Airedale Ultima FreeCool UFC 300 [21/46] Ultima freecool chillers

Airedale Ultima FreeCool UFC 575 [21/46] Ultima freecool chillers
ULTIMA FREECOOL Chillers
Chillers
20
Installation & Maintenance Manual : 903-125 IM E 05/04/A
Installation Data
ELECTRICAL DATA
Model UFC200D-8 UFC225D-8 UFC250D-8 UFC275D-8 UFC300D-8
Unit Data (1)
Nominal Run Amps (2) A 141 154 167 174 183
Maximum Start Amps A 289 335 348 356 336
Permanent Supply VAC 230V 1PH 50Hz
Mains Supply VAC 400V 3PH 50Hz
Rec Permanent Fuse Size A 16 16 16 16 16
Rec Mains Fuse Size A 200 200 250 250 250
Max Permanent Incoming Cable
Size
mm² 4mm² Terminal
Max Mains Incoming Cable Size mm² Direct to Bus Bar
Control Circuit VAC 24V / 230VAC
Evaporator
Trace Heater Rating W 200 200 200 200 250
External Trace Heating
Available (fitted by others) W 500 500 500 500 500
Condenser Fan - Per Fan
Full Load Amps A 2.60 2.60 2.60 2.60 2.60
Locked Rotor Amps A 15.00 15.00 15.00 15.00 15.00
Motor Rating kW 1.70 1.70 1.70 1.70 1.70
Compressor - Per Compressor
Motor Rating kW 33 + 33 41 + 33 41 + 41 48 + 41 48 + 48
Nominal Run Amps (2) A 60 + 60 73 + 60 73 + 73 81 + 73 81 + 81
Crankcase Heater Rating W 150 150 150 150 150
Start Amps (3) 208 + 208 254 + 208 254 + 254 234 + 254 234 + 234
Type Of Start Star / Delta
QUIET DQ UFC200DQ-8 UFC225DQ-8 UFC250DQ-8 UFC275DQ-8 UFC300DQ-10
All data as above except:
Condenser Fan - Per Fan
Full Load Amps A 1.75 1.75 1.75 1.75 1.75
Locked Rotor Amps A 6.20 6.20 6.20 6.20 6.20
Motor Rating kW 0.98 0.98 0.98 0.98 0.98
SUPER QUIET DSQ UFC200DSQ-8 UFC225DSQ-8 UFC250DSQ-8 UFC275DSQ-10 UFC300DSQ-10
All data as above except:
Condenser Fan - Per Fan
Full Load Amps A 1.15 1.15 1.15 1.15 1.15
Locked Rotor Amps A 2.10 2.10 2.10 2.10 2.10
Motor Rating kW 0.70 0.70 0.70 0.70 0.70
OPTIONAL EXTRAS - Fitted to standard D models - for data on DQ & DSQ please refer to Airedale.
Power Factor Correction
Nominal Run Amps (2) A 129 140 151 158 165
Maximum Start Amps (3) A 289 335 348 356 336
Recommended Mains
Fuse
A 160 200 200 250 250
Compressor Nominal
Run Amps - Per
Compressor
A 54 + 54 65 + 54 65 + 65 72 + 65 72 + 72
Closed Transition
Nominal Run Amps (2) A 141 154 167 174 183
Maximum Start Amps A 289 335 348 356 336
Recommended Mains
Fuse
A 200 200 250 250 250
Compressor Nominal
Run Amps - Per
Compressor
A 60 + 60 73 + 60 73 + 73 81 + 73 81 + 81
(1) Refers to standard speed fans.
(2) Based at 12/7°C water and 30°C ambient
(3) Starting amps refers to the Star connection only.