Cyberpower PDU20SWHVIEC10ATNET [3/34] Switched series metered monitored series
![Cyberpower PDU32SWHVCEE18ATNET [3/34] Switched series metered monitored series](/views2/1472133/page3/bg3.png)
1
Overview
CyberPower Automatic Transfer Switches PDUs with dual input for power
provide redundant and increased reliability for critical devices with a single
power plug. Users can define the preferred input power source. When a
selected source is unstable or unavailable, the ATS PDU will switch to the
second power source to constantly provide power to connected devices. The
entire ATS PDU series are designed with LED and LCD interfaces for users
to easily observe power status and device load. On-site power management
is accomplished as users can configure power settings, via LCD interface,
according to local power condition. Available in both switched and metered/
monitored configurations, users have a broad base of options to select the
ATS PDU that best fits their needs.
WARNING: This automatic transfer switch has dual power cords (A & B) to
provide redundant power sources to devices with single power supplies and
can be plugged into separate compatible sources* to ensure continuous
access. Users select the preferred source as the primary input. CyberPower
Smart App Online and Sinewave series UPS are highly recommended for use
as the power source.
*Note: Only sine wave AC power sources are compatible with this ATS PDU.
Simulated sine wave AC power sources are NOT compatible.
Model List
Switched Series Metered/Monitored Series
1U 1U
PDU15SW10ATNET PDU15M10AT
PDU20SW10ATNET PDU20M10AT
PDU20SWT10ATNET PDU20MT10AT
PDU20SWHVT10ATNET PDU20MHVT10AT
PDU15SWHVIEC12ATNET PDU15MHVIEC12AT
PDU20SWHVIEC10ATNET PDU20MHVIEC10AT
PDU20SWHVCEE10ATNET* PDU20MHVCEE10AT*
2U 2U
PDU30SWT17ATNET PDU30MT17AT
PDU30SWHVT19ATNET PDU30MHVT19AT
PDU32SWHVCEE18ATNET* PDU32MHVCEE18AT*
*Selected models may not be available in certain regions. Please contact your
CyberPower sales team for more information.
Safety Precautions
Read the following before installing or operating the Automatic Transfer
Switches (ATS) PDU:
•
Use only the supplied hardware to attach the mounting brackets.
•
The ATS PDU must be plugged into a single phase three-wire, grounded
outlet on a circuit that is protected by a fuse or circuit breaker. For
PDU15xxxxx series, please use a 15A circuit protector. For PDU20xxxxx
series, please use a 20A circuit protector. For PDU30xxxxx series,
please use a 30A circuit protector. Connection to any other type of
power outlet may result in a electrocution hazard.
•
Do not use extension cords or adapters with these ATS PDUs.
•
Never install an ATS PDU or associated wiring or equipment during a
lightning storm.
•
Ensure that the power cord, plug, and socket are in good condition.
To prevent the risk of fire or electrocution, this ATS PDU should
be installed in a temperature and humidity controlled indoor area
free of conductive contaminants. Do not install this ATS PDU where
excessive moisture or heat is present.
Before using, please check to ensure the package contains all the
items shown below. If there are missing parts, please contact your
local CyberPower sales team for technical support.
