FSP EP1500 [3/41] Trouble shooting

FSP EP1500 [3/41] Trouble shooting
6. Trouble Shooting
Problem
Possible Cause
Solution
No words on the front
LCD panel display.
Low battery.
Charge the UPS at least 6 hours.
Battery fault.
Replace the battery with the same
type of battery.
The UPS is not turned on.
Press the power switch again to turn
on the UPS.
Alarm continuously
sounds although
mains supply is
normal.
The UPS is overloaded.
Remove some devices. Before
reconnecting equipment, please
check that the load matches the UPS
capacity specified in the specs.
When power fails,
back-up time is
shorten.
The UPS is overloaded.
Remove some critical load.
Battery voltage is too low.
Charge the UPS at least 6 hours.
Battery defect. Operating
temperature could be too
high, or battery is not
correctly used.
Replace the battery with the same
type of battery.
The mains is normal
but the unit is on
battery mode.
Power cord is loose.
Check and reconnect the power cord.
7 Specifications
Model
EP 1500
EP 2000
CAPACITY
1500 VA / 900 W
2000 VA / 1200 W
Voltage
110/120 VAC or 220/230/240 VAC
Voltage Range
81-145 VAC / 162-290 VAC
Voltage Regulation
+/-10%
Transfer Time
Typical 2-6 ms, 10 ms max.
Waveform
Simulated Sine Wave
Type & Number
12 V/9 AH x 2
Charging Time
4-6 hours recover to 90% capacity
Dimension (DxWxH)
397 x 146 x 205 mm
Net Weight (kgs)
11.1
11.5
Humidity
0-90 % RH @ 0-40° C (non-condensing)
Noise Level
Less than 40 dB
USB/RS-232
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7,
Linux, and MAC
1. Lieferumfang
Im Lieferumfang sollten Sie folgendes finden:
- USV Einheit
- Kurzanleitung
- Kommunikationskabel (nur für Modelle mit USB/RS-232 Schnittstelle)
- Netzkabel (nur für Modelle mit IEC-Eingang)
2. Produktü bersicht
Vorderansicht: LCD panel:
ckansicht:
Line Interactive UPS Kurzanleitung V. 1.1
4
5
DE
Ein/Aus Schalter
LCD panel
Eingangsspannung
Lade Status Anzeige, Blinken
Ausgangsspannung
zeigt Ü berladung an
AC Modus Anzeige
Batteriekapazitätsanzeige, Blinken
Batterie Modus Anzeige zeigt niedrigen Batteriestatus an
Ausgänge
AC Eingang
Schutzschalter
Modem / Telefon / Netzwerk Überspannungsschutz
RS-232 com. Schnittstelle
USB com. Schnittstelle