Ecoflam MAIOR P 400.1 PR ТC [12/44] Firing head setting

Ecoflam MAIOR P 400.1 AB HS Z3 ТL [12/44] Firing head setting
12
420010258600 Maior P 300.1/400.1 AB
EN
FIRING HEAD SETTING
1
2
1234567
LANDIS SQM 50.381A2
COMBUSTION AIR FLOW ADJUSTMENT (HIGH-LOW FLAME)
Remove cover to gain access to the adjusting cams. The cams are to
be adjusted through the suitable key provided . Description:
MAIOR P 400
I - Limit switch for air damper “3rd. stage” position
adjustment (Max. power).
II - Limit switch for air damper “1st. stage” position
adjustment (Min. power).
III - Limit switch for air damper “2nd. stage” position
adjustment .
IV - Switches from 3rd stage to 2nd stage
(always 5° bigger than 2nd stage adjusting limit switch)
V - Limit switch for 2nd stages solenoid valve
opening release.
VI - Limit switch for 3rd stages solenoid valve
opening release.
VII - Limit switch “NOT USED”.
VIII - Limit switch “NOT USED”.
MAIOR P 300
I - Limit switch for air damper “2nd. stage” position
adjustment (Max. power)
II - Limit switch for air damper “1st. stage” position
adjustment (Min. power).
III - Limit switch for ignition flame position adjustment.
IV - Limit switch for 2nd stage’s solenoid valve
opening release..
V - Limit switch “NOT USED”.
VI - Limit switch “NOT USED”.
VII - Limit switch “NOT USED”.
VIII - Limit switch “NOT USED”.