–7–
Installation of hanging bolt
• Consider the piping / wiring after the unit is hung to
determine the location of the indoor unit installation
and orientation.
• After the location of the indoor unit installation has
been determined, install hanging bolts.
• For the dimensions of the hanging bolt pitches, refer
to the external view.
• When a ceiling already exists, lay the drain pipe,
refrigerant pipe, control wires, and remote controller
wires to their connection locations before hanging
the indoor unit.
Procure hanging bolts washer and nuts for installing
the indoor unit (these are not supplied).
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, locally procured).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.
Installation of indoor unit
Treatment of ceiling
The ceiling differs according to structure of building.
For details, consult your constructor or interior finish
contractor.
In the process after the ceiling board has been
removed, it is important to reinforce ceiling foundation
(frame) and to keep horizontal level of installed ceiling
correctly in order to prevent vibration of ceiling board.
• Attach the nuts and the M10 flat washers to the
hanging bolt.
• Put washers at up and down of the hanging bracket
of the indoor unit to hang down the indoor unit.
• Check that four sides are horizontal with a level
gauge. (Horizontal degree: Within 5 mm)
REQUIREMENT
• Hang the unit in a horizontal position.
When unit is hanged to slant, it may cause overflow of
drainage.
• Install the unit within the dimension according to the
figure below.
• Use level gauge to confirm whether the unit is hang
horizontally.
Hanging bolt M10 or W3/8 4 pieces
Nut M10 or W3/8 12 pieces
Washer M10 8 pieces
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Steel flame structure
Use existing angles or install new support angles.
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
Rubber
Anchor bolt
(Blade type
bracket)
(Slide type
bracket)
(Pipe hanging
anchor bolt)
Hanging bolt
Hanging bolt
Support angle
Nut
(W3/8 or M10)
M10 flat washer
M10 flat washer
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
0 to 5 mm
±5 mm
Set the air intake and air
discharge sides are within 5 mm
with each other.
Set the drain pipe connecting
port side within 5 mm lower
than opposite side.
Front view
Side view
Mounting filter rails and filters
1 Mount the filter rail so that the hooks fit into the corresponding holes.
(Note that the upper and lower filter rails are not identical.)
Changing from back air intake to under air intake
1 Remove the filters on back of unit.
2 Remove the suction board cover attached to the bottom, and screw it to the back of unit.
3 Mount the supplied rail to the bottom, then set the filter.
* The sizes of the left and right covers of SM80 class unit are not identical. As shown in the figure, re-mount the
covers left-right reversed by facing the hook part upwards.
2 Mount the filter stopper.
CAUTION
When mounting the rails, push them until the 3
latches click.
3 Slide and push the filters until it stop.
* Insert the filters into the direction which the
arrows, carved on the filters, show. (2 filters
are identical)
Filter stopper (accessory)
Lower filter rail
Square hole
Fit this hook into
the square hole.
Upper filter rail
Suction board cover
Suction board cover
Hook part
Hook part
Screw
Suction board cover
Suction board cover
Screw
13-EN 14-EN
Содержание
- Accessory parts p.2
- Maintenance 8 p.2
- Drain piping p.2
- Definition of qualified installer or qualified service person the air conditioner must be installed maintained repaired and removed by a qualified installer or qualified service person when any of these jobs is to be done ask a qualified installer or qualified service person to do them for you a qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the following table p.2
- Contents p.2
- This air conditioner uses r410a an environmentally friendly refrigerant p.2
- Applicable controls 5 p.2
- Thank you for purchasing this toshiba air conditioner please read carefully through these instructions that contain important information which complies with the machinery directive directive 2006 42 ec and ensure that you understand them after completing the installation work hand over this installation manual as well as the owner s manual provided to the user and ask the user to keep them in a safe place for future reference p.2
- Adoption of new refrigerant p.2
- Test run 7 p.2
- Specifications 4 p.2
- Selection of installation place p.2
- Refrigerant piping 2 p.2
- Precautions for safety p.2
- Please read this installation manual carefully before installing the air conditioner p.2
- Original instruction p.2
- Installation p.2
- Generic denomination air conditioner p.2
- Electrical connection 3 p.2
- Duct design 1 p.2
- Troubleshooting 9 p.2
- Warning indications on the air conditioner unit p.3
- Warning p.3
- Stop the unit before the servicing p.3
- Open the service valves before the operation otherwise there might be the burst p.3
- Caution p.3
- Burst hazard p.3
- Warning p.4
- The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual p.4
- Selection of installation location p.4
- Refrigerant piping p.4
- Precautions for safety p.4
- Installation p.4
- General p.4
- Electrical wiring p.4
- Accessory parts p.5
- Caution p.5
- Selection of installation place p.6
- Installation under high humidity atmosphere p.6
- Avoid installing in the following places p.6
- Installation space p.7
- Installation p.7
- Filter cleaning sign term setting p.7
- External dimensions p.7
- Caution p.7
- Mount the supplied rail to the bottom then set the filter p.8
- Mount the filter stopper p.8
- Mount the filter rail so that the hooks fit into the corresponding holes note that the upper and lower filter rails are not identical p.8
- Installation of indoor unit p.8
- Installation of hanging bolt p.8
- Changing from back air intake to under air intake p.8
- Caution p.8
- Treatment of ceiling p.8
- Slide and push the filters until it stop p.8
- Remove the suction board cover attached to the bottom and screw it to the back of unit p.8
