Hoshizaki KM-100A [10/65] Sequence of operation

7
2. SEQUENCE OF OPERATION
Thestepsinthesequenceareasoutlinedbelow.Whenpowerissupplied,a5second
delayoccursatstartup.NotethattheorderoftheLEDsfromtheouteredgeoftheboard
is5,6,8,9,4,7.
[a] ONE MINUTE FILL CYCLE
LED8ison.WVopensandthellperiodbegins.After1minute,theboardchecksfor
aclosedF/S.IfF/Sisclosed,theharvestcyclebegins.Ifnot,WVwillremainenergized
through additional 1 minute cycles until water enters the sump and F/S closes. This
servesasalowwatersafetytoprotectthewaterpump.
[b] INITIAL HARVEST CYCLE
LEDs5,6,and8areon.WVremainsopen,Compenergizes,HGVopens,andharvest
begins.As the evaporator warms, the thermistor located on the suction line checks
fora9°Ctemperature.When9°Cisreached,a3.9kΩsignalturnstheharvestoverto
the adjustable harvest timer which is factory set for normal conditions.The timer has
settingsof60,90,120,and180seconds(S1dipswitch1&2).Whentheharvesttimer
completesitscountdown,theharvestcycleiscompleteandthefreezecyclestarts.The
minimumtotaltimeallowedbytheboardforacompleteharvestcycleis2minutes.WV
isopenduringharvestforamaximumof6minutesorthelengthofharvestminus0,10,
30,or50seconds(adjustablebyS1dipswitch7&8),whicheverisshorter.LED8goes
offwhen WV closes. PM energizes and runs for the last 0, 10, 30, or 50 seconds of
harvestdependingonS1dipswitch7&8setting.LED7comesonwhenPMenergizes.
Attheendofharvest,thecontrolboardchecksthepositionofF/Sandproceedstothe
freezecycleifitisclosedorcallsfora1-minutellifitisopen.
[c] FREEZE CYCLE
LEDs5&7areon.Compcontinuestorun,PMandFMSenergize,HGVclosesandthe
freezecyclestarts.Fortherst5minutesafterthethermistortemperaturereaches2°C,
thecontrolboardwillnotacceptasignalfromF/S.Thisminimumfreezeperiodactsasa
shortcycleprotection.Attheendofthisperiod,F/Sassumescontrol.Astheevaporator
cools,thethermistorlocatedonthesuctionlinechecksthetemperatureandPMstops
(see“III.3.TIMINGCHART”fordetails).Thisistopreventslushing.Asicebuildsonthe
evaporatorthewaterlevelinthesumplowers.ThefreezecontinuesuntilF/Sopensand
terminatesiceproduction.