When the building power supply is of an IT ungrounded type or corner grounded TN type disconnect the internal EMC filter by removing the screw at EMC WARNING If a drive whose EMC filter is not disconnected is installed on an IT system an ungrounded power system ora high resistance grounded over 30 ohms power system the system will be connected to earth potential through the EMC filter capacitors of the drive This may cause danger or damage the drive If a drive whose EMC filter is not disconnected is installed on a corner grounded TN system the drive will be damaged Press the release lever on top of the drive 15 English FREQUENCY DRIVE This equipment is installed on external units 405M 755 and 905