Airwell MQL 8T [14/40] Installation

Airwell MQL 8T [14/40] English
Page 13
English
4.2 Water connections
Water Piping
Local authorities can supply the installer with the
proper building and safety codes required for safe
and proper installation.
Install piping with minimum bends and
changes in elevation to minimize pressure
drop.
Consider the following when installing
water piping:
1. Vibration eliminators to reduce vibration and
noise transmission to the building. Check the free
volume expansion of the connection piping.
2. Shut-off valves to isolate the unit from the piping
system during unit servicing.
3. Manual or automatic air vent valves at the high-
est points of the chilled water piping.
4. A means of maintaining adequate system water
pressure (expansion tank or regulating valve).
5. Temperature and pressure indicators located at
the unit to aid in unit servicing.
6. To avoid all risks of penetration of for-
eign matters and to keep system perfor-
mance up, it is mandatory to install a
strainer at the inlet of the unit.
Protection from freezing
It is recommended to protect the water system from
freezing whatever the model used (cooling only or
reverse cycle). The table below shows the anti-
freeze concentration to be used depending on the
minimum outdoor temperature.
Installation
0 -5 -10 -15 -25 -30
10 20 30 40 50 60
Safety Differential Pressure Switch
A safety differential pressure switch (ref. 6) is facto-
ry mounted on water inlet piping of evaporator, in
order to ensure adequate water flow to evaporator
before starting up the unit.
It comes into operation in case of drop in water
flow owing to the fact that the pump failed to oper-
ate.
The safety differential pressure switch is the main
protective device of the machine.
It is not our policy to make recommenda-
tions on water treatment. The general con-
tractor or owner should contact a local
water treatment company regarding water
treatment. However, this topic is critical
and care should be taken to make sure it is
done properly to prevent problems related
to flow. A fouled water system will lead to
premature component failure.
Water connections could be damaged by
an important stress when screwing them.
Use a second spanner to compensate the
stress of tightening.
Minimum
outdoor temp. °C
Concentration
in %
Manuale MQL-MQH 10.6.2005 12:26 Pagina 13