Aspen pumps ERRP Pump [2/6] Economy retail refrigeration pump errp

Aspen pumps ERRP Pump [2/6] Economy retail refrigeration pump errp
Description:
The pump is designed to be installed underneath
refrigeration chiller units to collect water during
the defrost cycle, where direct drainage is not
available. The pump is triggered by a hall-effect
float/sensor arrangement and will discharge the
water to a maximum height of 30 metres to a
suitable drain. There is a high level safety switch
which will either enable the plant to be switched
off or sound an alarm in the event of a
pump failure.
Installation Notes:
This pump is designed to sit level on its base.
Ensure that there are no kinks or trapped parts in
the discharge piping, which must have an internal
diameter of 9mm and be secured to the pump
outlet with a clamp.
The float must always
be located around the
float column, with the
magnet uppermost:
IMPORTANT: For hygiene and performance, we
strongly recommend an anti-bacterial “Stayclean”
strip is ALWAYS positioned between the two filters
in the tank.
The anti-bacterial strip must be BETWEEN the two
filters and NOT in the float chamber:
IMPORTANT Service Guide:
Flush the pump through with anti-bacterial wash
and clean both filters every 6 months or more
often if required, to avoid sludge build up.
Replacement anti-bacterial “Stayclean” strips are
available from Aspen Pumps.
N.B. The contractors should satisfy themselves
that any chemicals used are compatible with
the pump.
For further help contact Aspen Pumps.
GB
Technical Specification:
Q ABS Plastic tank/covers
Q Tank capacity: 11 litres
Q Maximum water flow rate:
225 litres per hour
Q
Maximum recommended head: 30 metres
Q Thermally protected 230V
continuously rated motor
Q 75W max. 0.35 A max.
Q High level safety switch
Q Inlet hole in tank cover: 50mmØ
(side inlet option also available)
Q Outlet hose connection: 10mmØ
Q Push-in plug connector
Q Filter to catch debris
Q Water temperature: 0ºC to 40ºC
Dimensions:
Height: 100mm Width: 590mm
Depth: 405mm Weight: 4.9kg
Electrical Connections:
Brown: Live
Blue: Neutral
Green/yellow: Earth
Black: N/C
Black: Common
Economy
Retail
Refrigeration
Pump (ERRP)
Float
Fine filter
“Stay clean” strip
Large filter
IMPORTANT:
The safety switch should
always be utilised.
PUMP CASING
PCB
PUMP
MOTOR
FLOAT
SAFETY
ON
OFF
LIVE
NEUTRAL
EARTH
N/C
COMMON
4
3
2
1
0
010203040
FLOW IN LITRES/MIN
TYPICAL PERFORMANCE
METRES HEAD