Daikin FWC12AT [23/26] Sound data

Daikin FWC05AF [23/26] Sound data
3
1
8
• Fan coil units • Ceiling mounted cassette unit • FWC
21
Fan coil units • Ceiling mounted cassette unit • FWC
8 Sound data
8 - 1 Sound power spectrum
FWC-F (4 PIPE)
1/1 Octave Sound Power Level (dB, reference 1pW)
Overall
(dBA)
Model
Freq
125 250 500 1000 2000 4000 8000
FWC02AF
Hi
59 57 50 46 42 32 28 52
Me
58 56 47 43 38 31 27 50
Lo
57 55 46 42 36 30 26 49
FWC03AF
Hi
60 58 52 49 43 37 31 55
Me
57 55 49 45 39 33 28 52
Lo
55 53 47 42 37 32 27 50
FWC04AF
Hi
64 62 57 54 47 35 40 60
Me
60 58 54 49 42 41 39 56
Lo
59 57 52 47 40 39 37 54
FWC05AF
Hi
64 62 60 56 49 46 37 61
Me
62 60 58 53 46 42 34 59
Lo
61 59 57 51 44 38 33 57
FWC06AF
Hi
67 65 63 59 53 52 44 64
Me
66 64 61 57 51 51 42 63
Lo
65 63 60 56 49 49 41 61
Microphone position:
FWC02&03 1.4m below the the facia
FWC04~03 1.5m below the the facia
FWC-T (2 PIPE)
1/1 Octave Sound Power Level (dB, reference 1pW)
Overall
(dBA)
Model
Freq
125 250 500 1000 2000 4000 8000
FWC07AT
Hi
59 57 50 46 42 32 28 52
Me
58 56 47 43 38 31 27 50
Lo
57 55 46 42 36 30 26 49
FWC08AT
Hi
60 58 52 49 43 37 31 55
Me
57 55 49 45 39 33 28 52
Lo
55 53 47 42 37 32 27 50
FWC10AT
Hi
64 62 57 54 47 35 40 60
Me
60 58 54 49 42 41 39 56
Lo
59 57 52 47 40 39 37 54
FWC11AT
Hi
64 62 60 56 49 46 37 61
Me
62 60 58 53 46 42 34 59
Lo
61 59 57 51 44 38 33 57
FWC12AT
Hi
67 65 63 59 53 52 44 64
Me
66 64 61 57 51 51 42 63
Lo
65 63 60 56 49 49 41 61