5.1 Wiring on the Back
This chapter illustrates how the wiring on the back is done.
Note:
To avoid electric shock, do not alter wiring when the power is on.
As there is no power switch on the power meter, be sure to install a breaker switch on the power
cord for the meter.
Recommended wiring materials are shown below:
Connecting Terminals Wire Diameters Screw Turning Torque
Functional Power AWG 10 ~ 24 7.14 kgf - cm (0.7 N*m)
Measured Voltage AWG 10 ~ 26 7.14 kgf - cm (0.7 N*m)
Measured Current AWG 14 ~ 22 8.0 kgf - cm (0.79 N*m)
RS - 485 AWG 14 ~ 28 2.04 kgf - cm (0.2 N*m)
RTwisted pair cables must be used in cabling for RS485 communication. When connecting multiple
devices in series, the wiring method is displayed in the diagram below.
The D+ communication terminal for all devices should be connected on the same twisted pair cable. The
D - terminals should be connected on the other twisted pair cable. The insulation net is grounded. The
device on the end terminal needs to have terminal resistor (100~120Ω,0.25W) installed on it.
Wiring Diagrams
Terminal Resistor