alt flashing is alternately when there are two flashing led sim simultaneous flashing when there are two flashing led p.21
- On the wired remote controller central control remote controller and the interface p c board of the outdoor unit i f a check display lcd remote controller or 7 segment display on the outdoor interface p c board to display the operation is provided therefore the operation status can be known using this self diagnosis function a trouble or position with error of the air conditioner can be found as shown in the following table p.21
- Check method p.21
- Check code list p.21
- Error detected by tcc link central control device p.24
- Specifications p.25
- Declaration of conformity p.25
- Check of concentration limit p.26
- Warnings on refrigerant leakage p.26
- Note 3 p.26
- Note 2 p.26
- Note 1 p.26
- Important p.26
- Requirement p.27
- Prior to delivery to the customer check the address and setup of the indoor unit which has been installed in this time and fill the check sheet following table data of four units can be entered in this check sheet copy this sheet according to the no of the indoor units if the installed system is a group control system use this sheet by entering each line system into each installation manual attached to the other indoor units p.27
- Indoor unit setup check sheet p.27
- Confirmation of indoor unit setup p.27
- Toshiba carrier thailand co ltd p.28
Похожие устройства
-
Toshiba MMK-AP0074MH-EИнструкция по эксплуатации -
Toshiba MMK-AP0094MH-EИнструкция по эксплуатации -
Toshiba MMK-AP0124MH-EИнструкция по эксплуатации -
Toshiba MMD-AP0156BH-EБрошюра -
Toshiba MMD-AP0156BH-EИнструкция по эксплуатации -
Toshiba MMD-AP0126BHP-EИнструкция по эксплуатации -
Toshiba MMC-AP0364H-EБрошюра -
Toshiba MMC-AP0364H-EИнструкция по эксплуатации -
Toshiba MMC-AP0244H-EБрошюра -
Toshiba MMC-AP0244H-EИнструкция по эксплуатации -
Toshiba MMC-AP0274H-EБрошюра -
Toshiba MMC-AP0274H-EИнструкция по эксплуатации
Узнайте, как правильно установить и обслуживать внутренние блоки. Следуйте инструкциям по пространству установки, очистке фильтров и соблюдению мер безопасности.