ABB ACH550-01-031A-4+B055 [215/476] Ach550 01 user s manual

ABB ACH550-01-180A-4 [215/476] Ach550 01 user s manual
Parameter listing and descriptions 211
ACH550-01 User's Manual
1605 USER PAR SET CHG -6…6
Defines control for changing the User Parameter Set.
See parameter 9902
APPLIC MACRO.
The drive must be stopped to change User Parameter Sets.
During a change, the drive will not start.
Note: Always save the User Parameter Set after changing any
parameter settings or performing a motor identification.
Whenever the power is cycled, or parameter 9902
APPLIC MACRO is
changed, the drive loads the last settings saved. Any unsaved
changes to a user parameter set are lost.
Note: The value of this parameter (1605) is not included in the User
Parameter Sets, and it does not change if User Parameter Sets change.
Note: You can use a relay output to supervise the selection of User
Parameter Set 2.
See parameter 1401.
0 =
NOT SEL – Defines the control panel (operator keypad) as the only
control for changing User Parameter Sets (using parameter 9902).
1 =
DI1 – Defines digital input DI1 as a control for changing User
Parameter Sets.
• The drive loads User Parameter Set 1 on the falling edge of the
digital input.
• The drive loads User Parameter Set 2 on the rising edge of the
digital input.
• The User Parameter Set changes only when the drive is stopped.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for
changing User Parameter Sets.
• See
DI1 above.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as a control for
changing User Parameter Sets.
• The drive loads User Parameter Set 1 on the rising edge of the
digital input.
• The drive loads User Parameter Set 2 on the falling edge of the
digital input.
• The User Parameter Set changes only when the drive is stopped.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as a control for changing User Parameter Sets.
• See DI1(INV) above.
Code Description Range

Содержание

Скачать