Check
Содержание
- Automatic transfer switch 1
- User s manual 1
- Appendix a hyper terminal 28 2
- Appendix b power device network utility 29 2
- Conformance approvals 26 2
- Customer service warranty 27 2
- Firmware upgrade 0 2
- Installation guide 2
- Model list 1 2
- Operation 18 2
- Overview 1 2
- Product contents 2
- Product features 4 2
- Table of contents 2
- Troubleshooting 25 2
- Model list 3
- Overview 3
- Safety precautions 3
- Switched series metered monitored series 3
- Below items only provided with iec type ats pdu 4
- For 1u models 4
- Product contents 4
- For 2u models 5
- Product contents 5
- A snmp http network slot 6
- Allows users to remotely control and monitor the ats pdu when installed with cyberpower s remote management card 6
- B serial port rj45 modular port 6
- C source indicator 6
- D output indicator 6
- Displays various ats pdu information such as power and load conditions 6
- E multifunction lcd readout 6
- F select button 6
- Front rear panel description 1u 15a models 6
- G enter button 6
- H ac inlet ac power cord 6
- I ground stud 6
- Iec type 6
- Indicates load condition of the ats pdu 6
- Indicates source a or b is in use when both sources are normal selected source shows constant green led while another source shows blinking green led 6
- J ac output receptacles 6
- K outlet indicator switched series only 6
- Nema type 6
- Product features 6
- Provides power distribution for connected equipment 6
- Technical specifications 6
- Use serial port to connect with pc and execute local control of the ats pdu 6
- Use to choose selected items enter to next level menu or return to previous menu 6
- Use to connect ats pdu to utility power or ups 6
- Use to control the lcd screen and toggle through the available informational options 6
- Use to ground the ats pdu 6
- When the led is on the outlet is providing power to connected equipment 6
- A snmp http network slot 7
- Allows users to remotely control and monitor the ats pdu when installed with cyberpower s remote management card 7
- B serial port rj45 modular port 7
- C souce indicator 7
- D output indicator 7
- Displays various ats pdu information such as power and load conditions 7
- E multifunction lcd readout 7
- F select button 7
- Front rear panel description 1u 20a models 7
- G enter button 7
- H ac inlet ac power cord 7
- I ground stud 7
- Iec type 7
- Indicates load condition of the ats pdu 7
- Indicates source a or b is in use when both sources are normal selected source shows constant green led while another source shows blinking green led 7
- J ac output receptacles 7
- K outlet indicator switched series only 7
- Nema type 7
- Product features 7
- Provides power distribution for connected equipment 7
- Technical specifications 7
- Use serial port to connect with pc and execute local control of the ats pdu 7
- Use to choose selected items enter to next level menu or return to previous menu 7
- Use to connect ats pdu to utility power or ups 7
- Use to control the lcd screen and toggle through the available informational options 7
- Use to ground the ats pdu 7
- When the led is on the outlet is providing power to connected equipment 7
- A snmp http network slot 8
- Allows users to remotely control and monitor the ats pdu when installed with cyberpower s remote management card 8
- B serial port rj45 modular port 8
- C source indicator 8
- D output indicator 8
- Displays various ats pdu information such as power and load conditions 8
- E multifunction lcd readout 8
- F select button 8
- Front rear panel description 2u 30a models 8
- G enter button 8
- H ac inlet ac power cord 8
- I ac output receptacles provides power distribution for connected equipment 8
- Iec type 8
- Indicates load condition of the ats pdu 8
- Indicates source a or b is in use when both sources are normal selected source shows constant green led while another source shows blinking green led 8
- J outlet indicator switched series only 8
- K circuit breaker 8
- L ground stud 8
- Nema type 8
- Product features 8
- Provides output overload protection 8
- Technical specifications 8
- Use serial port to connect with pc and execute local control of the ats pdu 8
- Use to choose selected items enter to next level menu or return to previous menu 8
- Use to connect ats pdu to utility power or ups 8
- Use to control the lcd screen and toggle through the available informational options 8
