Airedale UCFC 160 [12/46] Ultima compact freecool chillers

Airedale UCFC 125 [12/46] Ultima compact freecool chillers
ULTIMA COMPACT FREECOOL Chillers
Chillers
12
Installation & Maintenance : 903-132 IM E 06/05/A
Installation Data
Employ lifting specialists.
Local codes and regulations relating to the lifting of this type of equipment should
be observed.
Use the lifting eye bolts provided.
Use the appropriate spreader bars/lifting slings with the holes/lugs provided.
Attach lifting chains to the 4 lifting eye bolts/lifting lugs provided, each chain and eye
bolt must be capable of lifting the whole chiller.
Lift the unit slowly and evenly.
UNIT LIFTING
If the unit is dropped, it should immediately be checked for damage and reported to
Airedale Service.
CAUTION
Only use lifting points provided.
The unit should be lifted from the base and where possible, with all packing and
protection in position. If any other type of slinging is used, due care should be taken to
ensure that the slings do not crush the casework or coil.
LIFTING DIMENSIONS
E
A
B
C
D
UCFC75 - UCFC450 A B C D E
2 FANS /1 mm 290 1900 585 2500 1450
3 FANS /1 mm 290 2015 1320 2500 1450
4 FANS /1 mm 290 2870 1315 3000 1450
6 FANS /2 mm 465 2195 1140 2500 2350
8 FANS /2 mm 465 2560 1625 2500 2350
10 FANS/2 mm 465 3135 1900 3500 2350
12 FANS/2 mm 465 3610 2275 3500 2350
14 FANS/2 mm 465 4385 2350 4000 2350
16 FANS/2 mm 465 5035 2550 5000 2350

Содержание