TECHNICAL DATA
TBG 45 TBG 45P TBG 60 TBG 60P
THERMIC CAPACITY
MAX kW 450 600
MIN kW 100 120
OPERATION One stage Two stages One stage Two stages
NOx EMMISION mg/kWh < 80 (Classe III secondo EN 676)
MOTOR
kW 0,50 0,75
r.p.m. 2730 2800
ABSORBED ELECTRICAL POWER* kW 0,67 0,69 0,93 0,96
line fuse A / 400 V - - 4
IGNITION TRANSFORMER
26 kV - 40 mA - 230/240 V - 50/60 Hz
VOLTAGE 1N ~ 230 V ±10%- 50 Hz 3N ~ 400 V ±10%- 50 Hz
PROTECTION RATING IP 44
FLAME DETECTOR IONIZATION PROBE
NOISE** dBA 73 75
WEIGHT kg 40 42
Natural Gas (G 20)
FLOW RATE
MAX m³n/h 45,3 60,3
MIN m³n/h 10,1 12,1
GAS PRESSURE MAX mbar 360
*) Total absorption at start with ignition transformer on. .
**) Noise levels measured by the manufacturer in the laboratory with burner running on test boiler, at maximum nominal thermal output.
TBG 45 TBG 45P TBG 60 TBG 60P
BURNER FIXING FLANGE 2 2 2 2
ISOLATING GASKET 1 1 1 1
STUD BOLTS 4 M 12 4 M 12 N° 4 M 12 4 M 12
EXAGONAL NUTS 4 M 12 4 M 12 N° 4 M 12 4 M 12
FLAT WASHERS 4 Ø 12 4 Ø 12 N° 4 Ø 12 4 Ø 12