- Use to ground the ats pdu 8
- When the led is on the outlet is providing power to connected equipment 8
- A snmp http network slot 9
- Allows users to remotely control and monitor the ats pdu when installed with cyberpower s remote management card 9
- B serial port rj45 modular port 9
- C source indicator 9
- D output indicator 9
- Displays various ats pdu information such as power and load conditions 9
- E multifunction lcd readout 9
- F select button 9
- Front rear panel description 2u 32a models 9
- G enter button 9
- H ac inlet ac power cord 9
- I ac output receptacles 9
- Indicates load condition of the ats pdu 9
- Indicates source a or b is in use when both sources are normal selected source shows constant green led while another source shows blinking green led 9
- J outlet indicator switched series only 9
- K circuit breaker 9
- L ground stud 9
- Product features 9
- Provides output overload protection 9
- Provides power distribution for connected equipment 9
- Technical specifications 9
- Use serial port to connect with pc and execute local control of the ats pdu 9
- Use to choose selected items enter to next level menu or return to previous menu 9
- Use to connect ats pdu to utility power or ups 9
- Use to control the lcd screen and toggle through the available informational options 9
- Use to ground the ats pdu 9
- When the led is on the outlet is providing power to connected equipment 9
- Ats pdu configuration 10
- Best configuration 10
- Installation guide 10
- Minimum acceptable configuration 10
- Note only sine wave ac power sources are compatible with this ats pdu 10
- Simulated sine wave ac power sources are not compatible 10
- Warning this automatic transfer switch has dual power cords a b to provide redundant power sources to devices with single power supplies and can be plugged into separate compatible sources to ensure continuous access users select the preferred source as the primary input cyberpower smart app online and sinewave series ups are highly recommended for use as the power source 10
- For 1u models 11
- Front mounting 11
- Installation guide 11
- For 2u models 12
- Front mounting 12
- Installation guide 12
- For 1u models 13
- Front mounting 13
- Installation guide 13
- Rear mounting 13
- Installation guide 14
- Rear mounting 14
- For 2u models 15
- Installation guide 15
- Rear mounting 15
- Installation guide 16
- Rear mounting 16
- Electrical installation 17
- Installation guide 17
- Replacing the lcd panel 17
- Input power cord 18
- Installation guide 18
- Output power cord 18
- Power cord locking for iec type ats pdu 18
- Installation guide 19
- Network installation 19
- Lcd operation 20
- Local management 20
- Operation 20
- Remote management 20
- Telnet and ssh 20
- Device reset 21
- Environmental monitoring optional 21
- Led indicators 21
- Local management 21
- Operation 21
- Unattended automatic shutdown 21
- Ats pdu 22
- Firmware upgrade 22
- Firmware upgrade 23
- Firmware upgrade 24
- Firmware upgrade 25
- Rmcard 25
- Firmware upgrade 26
- Firmware upgrade 27
- Troubleshooting 27
- Conformance approvals 28
- Customer service warranty 28
- European union 28
- Fcc warning 28
- Customer service warranty 29
- Limited warranty 29
- Appendix a hyper terminal 30
- Appendix b power device network utility 31
- Installation 31
- Overview 31
- Appendix b power device network utility 32
- Getting started 32
- Launch program 32
- Advanced settings 33
- Appendix b power device network utility 33
Похожие устройства
- Cyberpower PDU20SWHVIEC10ATNET Техническое описание
- Cyberpower PDU32SWHVCEE18ATNET Руководство пользователя
- Cyberpower PDU32SWHVCEE18ATNET Техническое описание
- Cyberpower RMCARD205 Инструкция по работе
- Cyberpower RMCARD205 Руководство пользователя
- Cyberpower RMCARD205 Техническое описание
- Cyberpower ENVIROSENSOR Руководство пользователя
- Cyberpower ENVIROSENSOR Техническое описание
- Cyberpower CPS1000EI Руководство пользователя
- Helvi РС 123 Инструкция по эксплуатации
- Helvi РС 123 Деталировка
- Helvi РС 75 Инструкция по эксплуатации
- Helvi РС 75 Деталировка
- Cyberpower CPS2000EI Руководство пользователя
- Helvi РС 63 Инструкция по эксплуатации
- Helvi РС 55 Инструкция по эксплуатации
- Helvi РС 55 Деталировка
- Helvi РС 53 Инструкция по эксплуатации
- Helvi РС 53 Деталировка
- Helvi РС 43 Инструкция по эксплуатации