Airedale OptiChill OPC 750 [17/60] C of g
![Airedale OptiChill OPC 500 [17/60] C of g](/views2/1409430/page17/bg11.png)
Chillers OPTICHILL
Chillers
Installation & Maintenance : 6564868 08/2008
17
Installation Data
WEIGHTS, POINT LOADINGS & CENTRE OF GRAVITY (C OF G) - NO PUMPS
High Efficiency
1
2
L1
R1
L2
R
2
L3
R3
L4
R4
= (C of G)
1
2
L1 L
2
L3 L4
R1 R
2
R3 R4
L5 L
6
R5 R
6
= C of G
Point Loadings (kg) C of G (mm)
L1 L2 L3 L4 L5 L6 R1 R2 R3 R4 R5 R6
Operating
Weight (kg)
1 2
OPC500HED8 650 680 670 470 (1) (1) 830 860 850 590 (1) (1) 5600 1220 2225
OPC525HED8 660 690 680 470 (1) (1) 830 870 850 590 (1) (1) 5640 1220 2225
OPC550HED8 660 690 680 470 (1) (1) 830 870 860 590 (1) (1) 5650 1220 2230
OPC600HED10 750 880 770 370 (1) (1) 920 1080 950 450 (1) (1) 6170 1205 2495
OPC650HED10 760 900 790 380 (1) (1) 1010 1190 1040 500 (1) (1) 6570 1245 2515
OPC700HED12 760 630 830 760 360 (2) 950 800 1040 950 450 (2) 7530 1220 3130
OPC750HED12 810 680 880 810 380 (2) 1010 840 1100 1010 480 (2) 8000 1215 3230
OPC800HED12 810 680 880 810 390 (2) 1010 850 1100 1010 480 (2) 8020 1215 3225
OPC850HED12 820 690 900 820 390 (2) 1070 890 1170 1070 510 (2) 8330 1235 3250
OPC900HED14 820 890 970 860 370 (2) 1040 1130 1240 1100 480 (2) 8900 1225 3510
OPC950HED14 830 900 980 870 380 (2) 1050 1140 1250 1110 480 (2) 8990 1225 3525
OPC1000HED16 900 910 1000 910 490 (2) 1130 1140 1260 1140 610 (2) 9490 1220 4290
OPC1100HED16 900 910 1000 910 490 (2) 1130 1140 1260 1140 610 (2) 9490 1220 4295
Point Loadings (kg) C of G (mm)
L1 L2 L3 L4 L5 L6 R1 R2 R3 R4 R5 R6
Operating
Weight (kg)
1 2
OPC500HEDQ10 800 940 820 390 (1) (1) 960 1130 990 470 (1) (1) 6500 1200 2520
OPC525HEDQ10 800 940 830 390 (1) (1) 960 1140 1000 470 (1) (1) 6530 1200 2520
OPC550HEDQ10 800 950 830 400 (1) (1) 970 1140 1000 480 (1) (1) 6570 1200 2520
OPC600HEDQ10 800 950 830 400 (1) (1) 970 1140 1000 480 (1) (1) 6570 1195 2520
OPC650HEDQ10 810 950 830 400 (1) (1) 970 1140 1000 480 (1) (1) 6580 1195 2525
OPC700HEDQ14 790 860 940 830 360 (2) 970 1050 1150 1020 450 (2) 8420 1205 3440
OPC750HEDQ14 840 910 1000 880 390 (2) 1020 1110 1210 1080 470 (2) 8910 1200 3510
OPC800HEDQ14 850 930 1010 900 390 (2) 1070 1170 1270 1130 490 (2) 9210 1220 3525
OPC850HEDQ14 850 930 1010 900 390 (2) 1070 1170 1280 1130 490 (2) 9220 1220 3525
OPC900HEDQ16 930 940 1040 940 510 (2) 1160 1170 1290 1170 630 (2) 9780 1215 4295
OPC950HEDQ16 940 950 1050 950 510 (2) 1170 1180 1300 1180 630 (2) 9860 1210 4305
OPC1000HEDQ18 970 1040 1110 1010 540 (2) 1180 1280 1360 1240 660 (2) 10390 1205 4485
OPC1100HEDQ18 970 1050 1110 1010 540 (2) 1190 1280 1360 1240 670 (2) 10420 1205 4485
(1) Only 8 fixing and loading points to this model.
