Ecoflam MAIOR P 400.1 PR ТC [9/44] Burner installation

Ecoflam MAIOR P 400.1 AB HS Z3 ТL [9/44] Burner installation
9
420010258600 Maior P 300.1/400.1 AB
EN
MAXIMUM LENGTH OF SUCTION LINES FOR TWO-PIPE SYSTEM
To correct length of pipes is
calculated by summing up the
length of all vertical and hori-
zontal right sections and bends.
The static suction head will be
the distance between the non-
return valve and the burner’s
pump axle. The depression
must not be greater than 0.45
bar; should it be higher, some
damages could occur to the
pump, with consequent increa-
se in mechanical noises and
,eventually, a failure.
2
1
3
45
6
7
BURNER INSTALLATION
1 - BURNER
2 - NUT
3 - WASHER
4 - GASKET
5 - BOLT
6 - BOILER
7 - GASKET
HYDRAULIC CIRCUIT
1 - HOSE
2 - OIL FILTER
3 - OIL COCK
4 - SUCTION
5 - RETURN
1
1
2
3
H
H
H
(m)
ø 14 mm ø 16 mm
0
0,5
1
2
3
3,5
16
18
20
25
29
31
29
33
37
44
52
55
J 7
(m)
H
(m)
ø 14 mm ø 16 mm
0
0,5
1
2
3
3,5
16
14
12
7
3
1
29
26
22
14
7
4
J 7
(m)
TA2C
(m)
TA2C
(m)
Two-pipe siphon feed system
Two-pipe lift system
Pipe length
Pipe length
4
5
VS
V2
V1
V3
VS
V2
V1
4
5

Содержание

Скачать