Dungs ZRDLE 4050/5 Технические данные онлайн [2/6] 406014
![Dungs ZRDLE 415/5 Технические данные онлайн [2/6] 406011](/views2/1490438/page2/bg2.png)
2 … 6
DN 40 50
Rp 3/4 1 1 1/2 2
Connection ange as per DIN EN 1092-1
up to 360 mbar (36 kPa)
Valve as per EN 161, Class A, Group 2, two-stage mode, EN 1531
< 1 s
for ZRLE and ZRDLE approx. 20 s at approx. +20°C and without fast stroke
Manually adjustable for ZRLE and ZRDLE
Manually adjustable for ZRDLE
Manually adjustable for ZRLE and ZRDLE
Housing: aluminium, steel, brass
Seals: NBR basis
50-60 Hz, 230 V AC (+10% -15%); further voltages on request
Refer to type overview
100%
IP 54, IP 65 on request
At screw terminals via PG* 11 cable gland (* = heavy-gauge conduit thread)
ZRLE 4…/5, ZRDLE 4…/5: max. 100/h
G 1/4 ISO 228, on both sides in inlet section,
additionally G 3/4 on inlet side, from size DN 40 (ange) upwards
Sieve installed, mesh width 1 mm
-15
°
C to +60
°
C
Solenoid from vertically upright to horizontally lying
Type K01/1, DIN-tested
Type VDK 200 A S02, mountable via G 1/4 test connection, Type VPS 504,
mountable on housing Rp 3/4 to Rp 2 with adapter
K01 closed position signal contact, see Datasheet 12.01 211 202
ZRLE/5
Two-stage solenoid valve,
normally
when closed, slow opening with adjustable fast stroke, fast clos-
ing. Partial volume adjustable. Closed position signal contact mountable.
ZRDLE/5
Two-stage solenoid valve,
normally
when closed, slow opening with adjustable fast stroke, fast clos-
ing. Main volume adjustable. Partial volume adjustable. Closed position signal contact mountable.
Nominal diameters
Pipe thread as per ISO 7/1
Flange
Max. operating pressure
Solenoid valve
Closing time
Opening time
Fast stroke
Main volume adjustment
Partial volume adjustment
Materials of gas-conveying parts
Voltage/frequency
Rating / power consumption
Switch-on duration
Degree of protection
Electrical connection
Switching rate
Measuring/ignition gas connection
Dirt trap
Ambient temperature
Installation position
Closed position signal contact
Valve proving system
Accessories
Specications
Содержание
- Two stage safety solenoid valves 1
- Zrle 5 zrdle 5 1
- Stage i 5
- Stage ii 5
- D 73660 urbach germany telephone 49 0 7181 804 0 fax 49 0 7181 804 166 6
- Flow diagram 6
- Head offices and factory karl dungs gmbh co kg 6
- Postal address karl dungs gmbh co kg postfach 12 29 d 73602 schorndorf germany e mail info dungs com internet www dungs com 6
- Siemensstraße 6 10 6
- Two stage safety solenoid valves zrle 5 zrdle 5 6
- We reserve the right to make any changes in the interest of technical progress 6
Похожие устройства
- Dungs MV 502 Инструкция по эксплуатации
- Dungs MV 502 Технические данные
- Dungs MV 502/1 Инструкция по эксплуатации
- Dungs MV 502/1 Технические данные
- Dungs DMV 5065/12 Инструкция по эксплуатации
- Dungs DMV 5065/12 Технические данные
- Dungs DMV 5080/12 Инструкция по эксплуатации
- Dungs DMV 5080/12 Технические данные
- Dungs DMV 5100/12 Инструкция по эксплуатации
- Dungs DMV 5100/12 Технические данные
- Dungs DMV-DLE 5065/12 Инструкция по эксплуатации
- Dungs DMV-DLE 5065/12 Технические данные
- Dungs DMV-DLE 5080/12 Инструкция по эксплуатации
- Dungs DMV-DLE 5080/12 Технические данные
- Dungs DMV-DLE 5100/12 Инструкция по эксплуатации
- Dungs DMV-DLE 5100/12 Технические данные
- Dungs DMV-D 5065/12 Инструкция по эксплуатации
- Dungs DMV-D 5065/12 Технические данные
- Dungs DMV-D 5080/12 Инструкция по эксплуатации
- Dungs DMV-D 5080/12 Технические данные