(2) Only 10 fixing and loading points to this model.
(3) Based on standard unit, for units fitted with options, please contact Airedale.
(4) Operating weight includes refrigerant charge and system water volume.
Содержание
- Air cooled screw chiller 1
- Installation maintenance 1
- Kw 1100 kw 1
- Optichill 1
- About airedale products customer services 2
- Optichill chillers 2
- Chillers optichill 3
- Contents 3
- General statement 4
- Optichill chillers 4
- Chillers optichill 5
- Warranty 5
- General description 6
- Optichill chillers 6
- Chillers 7
- Features 7
- Installation maintenance 6564868 08 2008 7
- Optichill 7
- General description 8
- Optichill chillers 8
- Chillers optichill 9
- General description 9
- General description 10
- Optichill chillers 10
- Chillers 11
- Chillers optichill 11
- Dimensional data 12
- Optichill chillers 12
- Chillers optichill 13
- Dimensional data 13
- Dimensional data 14
- Optichill chillers 14
- Chillers optichill 15
- Dimensional data 15
- 1 for plenum weights please contact airedale 16
- Dimensional data 16
- Optichill chillers 16
- C of g 17
- Chillers optichill 17
- Installation data 17
- L1 l1 l2 l3 l4 l5 l6 r1 r2 r3 r4 r5 r6 operating weight kg 1 2 17
- Opc1000hed16 17
- Opc1000hedq18 17
- Opc1100hed16 17
- Opc1100hedq18 17
- Opc500hed8 17
- Opc500hedq10 17
- Opc525hed8 17
- Opc525hedq10 17
- Opc550hed8 17
- Opc550hedq10 17
- Opc600hed10 17
- Opc600hedq10 17
- Opc650hed10 17
- Opc650hedq10 17
- Opc700hed12 17
- Opc700hedq14 17
- Opc750hed12 17
- Opc750hedq14 17
- Opc800hed12 17
- Opc800hedq14 17
- Opc850hed12 17
- Opc850hedq14 17
- Opc900hed14 17
- Opc900hedq16 17
- Opc950hed14 17
- Opc950hedq16 17
- Point loadings kg c of g mm 17
- Point loadings kg point loadings kg c of g mm 17
- C of g 18
- Installation data 18
- L1 l1 l2 l3 l4 l5 l6 r1 r2 r3 r4 r5 r6 operating weight kg 1 2 18
- Opc1000he d18 18
- Opc1000he dq20 18
- Opc1100he d18 18
- Opc1100he dq20 18
- Opc500he d8 18
- Opc500he dq12 18
- Opc525he d10 18
- Opc525he dq12 18
- Opc550he d10 18
- Opc550he dq12 18
- Opc600he d10 18
- Opc600he dq12 18
- Opc650he d10 18
- Opc650he dq12 18
- Opc700he d12 18
- Opc700he dq14 18
- Opc750he d12 18
- Opc750he dq16 18
- Opc800he d14 18
- Opc800he dq16 18
- Opc850he d14 18
- Opc850he dq18 18
- Opc900he d16 18
- Opc900he dq20 18
- Opc950he d18 18
- Opc950he dq20 18
- Optichill chillers 18
- Point loadings kg c of g mm 18
- Point loadings kg point loadings kg c of g mm 18
- Chillers optichill 19
- Installation data 19
- Installation data 20
- Optichill chillers 20
- 2 for models with optional pumps fitted please consult airedale 21
- A 1 b c d e fø 21
- Beginning with the mount with the largest deflection adjust the height of each mount using the levelling screw 3 21
- Chillers optichill 21
- Components 21
- Components installation 21
- Dimensions 21
- Do not connect any services until all anti vibration mounts have been fully adjusted 21
- Each mount is coloured to indicate the different loads refer to av selection sheet supplied separately for correct allocation 21
- Installation 21
- Installation data 21
- Installation maintenance 6564868 08 2008 21
- Locate and secure mount using bolting down holes 10 in base plate 2 ensure mounts are located in line with the unit base 3 if applicable remove compressor enclosure covers to allow access to mount fixing holes in the unit base 4 lock the upper retaining nuts 6a to the underside of the top plate 9 before a load is applied 5 remove retaining nut and washer 2 lower the unit onto the mounts and replace retaining nut and washer 21
- Mountings must be adjusted incrementally in turn do not fully adjust 1 mount at a time as this may overload and damage springs 21
