AFLV _FL06_IT-EN Rev.01 11-2014 pag. 51
7. - PARAMETER TABLE
To enter programming press the UP and DOWN arrows simultaneously for at least 4 seconds. Display (B) will show the
parameter number and display (D) its value. Use (L) and (N) to go from one parameter to another and the UP and DOWN
arrows to edit the value.
Par. n°
Description
Meas. Unit
Setting
AFLV / 20 - 40
1
0=Celsius
1=Fahrenheit
- - -
0
2
Min set-point Cooling
°C
-2
3
Max set-point Cooling
°C
+14
4
Min set-point Proving
°C
+14
5
Max set-point Proving
°C
+35
6
Min set-point Holding
°C
-2
7
Max set-point Holding
°C
+35
8
Regulation hysteresis
°C
+3
9
Counter-phase cut-in differential
°C
+1
10
Fan pickup time
Sec.
5
11
Fan partialization scale
- - -
600
12
Delay between two compressor ONs
Sec.
300
13
Delay between compressor OFF and ON
Sec.
270
14
Compressor inhibition time from reset
Sec.
10
15
Door polarity:
0=no voltage applied (door closed)
1=voltage applied (door closed)
- - -
1
16
Door open buzzer delay
Sec.
20
17
Safety thermostat polarity:
0=activate alarm with open contact
1=activate alarm with closed contact
- - -
0
18
Manual programming time-out
Sec.
20
19
Automatic programming time-out
Sec.
20
20
Time between two successive defrosting
operations
.h.
8
21
Type of defrosting:
0=element
1=hot gas
2=air
- - -
0
22
End of defrosting temperature
°C
8
23
Max. duration defrosting
.min.
30
24
Dripping time
.min.
5
25
Time base:
0=hours/minutes
1=minutes/seconds
- - -
0
26
Enables fan stop during defrosting
0=enable
1=stop
- - -
1
27
Duration fan stop after dripping
.min.
0
28
Choice of stage in which defrosting is enabled:
0=no stage
1=cooling
2=cooling/holding
3=holding
- - -
2
29
Omissis
Sec.
0
30
Evaporator probe enabling:
0=disabled
1=enabled
- - -
1
31
Cabinet temperature bottom limit for steam
injection
°C
+10
32
Enables humidity control by elements:
0=always ON Humidity
1=ON Humidity with ON elements
- - -
0
33
Choice of configuration:
0=step Humidity
1=ON Humidity / controlled Humidity
- - -
1
34
Par.33=1 Humidity regulation differential
%
5
35
P1 steam injection ON time
Sec.
0
36
P2 steam injection ON time
Sec.
0
37
P3 steam injection ON time
Sec.
0
38
P4 steam injection ON time
Sec.
0
39
P5 steam injection ON time
Sec.
0