- Remove the filters on back of unit p.8
- Mounting filter rails and filters p.8
- Pipe material size and insulator p.9
- Gravitational drainage p.9
- Drain up p.9
- Drain piping p.9
- Connecting drain pipe p.9
- When the electrical and wiring work has not been completed p.10
- When the electrical and wiring work has been completed p.10
- Heat insulating process p.10
- Connecting method of the duct p.10
- Check the draining p.10
- Caution p.10
- High tap 40pa p.11
- High tap 30pa p.11
- High tap 120pa p.11
- High tap 100pa p.11
- Upper limit of external static pessure 120pa p.11
- High tap p.11
- Upper limit of p.11
- Fan characteristics p.11
- Standard filter pressure p.11
- External static pressure pa p.11
- Standard filter p.11
- External static p.11
- Pressure loss p.11
- En 20 en p.11
- Pessure 120pa p.11
- Ap0306 type ap03 6 type ap0486 ap0566 type p.11
- Lower limit of external static pessure 120pa p.11
- Ap0076 type ap0096 ap0126 type ap0156 ap0186 type ap0246 ap0276 type p.11
- Lower limit of p.11
- Air volume p.11
- Low tap 120pa p.11
- 480 580 680 780 880 980 p.11
- High tap 80pa p.11
- 300 400 500 600 700 800 p.11
- High tap 65pa p.11
- 1200 1400 1600 1800 2000 2200 2400 2600 p.11
- High tap 50pa p.11
- 1100 1300 1500 1700 1900 2100 2300 2500 p.11
- Arrangement p.12
- Ap0246 ap0276 ap0306 ap0366 ap0486 ap0566 p.12
- Ap0156 ap0186 p.12
- Ap0076 ap0096 ap0126 p.12
- Duct design p.12
- Refrigerant piping p.13
- Refrigerant amount to be added p.13
- Projection margin in flaring b unit mm p.13
- Pipe size p.13
- Permissible piping length and p.13
- Open the valve fully p.13
- Height difference p.13
- Gas leak check p.13
- Flaring diameter size a unit mm p.13
- Flaring p.13
- Evacuation p.13
- Connecting refrigerant piping p.13
- Caution p.13
- Electrical connection p.14
- Caution p.14
- Warning p.14
- Specifications p.14
- Power supply wire and communication wires p.14
- Indoor unit power supply p.14
- Heat insulation process p.14
- Wiring example p.15
- Wiring between indoor unit and outdoor unit p.15
- The remote controller wire communication line and ac 220 240 v wires cannot be parallel to contact each other and cannot be stored in the same conduits if doing so a trouble may be caused on the control system due to noise or other factor p.15
- Remote controller wiring p.15
- Power supply p.15
- Control wiring central controller wiring p.15
- Communication line p.15
- Caution p.15
- An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit p.15
- 2 core with polarity wires are used for the control wiring between indoor unit and outdoor unit and central controller wiring to prevent noise trouble use 2 core shield wire the length of the communication line means the total length of the inter unit wire length between indoor and outdoor units added with the central control system wire length p.15
- 2 core with non polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring p.15
- Wire connection p.16
- Settings p.16
- Remote controller wiring p.16
- Push and hold button and temp button simultaneously for 4 seconds or more after a while the display flashes as shown in the figure confirm that the code no is 01 p.16
- Basic procedure for changing p.16
- Applicable controls p.16
- Settings p.17
- External static pressure p.17
- Test run p.18
- Maintenance p.19
- Troubleshooting p.20
- Confirmation of error log p.20
- Confirmation and check p.20
- On the wired remote controller central control remote controller and the interface p c board of the outdoor unit i f a check display lcd remote controller or 7 segment display on the outdoor interface p c board to display the operation is provided therefore the operation status can be known using this self diagnosis function a trouble or position with error of the air conditioner can be found as shown in the following table p.21
- Check method p.21
- Check code list p.21
- The following list shows each check code find the check contents from the list according to part to be checked in case of check from indoor remote controller see wired remote controller display in the list in case of check from outdoor unit see outdoor unit 7 segment display in the list in case of check from ai net central control remote controller see ai net central control display in the list in case of check from indoor unit with a wireless remote controller see sensor block display of receiving unit in the list lighting flashing goes off ai net artificial intelligence ipdu intelligent power drive unit alt flashing is alternately when there are two flashing led sim simultaneous flashing when there are two flashing led p.21
- Error detected by tcc link central control device p.24
- Specifications p.25
- Declaration of conformity p.25
- Warnings on refrigerant leakage p.26
- Note 3 p.26
- Note 2 p.26
- Note 1 p.26
- Important p.26
- Check of concentration limit p.26
- Requirement p.27
- Prior to delivery to the customer check the address and setup of the indoor unit which has been installed in this time and fill the check sheet following table data of four units can be entered in this check sheet copy this sheet according to the no of the indoor units if the installed system is a group control system use this sheet by entering each line system into each installation manual attached to the other indoor units p.27
- Indoor unit setup check sheet p.27
- Confirmation of indoor unit setup p.27
- Toshiba carrier thailand co ltd p.28
Похожие устройства
-
Toshiba MMK-AP0074MH-EИнструкция по эксплуатации -
Toshiba MMK-AP0094MH-EИнструкция по эксплуатации -
Toshiba MMK-AP0124MH-EИнструкция по эксплуатации -
Toshiba MMD-AP0156BH-EБрошюра -
Toshiba MMD-AP0156BH-EИнструкция по эксплуатации -
Toshiba MMD-AP0126BHP-EИнструкция по эксплуатации -
Toshiba MMC-AP0364H-EБрошюра -
Toshiba MMC-AP0364H-EИнструкция по эксплуатации -
Toshiba MMC-AP0244H-EБрошюра -
Toshiba MMC-AP0244H-EИнструкция по эксплуатации -
Toshiba MMC-AP0274H-EБрошюра -
Toshiba MMC-AP0274H-EИнструкция по эксплуатации
Узнайте, как правильно установить внутренний блок кондиционера. Пошаговые инструкции по монтажу, выбору крепежа и проверке уровня для надежной работы.