Activate Drive Control Functions – EFB
Input Reference Select
Using the fieldbus to provide input references to the drive requires:
Drive parameter values set as defined below.
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Reference Scaling
Where required,
REFERENCES can be scaled. See the following, as appropriate:
Modbus Register "40002" in the "Modbus Protocol Technical Data" section.
"Reference Scaling" in the "ABB Control Profiles Technical Data" section.
"N2 Analog Output Objects" in the "N2 Protocol Technical Data" section.
The slope of points 60 and 61 in the "FLN Protocol Technical Data" section.
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN
ABB DRV
DCU
PROFILE
1102 EXT1/EXT2
SEL
8 (COMM) Reference set
selection by fieldbus.
40001 bit 11 40031 bit 5 BO5 26
1103
REF1 SEL 8 (COMM) Input reference 1 by
fieldbus.
40002 AO1 60
1106
REF2 SEL 8 (COMM) Input reference 2 by
fieldbus.
40003 AO2 61