Page 10
6 - Installation (cont'd)
6.4 - Supply Air Throw (m)
900 1400 900 1400 900 1400 900 1400 900 1400 700 900 900 1400
L
8.0 12.010.014.012.016.014.018.016.020.016.020.014.018.0
H
3.0 3.0 4.0 5.0 4.0 5.0 4.0 5.0 4.0 5.0 4.0 5.0 4.0 5.0
L
8.0 12.010.014.012.016.014.018.016.020.016.020.014.018.0
H
3.0 3.0 4.0 5.0 4.0 5.0 4.0 5.0 4.0 5.0 4.0 5.0 4.0 5.0
D
7.0 10.0 9.0 12.0 11.0 14.0 12.0 16.0 14.0 18.0 14.0 18.0 12.0 16.0
G *
4.0 4.5 4.5 5.0 4.5 5.5 5.0 6.0 5.5 6.5 5.5 6.5 5.0 6.0
S
- - - - - -
L
- - 6.0 8.0 7.0 9.0 7.5 9.0 - - - -
G
4.0 4.5 4.5 5.0 4.5 5.5 5.0 6.0 5.5 6.5 - - - -
D
7.0 10.0 9.0 12.0 11.0 14.0 12.0 16.0 14.0 18.0 - - - -
V
3.0 4.0 3.5 4.5 3.5 5.0 4.0 5.0 3.0 4.0 - - - -
X
3.0 4.0 4.0 5.0 4.5 5.5 5.0 6.0 5.5 6.5 - - - -
2.5 to 4.0
6.5 to 8.5
2.5 to 4.0 2.5 to 4.0
50 55
Fan s
p
eed
VM
3
5
4
5
VR
2.5 to 4.0
7
0
11
0
VN
HN
HO
HP
6
5
Size
s
* Air throw of diffuser HN can be increased by changing the shutter position.
Vertical arrangement Horizontal arrangement
Diffuser VR (air curtain)
Diffuser HO
Diffuser VM, VN Diffuser HP, HN
V
X
L
H
S
L
G
D
The air throw of a propeller fan unit heater is the distance between
the unit and the points where the air velocity is no longer felt by the
human body (approx. 0.2 m/sec.).
The air throw allows the units to be installed in the room.
The table below gives the air throw of a unit in relation to model and
Temp.
difference
Factor
1.28 1.00 0.90 0.70 0.60
40 °C10 °C 15 °C 20 °C 30 °C
Correction factor
supply diffuser, for a supply air temperature difference of 15 °C.
For other temperature differences, use the correction factor.