- When all mounts are level lock each into place using the levelling lock nut 4 8 lock all retaining nuts 6a and 6b to the extreme ends of the retaining studs 5 21
- Installation data 22
- Optichill chillers 22
- Chillers optichill 23
- Installation data 23
- Following components are fitted within the chiller unit as standard following components are fitted within the chiller unit as standard temperature sensors drain point auto air vent 24
- Full design water flow must be maintained at all times variable water volume is not recommended and will invalidate warranty 24
- Installation data 24
- Installation maintenance 6564868 08 2008 24
- On page 10 for details 24
- Optichill chillers 24
- Optional extra 24
- The correct operation of the flow proving device is critical if the chiller warranty is the correct operation of the flow proving device is critical if the chiller warranty is to be valid 24
- The following diagram illustrates the minimum component installation requirements a wide range of optional extras are available to suit various applications please refer to 24
- The following installation recommendations should be adhered to failure to do this will invalidate the chiller warranty 24
- Chillers optichill 25
- Installation data 25
- Installation data 26
- Optichill chillers 26
- Chillers optichill 27
- Installation data 27
- Installation data 28
- Optichill chillers 28
- Chillers optichill 29
- Installation data 30
- Optichill chillers 30
- Chillers optichill 31
- Installation data 31
- Installation data 32
- Optichill chillers 32
- Chillers optichill 33
- Installation data 34
- Optichill chillers 34
- Chillers optichill 35
- Installation data 36
- Optichill chillers 36
- Chillers optichill 37
- Controls 38
- Optichill chillers 38
- Chillers optichill 39
- Controls 39
- Controls 40
- Optichill chillers 40
- Chillers optichill 41
- Controls 41
- Controls 42
- Optichill chillers 42
- Chillers optichill 43
- Commissioning data 43
- Commissioning data 44
- Optichill chillers 44
- Chillers optichill 45
- Commissioning data 46
- Optichill chillers 46
- Chillers optichill 47
- Commissioning data 47
- Commissioning data 48
- Optichill chillers 48
- Chillers optichill 49
- Commissioning data 49
- Commissioning data 50
- Cp1 on 50
- Cp3 on 50
- Cp5 off 50
- Cp5 on 50
- Optichill chillers 50
- Chillers optichill 51
- Commissioning data 51
- Commissioning procedure 52
- Optichill chillers 52
- Chillers optichill 53
- Commissioning procedure 53
- Commissioning procedure 54
- Optichill chillers 54
- Chillers optichill 55
- Maintenance 55
- Maintenance 56
- Optichill chillers 56
- Chillers optichill 57
- Maintenance 57
- Optichill chillers 58
- Parts identification 58
- Chillers 59
- Chillers optichill 59
- Installation maintenance 6564868 08 2008 59
- Head office 60
Похожие устройства
- Airedale OptiChill OPC 800 Инструкция по эксплуатации
- Airedale OptiChill OPC 850 Инструкция по эксплуатации
- Airedale OptiChill OPC 900 Инструкция по эксплуатации
- Airedale OptiChill OPC 950 Инструкция по эксплуатации
- Airedale OptiChill OPC 1000 Инструкция по эксплуатации
- Airedale OptiChill OPC 1100 Инструкция по эксплуатации
- Airedale TurboChill TTC1 Инструкция по эксплуатации
- Airedale UCFC 75 Инструкция по эксплуатации
- Airedale UCFC 100 Инструкция по эксплуатации
- Airedale UCFC 125 Инструкция по эксплуатации
- Juguni 0402.711 Инструкция по эксплуатации
- Airedale UCFC 150 Инструкция по эксплуатации
- Airedale UCFC 160 Инструкция по эксплуатации
- Juguni 0402.732 Инструкция по эксплуатации
- Airedale UCFC 225 Инструкция по эксплуатации
- Juguni 0402.742 Инструкция по эксплуатации
- Airedale UCFC 275 Инструкция по эксплуатации
- Airedale UCFC 330 Инструкция по эксплуатации
- Airedale UCFC 450 Инструкция по эксплуатации
- Juguni 0402.643 Инструкция по эксплуатации