Delta Electronics REG370A23A-21 [81/131] Multi function input command 2 mi2

Delta Electronics AFE370A43A [81/131] Multi function input command 2 mi2
Chapter 11 Description of Parameter SettingsAFE2000 Series
11-79
02 Digital Input/Output Parameters This parameter can be set during the operation.
Multi-Function Input Command 1 (MI1)
Factory Setting: 1
Multi-Function Input Command 2 (MI2)
Factory Setting: 2
Multi-Function Input Command 3 (MI3)
Factory Setting: 3
Multi-Function Input Command 4 (MI4)
Factory Setting: 4
Multi-Function Input Command 5 (MI5)
Factory Setting: 5
Multi-Function Input Command 6 (MI6)
Factory Setting: 0
Multi-Function Input Command 7 (MI7)
Factory Setting: 0
Multi-Function Input Command 8 (MI8)
Factory Setting: 0
Settings 0: Disable
1: RUN
2: STOP
3: EF1
4: RESET
5: master/slave (will be available soon)
6: enable
7: EF2
8: EF3
9: oH3
This parameter is user defined setting to select the functions for each multi-function terminal.
Summary of function settings:
Settings Functions Descriptions
0 No function Output terminal has no function
1 RUN
This terminal is a latched contact.
The terminal setting is valid when Pr.01-04=1 (control by
external terminal).
2 STOP
This terminal is a latched contact
The terminal setting is valid when Pr.01-04=1 (control by
external terminal).
3 EF1 Emergency stop 1
4 RESET
When the fault is cleared, this terminal allows AFE2000 to
perform the reset.
5 Master/Slave (not supported)-
6 Enable
If this terminal is set, AFE2000 is enabled when the
contact is triggered.
7 EF2 Emergency stop 2
8 EF3 Emergency stop 3
9 oH3
Reactor overheat warning
When this terminal is triggered on, it will signal a reactor
overheat warning.